Plan Review Details - Permit 99110257
Plan Review Stops For Permit 99110257
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-11-22 Cont ID  
Sent By hpiskura Date 1999-11-22 Time 07:57 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-04-24 Cont ID  
Sent By dpalmer Date 2000-04-24 Time 14:47 Rev Time 0.00
Received By dpalmer Date 2000-04-24 Time 14:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-04-05 Cont ID  
Sent By dpalmer Date 2000-04-05 Time 21:28 Rev Time 0.00
Received By dpalmer Date 2000-04-05 Time 21:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-11-09 Cont ID  
Sent By jleahy Date 1999-11-09 Time 10:28 Rev Time 1.00
Received By jleahy Date 1999-11-09 Time 10:17 Sent To  
Notes
2001-01-08 00:00:001- PROVIDE RISER DIAGRAM
  
 2- PROVIDE AIC RATINGS FOR PANELS AND
 CIRCUITS BREAKERS

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-11-08 Cont ID  
Sent By rturnque Date 1999-11-08 Time 14:58 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE PERMIT AND SHOP DRAWINGS FOR
 FIRE SPRINKLER SYSTEM AND FIRE ALARM
 SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-17 Cont ID  
Sent By ndenmark Date 1999-11-17 Time 15:51 Rev Time 0.33
Received By ndenmark Date 1999-11-17 Time 15:51 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
 DUCT SMOKE DETECTOR TO BE TIED TO BLDG
 FIRE FOR NOTIFICATION PER NFPA 90A 4-4.4
 .2 OR HORN AND STROBE PER 4-4.4.3 IF NO
 BLDG FIRE ALARM SYSTEM

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-04-26 Cont ID  
Sent By pschmitz Date 2000-04-26 Time 20:20 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO; WTRHTR TO BE READLY ACESIBLE.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-11-12 Cont ID  
Sent By tlarge Date 1999-11-12 Time 17:00 Rev Time 0.75
Received By tlarge Date 1999-11-12 Time 17:00 Sent To  
Notes
2001-01-08 00:00:00PROVISO:DRINKING FOUNTAIN SHALL COMPLY
 W/FACBC SEC.4.1.3(10)(A).