| Plan Review Stops For Permit 99100932 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-10-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-10-21 |
Time |
05:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
1999-10-21 |
Time |
05:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************PROVISO****************** | | | | | | 1)NOTE:PAGE E-19 ALL PANELS AT DETACHED | | | STRUCTURES,,G2,CW,G1,,,ARE TO HAVE | | | GROUND RODS,FOOTER STEEL AND COLD WATER | | | BOND (IF ANY).AS PER 250-24/250-81 | | | 2)NOTE:SERVICE TO TC SHOWS EQUIPMENT | | | GROUNDS BEING INSTALLED FROM METER/GUTT- | | | -ER TO FIRST MEANS OF DISC!!!?? | | | EQUIPMENT GROUND IS ONLY TO BE INSTALLED | | | AFTER FIRST MEANS OF DISC. | | | 3)NOTE:AS PER 215-5 ELECTRICAL RISER | | | FOR G-2 AND PANEL FOR G-2 NEED TO MATCH | | | FOR CONDUIT SIZE FEEDING PANEL CW!! | | | 4)NOTE:PAGE E-20 GATE HOUSE SERVICE.... | | | GROUNDING ELECTRODE CONDUCTOR IS TO GO | | | TO COLD WATER BOND (IF ANY). | | | 5)NOTE,NOTE:ALL DISC.MEANS AT DETACHED | | | STRUCTURES SHALL BE CLEARLY LABELED AS | | | TO WHERE FEEDS ARE FROM!!! | | | | | | NEED TO SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL BEFORE FIRST | | | ROUGH ELECTRICAL INSPECTION IS CALLED IN |
|
|