Plan Review Details - Permit 99110283
Plan Review Stops For Permit 99110283
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-12-13 Cont ID  
Sent By jcaloger Date 1999-12-13 Time 16:45 Rev Time 2.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-11-10 Cont ID  
Sent By jleahy Date 1999-11-10 Time 10:14 Rev Time 0.00
Received By jleahy Date 2000-02-24 Time 11:01 Sent To  
Notes
2001-01-08 00:00:001- NEED LOAD CALCULATIONS
  
 2- NEED TO SHOW BRANCH CIRCUIT NUMBERS
 ON PLAN (# OF LIGHTS OR OUTLETS)
  
 3- NEED PANEL SCHEDULES

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 1999-12-13 Cont ID  
Sent By jcaloger Date 1999-12-13 Time 16:45 Rev Time 0.50
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-11-08 Cont ID  
Sent By rturnque Date 1999-11-08 Time 14:46 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE PERMIT AND SHOP DRAWINGS FOR FIR

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-09 Cont ID  
Sent By ndenmark Date 1999-11-09 Time 10:32 Rev Time 0.25
Received By ndenmark Date 1999-11-09 Time 10:32 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR REQ
 UIRED W/ NOTIFICATION BY BLDG FIRE ALARM
 PER NFPA 4-4.4.2

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-01-07 Cont ID  
Sent By tlarge Date 2000-01-07 Time 17:10 Rev Time 0.25
Received By tlarge Date 2000-01-07 Time 17:10 Sent To  
Notes
2001-01-08 00:00:00PLBG.REVISIONS TO SANITARY.

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-11-29 Cont ID  
Sent By tlarge Date 1999-11-29 Time 08:56 Rev Time 0.33
Received By tlarge Date 1999-11-29 Time 08:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-12-13 Cont ID  
Sent By tlarge Date 1999-11-15 Time 09:30 Rev Time 0.65
Received By jcaloger Date 1999-11-15 Time 09:30 Sent To  
Notes
2001-01-08 00:00:00SUBMIT WATER RISER DIAGRAM FOR REVIEW
 PER COUNTYWIDE AMENDMENTS TO STD.PLBG.
 CODE SEC.104.2.1.
  
 BREAKROOM SINKS SHALL COMPLY W/FACBC
 SEC.4.24.- 4.24.7.

Review Stop Z ZONING
Rev No 1 Status N Date 1999-12-13 Cont ID  
Sent By jcaloger Date 1999-12-13 Time 16:50 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***