Plan Review Details - Permit 99101414
Plan Review Stops For Permit 99101414
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-03-07 Cont ID  
Sent By hpiskura Date 2001-03-07 Time 09:01 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-03-07 00:00:00PLEASE PROVIDE A TEST REPORT FROM A
 RECOGNIZED AGENCY THAT THE TYPE
 PARTITION IS SUITABLE FOR AN EXTERIOR
 WALL APPLICATION, INCLUDING THE
 WINDLOADS IN SBC 16 OR A DETAILED
 ENGINEERING ANALYSIS DEMONSTRATING SAME.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-12-18 Cont ID  
Sent By jwitmer Date 2000-12-18 Time 13:28 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISIONS: Z CORRIDOR REVISIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-10-27 Cont ID  
Sent By sgraham Date 1999-10-27 Time 10:39 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-12-14 Cont ID  
Sent By dpalmer Date 2000-12-14 Time 22:00 Rev Time 0.00
Received By dpalmer Date 2000-12-14 Time 22:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-09-01 Cont ID  
Sent By dpalmer Date 2000-09-01 Time 15:40 Rev Time 0.00
Received By dpalmer Date 2000-09-01 Time 15:40 Sent To  
Notes
2001-01-08 00:00:00SHEETS1.2 1.3 5.2 1.2

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-01 Cont ID  
Sent By dpalmer Date 2000-08-01 Time Y8:36 Rev Time 0.00
Received By dpalmer Date 2000-08-01 Time 08:36 Sent To  
Notes
2001-01-08 00:00:00ONLY FOR TWO E- SHEETS E-1.1 E-5.2

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-03-29 Cont ID  
Sent By jleahy Date 2000-03-29 Time 12:55 Rev Time 2.30
Received By jleahy Date 2000-03-29 Time 12:54 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-01-26 Cont ID  
Sent By dlauderm Date 2000-01-26 Time 10:14 Rev Time 1.00
Received By dlauderm Date 2000-01-26 Time 10:13 Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISO:
 THE CITY CAN NOT PICK UP A 17 CUBIC YARD
 DUMPSTER AS SHOWN ON SHEET A5.6B.THIS
 DUMPSTER WILL NEED TO BE PICKED UP BY TH
 SANITATION COMPANY THAT HAS THE AREA THI
 BUILDING IS LOCATED IN. IT COULD BE EITH
 WASTE MANAGEMENT OR BFI.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-03-09 Cont ID  
Sent By mcarsill Date 2001-03-09 Time 15:12 Rev Time 0.00
Received By mcarsill Date 2001-03-09 Time 15:12 Sent To  
Notes
2001-03-09 00:00:00REVISION # 20.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-11-27 Cont ID  
Sent By mcarsill Date 2000-11-27 Time 10:12 Rev Time 0.00
Received By mcarsill Date 2000-11-27 Time 10:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-08-09 Cont ID  
Sent By mcarsill Date 2000-08-09 Time 13:47 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) EXITING THROUGH LOADING DOCK NOT
 ACCEPTABLE. OVERHEAD DOOR NOT ACCEPTABLE
 FOR EXITING AT LOADING DOCK AREA.
 2) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, 1985 EDITION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-01-19 Cont ID  
Sent By rturnque Date 2000-01-19 Time 15:07 Rev Time 0.55
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-12-20 Cont ID  
Sent By ndenmark Date 2000-12-20 Time 08:21 Rev Time 0.50
Received By ndenmark Date 2000-12-20 Time 08:21 Sent To  
Notes
2001-01-08 00:00:00REVISION DATED 12/20/00 OK THIS PERMIT
 IS A SHELL BUILDING

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-29 Cont ID  
Sent By ndenmark Date 2000-08-29 Time 06:44 Rev Time 0.50
Received By ndenmark Date 2000-08-29 Time 06:44 Sent To  
Notes
2001-01-08 00:00:00REVISION INDICATING UNITS AND DUCTWORK
 FOR INFORMATION PURPOSES ONLY

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-23 Cont ID  
Sent By ndenmark Date 2000-03-23 Time 07:00 Rev Time 2.00
Received By ndenmark Date 2000-03-23 Time 07:00 Sent To  
Notes
2001-01-08 00:00:00THIS REVIEW IS FOR REVISIONS ONLY

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-12-10 Cont ID  
Sent By pschmitz Date 2000-12-10 Time 12:09 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISIONS FOR FLRS 3,4,5,ROOF,SHELL.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-08-30 Cont ID  
Sent By tlarge Date 2000-08-30 Time 19:44 Rev Time 0.50
Received By tlarge Date 2000-08-30 Time 19:44 Sent To  
Notes
2001-01-08 00:00:001)DISCHARGE PIPING FROM SUMP SHALL
 COMPLY W/SPC 717.2.SUBMIT ISOMETRIC
 DRAWING OF PIPING.
  
 2)CONNECTION TO BUILDING DRAINAGE
 SYSTEM SHALL COMPLY W/SPC SEC.717.11.
  
 3)LOCATION OF REQD.CHECK AND GATE VALVE
 SHALL COMPLY W/SPC 717.2.
  
 THIS REVIEW IS FOR SHT.P1.1.ONLY.
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-05-06 Cont ID  
Sent By pschmitz Date 2000-05-06 Time 09:20 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING REVISION 4-24-00 REVIEW
 (1) SHT A10.3 SUBMIT HEIGHTDEMINISONS
 FOR ALL HANDI-CAP FIXTURES, FACBC-97
 (2) SHT P1.1 CLEARLY SHOW INDIRECT WASTE
 TERMINATION OF OIL INTERCEPTOR TO
 SANITARY DRAIN THRU A FLOOR SINK IN
 THE LOADING DOCK.
 (3) SHT A10.3 RE: HANDI CAP, GENERAL
 NOTE NOT ACCEPTABLE. PALM BCH CNTY
 AMENDMENTS SEC. 104.2.1
 END OF COMMENTS

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-03-24 Cont ID  
Sent By tlarge Date 2000-03-24 Time 13:04 Rev Time 3.50
Received By tlarge Date 2000-03-24 Time 12:47 Sent To  
Notes
2001-01-08 00:00:00SIZE OF HANDICAP STALLS DO NOT COMPLY W/
 FACBC.COMPLY W/FACBC SEC.4.17.3.(SEE
 EXCEPTION:NEW CONSTRUCTION)
  
 SUBMIT ELEVATION DETAILS FOR ALL HANDI-
 CAP FIXTURES.COMPLY W/FACBC 1997 EDITION
  
 CLEARLY SHOW TERMINATION POINT OF SUMP
 DRAIN IN ELEVATOR.DRAIN SHALL CONNECT TO
 SANITARY SYSTEM THROUGH AN INDIRECT
 WASTE.IF ELEVATOR IS HYDRAULIC,AN OIL
 INTERCEPTOR WILL BE REQD.SPC SEC.1004.5.
  
 FLOOR DRAINS NOT PERMITTED ON STORM
 DRAIN PER SPC SEC.1106.4.
  
 SHT.P4.1-RELIEF LINE AND PAN DRAIN SHALL
 DISCHARGE TO EXTERIOR PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.507.6.