Plan Review Details - Permit 99111208
Plan Review Stops For Permit 99111208
Review Stop    
Rev No 1 Status P Date 1999-12-13 Cont ID  
Sent By cthirben Date 1999-12-09 Time 11:11 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-11-29 Cont ID  
Sent By dpalmer Date 1999-11-29 Time 14:08 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00***********PROVISO*********************
  
 1)NOTE: AS PER 110-9/215-5 NEED TO
 SUBMIT AIC RATING OF EQUIPMENT MAINS.
 2)NOTE:INCLUDE GROUNDING ELECTRODE GOING
 BLG.STEEL AND COLD WATER PIPE.
 3)NOTE:AS PER ART;210-52D NEED TO SHOW
 REQ`D BATH CIRCUT ON PANEL SCHEDULE.
 20 AMP,#12 AWG.
 4)NOTE:AS PER ART:210-8-A-6 ALL RECEPTS.
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 5)NOTE:AS PER 210-52-C-3 NEED TO SHOW
 REQ`D RECEPTS. FOR PENINSULAR IN KITCHEN
 6)NOTE: AS PER 1996 NFPA-72
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEEPING ROOMS.
 7)NOTE: AS PER ART;210-52E WP GFI REC.
 ARE REQ`D FRONT AND BACK OF DWELLINGS.
  
 PLEASE SUBMIT FOR REVIEW AND APPROVAL
 BEFORE FIRST ROUGH ELECTRICAL
 INSPECTION IS CALLED IN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-09 Cont ID  
Sent By cthirben Date 1999-11-30 Time 11:54 Rev Time 0.00
Received By sgraham Date 2000-03-08 Time 13:03 Sent To  
Notes
2001-01-08 00:00:00PROVISO: SHOW E/F IN BATHROOMS
 SMC 503.3.1
 RETURN AIR NEEDS TO BE SHOWN

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-11-30 Cont ID  
Sent By tlarge Date 1999-11-30 Time 13:41 Rev Time 0.50
Received By tlarge Date 1999-11-30 Time 13:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-11-29 Cont ID  
Sent By tlarge Date 1999-11-29 Time 15:00 Rev Time 0.65
Received By tlarge Date 1999-11-29 Time 14:59 Sent To  
Notes
2001-01-08 00:00:00BAR SINK AND BATH #3 ARE NOT SHOWN ON
 THE SANITARY RISER DIAGRAM. COUNTYWIDE
 AMENDMENTS TO STD.PLBG.CODE SEC.104.2.1.
  
 DRY VENTS NOT PERMITTED.STACK MUST BE
 WASHED BY A FIXTURE.SPC SEC.901.2
  
 FIXTURES LOCATED DOWNSTREAM OF W.C.SHALL
 BE VENTED.SPC 913.2
  
 ONLY 2 WATER CLOSETS PERMITTED ON 3"
 BLDG.DRAIN PER SPC SEC.714.1

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 1999-12-13 Cont ID  
Sent By hpiskura Date 1999-12-13 Time 09:27 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 1999-11-30 Cont ID  
Sent By hpiskura Date 1999-11-30 Time 15:40 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00IMPACT FEE AND PROD APPROVALS NEEDED

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-11-30 Cont ID  
Sent By hpiskura Date 1999-11-30 Time 15:38 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-11-23 Cont ID  
Sent By gjoyce Date 1999-11-23 Time 08:38 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved