Plan Review Details - Permit 99111013
| Plan Review Stops For Permit 99111013 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2000-01-25 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
1999-12-01 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-01-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-12-13 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
1999-12-13 |
Time |
12:19 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************UNSAT********************* | | | | | | 1)NOTE:PLEASE SUBMIT RISER DIAGRAM | | | SHOWING EQUIPMENT,SHOW ALL PANELS,CONDUI | | | SIZES, WIRE SIZES. GROUNDING ELECTRODE | | | SYSTEM TO INCLUDE GROUND ROD BLDG.STEEL | | | AND COLD WATER PIPE IF ANY. | | | SUBMIT AIC RATING OF EQUIPMENT MAINS, | | | BRKRS. AS PER 110-9/215-5. | | | THE RISER DIAGRAM AND PANEL SCHEDULE | | | SHOULD BE DRAWN SEPARATE FROM OTHER | | | ELEC.DRAWINGS. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW AND | | | APPROVAL. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 561-659-8096 EXT,8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
1999-12-14 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-12-14 |
Time |
11:52 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
1999-12-14 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NO MECHANICAL SHOWN FOR REVIEW PROVIDE | | | INFORMATION AT TIME OF MECHANICAL PERMIT | | | APPLICATION FOR REVIEW |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-01-27 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-01-27 |
Time |
13:16 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|