Plan Review Details - Permit 99110470
Plan Review Stops For Permit 99110470
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-12-14 Cont ID  
Sent By jcaloger Date 1999-12-14 Time 14:34 Rev Time 2.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-04-10 Cont ID  
Sent By jleahy Date 2000-04-10 Time 12:28 Rev Time 0.00
Received By jleahy Date 2000-04-10 Time 12:56 Sent To  
Notes
2001-01-08 00:00:001- NOW PLANS DO NOT SHOW RISER DIAGRAM
  
 2-NO LOAD CALC FOR TRANSFORMER IF THERE
 IS ONE?
  
 3-MDP FAULT CURRENT RATIUNG IS NOT SHOWN
  
 4-SEE ORIGINAL NOTES FROM 11/12/99 REVIE

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-11-16 Cont ID  
Sent By jleahy Date 1999-11-16 Time 09:07 Rev Time 0.00
Received By jleahy Date 2000-04-10 Time 12:18 Sent To  
Notes
2001-01-08 00:00:001- PROVIDE A LOAD CALCULATION FOR TRANS.
 #T1215-5
  
 2-THE LOAD SIDE OF TRANS. #T3 HAS TO BE
 WITHIN 25' OF PANEL F240-21
  
 3-NEED FAULT CURRENT FOR MDP110-9
  
 4-SERVICES ARE TO HAVE PLAQUES STATING
 SERVICE ONE OF TWO WITH THE LOCATION
 OF THE OTHER SERVICE AND TWO OF TWO
 WITH THE LOCATION OF THE OTHER SERVICE
 PER 230-2B!!!!!!!!!!!!!!!!!!!!!!!!!
  
 5-SUBMIT THE REQUESTED PRIOR TO FINAL
 SO PLANS WILL BE ON JOB FOR THE FINAL

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 1999-12-14 Cont ID  
Sent By jcaloger Date 1999-12-14 Time 14:35 Rev Time 0.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-12-03 Cont ID  
Sent By rturnque Date 1999-12-03 Time 13:34 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-04-12 Cont ID  
Sent By ndenmark Date 2000-04-12 Time 06:53 Rev Time 0.33
Received By ndenmark Date 2000-04-12 Time 06:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-23 Cont ID  
Sent By ndenmark Date 1999-11-23 Time 07:38 Rev Time 0.25
Received By ndenmark Date 1999-11-23 Time 07:37 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 COMPUTER ROOM WALLS ARE RATED (SEE A-1)
 DUCTS PENETRATING RATED WALLS TO BE
 PROTECTED BY FIRE DAMPERS PER 1997 SMC
 610.1.2

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-04-01 Cont ID  
Sent By tlarge Date 2000-04-01 Time 07:03 Rev Time 0.65
Received By tlarge Date 2000-04-01 Time 07:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-11-20 Cont ID  
Sent By tlarge Date 1999-11-20 Time 10:12 Rev Time 0.65
Received By tlarge Date 1999-11-20 Time 10:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 1999-12-14 Cont ID  
Sent By jcaloger Date 1999-12-14 Time 14:34 Rev Time 0.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***