Plan Review Details - Permit 99110589
Plan Review Stops For Permit 99110589
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-12-08 Cont ID  
Sent By dpalmer Date 1999-12-08 Time 16:32 Rev Time 0.00
Received By dpalmer Date 1999-12-08 Time 16:31 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
  
 1)NOTE: AS PER 110-9/215-5 NEED TO
 AIC RATING OF EQUIPMENT MAINS/BRKRS.
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
  
 2)NOTE:AS PER ART;210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
  
 3)NOTE:PLEASE DRAW IN DISC. REQ`D FOR
 A/C COND. UNIT AS PER 440-11.
  
 4)NOTE:RISER DIAGRAM SHOWS MAIN DISC.
 PLANS ONLY SHOW METER?? PLEASE CORRECT.
  
 5)NOTE:AS PER 1993/1996 NFPA-72
 CHAPTER 2-2.1.1.1 SMOKE DETECTORS ARE
 REQ`D INSIDE AND OUTSIDE ALL SLEEPING
 ROOMS IN NEW DWELLINGS.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE ROUGH
 ELECTRICAL INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-02 Cont ID  
Sent By cthirben Date 1999-12-02 Time 10:59 Rev Time 0.50
Received By cthirben Date 1999-11-22 Time 16:04 Sent To  
Notes
2001-01-08 00:00:00PROVISO: INSTALL EXHAUST FAN IN BATHROOM

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-11-27 Cont ID  
Sent By tlarge Date 1999-11-27 Time 13:50 Rev Time 0.33
Received By tlarge Date 1999-11-27 Time 13:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-11-18 Cont ID  
Sent By tlarge Date 1999-11-18 Time 20:44 Rev Time 0.33
Received By tlarge Date 1999-11-18 Time 20:44 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-12-10 Cont ID  
Sent By jcaloger Date 1999-12-10 Time 09:55 Rev Time 2.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-11-18 Cont ID  
Sent By gjoyce Date 1999-11-18 Time 14:13 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***