Plan Review Details - Permit 99100989
Plan Review Stops For Permit 99100989
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-11-29 Cont ID  
Sent By dpalmer Date 1999-11-29 Time 12:48 Rev Time 0.00
Received By dpalmer Date 1999-11-29 Time 12:51 Sent To  
Notes
2001-01-08 00:00:00NEED TO SUBMIT AIC RATING OF MAINS AND
 EQUIPMENT. AS PER 110-9/215-5
 NEED TO SHOW GROUNDING ELECTRODE CONDUCT
 GOING TO BLDG. STEEL ASLO. AS PER 250-81
 MISSING REC IN MASTER BATH GFI AS REQ`D
 PER 210-52D AND ATLEAST ONE 20AMP CIRCUT
 REQ`D TO BE LISTED ON PANEL SCHED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-28 Cont ID  
Sent By jleech Date 1999-10-28 Time 15:22 Rev Time 0.50
Received By jleech Date 1999-10-28 Time 15:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-11-30 Cont ID  
Sent By tlarge Date 1999-11-30 Time 18:41 Rev Time 0.33
Received By tlarge Date 1999-11-30 Time 18:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-10-28 Cont ID  
Sent By tlarge Date 1999-10-28 Time 06:09 Rev Time 0.50
Received By tlarge Date 1999-10-28 Time 06:09 Sent To  
Notes
2001-01-08 00:00:00FIXTURES ARE NOT PROPERLY VENTED PER SPC
 901.2 AND ISOMETRIC SHALL CORRELATE W/
 THE FLOOR PLAN.SPC 104.2.1.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-12-01 Cont ID  
Sent By jcaloger Date 1999-11-29 Time 11:09 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS IMPACT FEES PAID

Review Stop Z ZONING
Rev No 1 Status P Date 1999-10-26 Cont ID  
Sent By gjoyce Date 1999-10-26 Time 13:46 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***