Plan Review Details - Permit 99110434
Plan Review Stops For Permit 99110434
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-02-02 Cont ID  
Sent By hpiskura Date 1999-12-01 Time 07:54 Rev Time 0.00
Received By lmartine Date 1999-11-30 Time 16:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-05-03 Cont ID  
Sent By dpalmer Date 2000-05-03 Time 08:55 Rev Time 0.00
Received By dpalmer Date 2000-05-03 Time 08:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-11-29 Cont ID  
Sent By jleahy Date 1999-11-29 Time 12:08 Rev Time 0.45
Received By jleahy Date 1999-11-29 Time 12:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-11-21 Cont ID  
Sent By rturnque Date 1999-11-21 Time 13:06 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE PLANS AND PERMIT FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-23 Cont ID  
Sent By ndenmark Date 1999-11-23 Time 11:45 Rev Time 0.25
Received By ndenmark Date 1999-11-23 Time 11:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-05-04 Cont ID  
Sent By tlarge Date 2000-05-04 Time 17:57 Rev Time 0.33
Received By tlarge Date 2000-05-04 Time 17:57 Sent To  
Notes
2001-01-08 00:00:00ADD WATER HEATER AND FLOOR SINK.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-02-02 Cont ID  
Sent By tlarge Date 2000-02-02 Time 11:36 Rev Time 0.33
Received By tlarge Date 2000-02-02 Time 11:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2000-02-02 Cont ID  
Sent By tlarge Date 1999-12-23 Time .4:12 Rev Time 0.75
Received By tlarge Date 1999-12-23 Time 14:11 Sent To  
Notes
2001-01-08 00:00:00STAFF LOUNGE SINK SHALL COMPLY FULLY W/
 FACBC SEC.4.24.1.- 4.24.7.
  
 WOMEN'S TOILET STALL SHALL COMPLY W/
 FACBC SEC.4.17.3(SEE EXCEPTION:NEW
 CONSTRUCTION)
  
 DOOR ON TOILET STALL IN WOMEN'S R.R.
 DOESN'T PERMIT USE OF WATER CLOSET.
 COMPLY W/SPC SEC.404.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 SIZE OF VENTING FOR PLBG.FIXTURES SHALL
 COMPLY W/SPC TABLE 920.2.
  
 NOT MORE THAN 2 WATER CLOSETS PERMITTED
 ON 3" BUILDING DRAIN PER TABLE 714.1,
 FOOTNOTE #3.
  
 RELIEF VALVE DRAIN SHALL DISCHARGE TO A
 FLOOR SINK/WASTE RECEPTOR TO PREVENT
 SPLASHING.SPC SEC.507.8.4.
  
 SUBMIT OCCUPANT LOAD AND SQ.FOOTAGE OF
 SPACE TO ENSURE COMPLIANCE W/SPC TABLE
 407.
  
 WALLS AND FLOORS IN TOILET ROOMS SHALL
 COMPLY W/SBC SEC.1204.2.
  
 *****NOTE:THESE ARE THE EXACT SAME
 COMMENTS EXCEPT ONE FROM PLAN REVIEW
 DATED 11/24/99 AND NOT ONE ITEM HAS BEEN
 CORRECTED.DO NOT RESUBMIT THESE PLANS
 FOR PLUMBING REVIEW UNTIL ALL ITEMS
 HAVE BEEN CORRECTED ACCORDING TO THE
 STANDARD PLBG.AND BUILDING CODE.

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-02-02 Cont ID  
Sent By tlarge Date 1999-11-24 Time 14:19 Rev Time 0.75
Received By tlarge Date 1999-11-24 Time 14:19 Sent To  
Notes
2001-01-08 00:00:00STAFF LOUNGE SINK SHALL BE ACCESSIBLE
 PER FACBC SEC.4.24.1- 4.24.7.
  
 WOMENS TOILET STALL SHALL COMPLY W/FACBC
 SEC.4.17.3
 (SEE EXCEPTION:NEW CONSTRUCTION.)
  
 DOOR ON TOILET STALL IN WOMEN'S R.R.DOES
 NOT PERMIT USE OF FIXTURE.COMPLY W/SPC
 SEC.404.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 SIZE OF VENTING FOR PLBG.FIXTURES SHALL
 COMPLY W/SPC TABLE 920.2.
  
 MORE THAN 2 W.C.'S NOT PERMITTED ON 3"
 BUILDING DRAIN.SPC TABLE 714.1,FOOTNOTE
 #3.
  
 RELIEF VALVE DRAIN SHALL DISCHARGE TO A
 FLOOR SINK/WASTE RECEPTOR TO PREVENT
 SPLASHING.SPC 507.8.4.
  
 SUBMIT OCCUPANT LOAD AND SQ.FOOTAGE OF
 SPACE TO ENSURE COMPLIANCE W.SPC SEC.
 TABLE