Plan Review Details - Permit 99111026
Plan Review Stops For Permit 99111026
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-11-30 Cont ID  
Sent By dpalmer Date 1999-11-30 Time 13:09 Rev Time 0.00
Received By dpalmer Date 1999-11-30 Time 13:09 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
  
 1)NOTE:AS PER ARTS;110-9/215-5 NEED TO
 SUBMIT AIC RATING OF EQUIPMENT MAINS.
 2)NOTE:MISSING OUTLET AS PER210-52
 3)NOTE:AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 4)NOTE;ALSO NOTE AS PER ART210-52-C-3
 REQ`D OUTLETS FOR KITCHEN COUNTERSPACE.
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 BEFORE ROUGH ELECTRICAL INSPECTION IS
 CALLED IN!!!
  
 NEED TO ALSO SUBMIT A NEW RISER DIAGRAM
 BEING LARGER AND MORE CLEAR.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-30 Cont ID  
Sent By cthirben Date 1999-11-30 Time 15:43 Rev Time 1.00
Received By cthirben Date 1999-11-30 Time 11:18 Sent To  
Notes
2001-01-08 00:00:00PROVISO: EXHAUSTING AIR INTO ATTIC OR
 CRAWL SPACE SHALL BE PROHIBITED
 SMC 501.3

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-11-24 Cont ID  
Sent By tlarge Date 1999-11-24 Time 11:01 Rev Time 0.33
Received By tlarge Date 1999-11-24 Time 11:01 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-12-07 Cont ID  
Sent By lmartine Date 1999-12-07 Time 15:49 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-11-22 Cont ID  
Sent By gjoyce Date 1999-11-22 Time 15:57 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***