Plan Review Details - Permit 99110592
Plan Review Stops For Permit 99110592
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-12-01 Cont ID  
Sent By dpalmer Date 1999-12-01 Time 16:19 Rev Time 0.00
Received By dpalmer Date 1999-12-01 Time 16:19 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO*****************
  
 1)NOTE:NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS AND BRANCH BRKRS. AS
 PER ARTS;110-9/215-5
 2)NOTE:KITCHEN WALL MISSING OUTLET REQ`D
 AS PER 210-52
 3)NOTE:AS PER 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 4)NOTE:PLEASE SHOW ON PANEL SCHEDULE
 CIRCUT REQ`D FOR BATH(S) REQ`D AS PER
 ART;210-52D
 5)NOTE: SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 IN NEW DWELLINGS. AS PER 1993-96 NFPA-72
 2-2.1.1.1
 6)NOTE:EQUIPMENT GROUND REQ`D AFTER
 FIRST MEANS OF DISC. AND SIZED PER
 250-95
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION IS CALLED IN

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-01 Cont ID  
Sent By cthirben Date 1999-12-01 Time 14:36 Rev Time 0.00
Received By cthirben Date 1999-12-01 Time 14:37 Sent To  
Notes
2001-01-08 00:00:00PROVISO: INSTALL EXHAUST FAN IN BATHROOM

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-11-27 Cont ID  
Sent By tlarge Date 1999-11-27 Time 13:51 Rev Time 0.33
Received By tlarge Date 1999-11-27 Time 13:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-11-18 Cont ID  
Sent By tlarge Date 1999-11-18 Time 20:44 Rev Time 0.33
Received By tlarge Date 1999-11-18 Time 20:44 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-12-06 Cont ID  
Sent By fknapp Date 1999-12-06 Time 07:54 Rev Time 4.00
Received By fknapp Date 1999-12-03 Time 10:59 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR:
 ARCH TRANSOMS
 FIXED GLASS
 FRONT OUTSWING DOORS WITH SIDELITES
  
 2)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR OPTIONAL DOORS IF USED
  
 3)PER NOTE #11 20 GA STORM PANEL
 EVALUATION REPORT TO BE SIGN,DATED AND
 HAVE RAISED SEAL TO BE VALID FOR PERMIT.
  
 4)IF GLASS BLOCK OPTION TO BE USED
 PROVIDE FIRE RATING OF 1 HOUR.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION.
  
 5)PROVIDE TRUSS ENGINEERING SHEETS THAT
 MATCHES THE TRUSS PLACEMENT PLAN.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-11-18 Cont ID  
Sent By gjoyce Date 1999-11-18 Time 14:12 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***