Plan Review Details - Permit 99110337
Plan Review Stops For Permit 99110337
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-11-30 Cont ID  
Sent By hpiskura Date 1999-11-30 Time 08:00 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 1999-12-20 Cont ID  
Sent By dpalmer Date 1999-12-20 Time 07:09 Rev Time 0.00
Received By dpalmer Date 1999-12-20 Time 07:09 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO******************
  
 NEED TO CHANGE PLANS TO MEET ORIGINAL
 NOTES PER J LEAHY.
  
 SEE NOTES PER JL ON FIRST REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-11-10 Cont ID  
Sent By jleahy Date 1999-11-10 Time 10:42 Rev Time 0.45
Received By jleahy Date 1999-11-10 Time 10:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-11-10 Cont ID  
Sent By rturnque Date 1999-11-10 Time 15:39 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-12-15 Cont ID  
Sent By cthirben Date 1999-12-15 Time 14:18 Rev Time 0.50
Received By cthirben Date 1999-12-15 Time 14:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-17 Cont ID  
Sent By ndenmark Date 1999-11-17 Time 07:34 Rev Time 0.33
Received By ndenmark Date 1999-11-17 Time 07:34 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 DUCT SMOKE DETECTOR TO BE TIED TO BLDG
 FIRE ALARM OR IF NO BLDG FIRE ALARM SYST
 EM, TIED TO HORN AND STROBE FOR NOTIFI-
 CATION PER NFPA 4-4.4.2 OR 4-4.4.3
 AREAS WITH 300 CFM OR MORE TO HAVE R/A
 FROM AREA

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-12-17 Cont ID  
Sent By pschmitz Date 1999-12-17 Time 16:06 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO, FOR ADA REQ.

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-12-08 Cont ID  
Sent By tlarge Date 1999-12-08 Time 06:02 Rev Time 0.65
Received By tlarge Date 1999-12-08 Time 06:02 Sent To  
Notes
2001-01-08 00:00:00SHT.ME-2-GENEREAL REFERENCES TO CODE ARE
 NOT PERMITTED PER COUNTYWIDE AMENDMENTS
 TOP SPC SEC.104.2.1.
  
 A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.THERE IS NO EXCEPTION.
  
 SIZE OF HANDICAP STALLS SHALL COMPLY W/
 FACBC SEC.4.1.6(B),4.17.3.
  
 LOCATION OF PLBG.FIXTURES ON SANITARY
 RISER SHALL MATCH FLOOR PLAN.(SEE LAV.IN
 WOMEN'S RESTROOM.CITY OF WPB AMENDMENTS
 TO SPC SEC.104.2.1.
  
 BREAKROOM SINK SHALL COMPLY W/FACBC
 SECS.4.24.1.-4.24.7.(MAX.HT.TO BE 34")

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-11-16 Cont ID  
Sent By tlarge Date 1999-11-16 Time 09:16 Rev Time 1.00
Received By tlarge Date 1999-11-16 Time 09:16 Sent To  
Notes
2001-01-08 00:00:00BREAKROOM SINK SHALL COMPLY W/FACBC SEC.
 4.24.1- 4.24.7.
  
 A DRINKING FOUNTAIN IS REQD.PER TABLE
 407 AND SHALL BE HANDICAP ACCESSIBLE PER
 FACBC 4.1.3(10)(A),4.15.
  
 WIDTH OF HANDICAP STALLS SHALL COMPLY W/
 FACBC SEC.4.17.3(SEE EXCEPTION:NEW
 CONSTRUCTION.)
  
 URINAL SHALL BE HANDICAP ACCESSIBLE AND
 COMPLY W/FACBC SEC.4.18.1- 4.18.4.
  
 FLOOR DRAINS SHALL BE EQUIPPED W/TRAP
 PRIMERS.SPC SEC.409.4.1.1.
  
 LAV.IN WOMEN'S R.R.MISSING FROM SANITARY
 RISER.
  
 VENT FOR URINAL CANNOT INCREASE IN SIZE.
 SPC 905.2.,904.3.1.
  
 OVER 2 FIXTURES SUPPLIED BY 1/2"COLD
 WATER.MODELWIDE AMENDMENTS TO STD.PLBG
 CODE SEC.607.7