Plan Review Details - Permit 99100920
Plan Review Stops For Permit 99100920
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-11-18 Cont ID  
Sent By lmartine Date 1999-11-18 Time 07:08 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-20 Cont ID  
Sent By dpalmer Date 1999-10-20 Time 18:40 Rev Time 0.00
Received By dpalmer Date 1999-10-20 Time 18:40 Sent To  
Notes
2001-01-08 00:00:00***********PROVISO**********************
  
 1)NOTE:PAGE E-19 ALL PANELS THAT ARE
 FED FROM OTHER STRUCTURES NEED TO HAVE
 SEPARATE GROND RODS,FOOTER STEEL AND
 COLD WATER PIPE(IF ANY) AS PER ARTS:
 250-24A/250-81
 2)NOTE:SERVICE FOR TRASH COMPACTOR SHOWS
 EQUIPMENT GROUND BEING INSTALLED FROM
 GUTTER/METER TO FIRST MEANS OF DISC.
 EQUIPMENT GROUND IS ONLY TO BE INSTALLED
 AFTER FIRST MEANS OF DISC.
 3)NOTE:PANEL G-1 REQ`S SEPARATE GROUND-
 -ING.250-24A /250-81
 4)NOTE:PANEL G-2 SHOWS 3/4 INCH CONDUIT,
 PLEASE CHANGE TO 1"AS SHOWN ON RISER.
 5)NOTE:PAGE E-20 GROUNDING ELECTRODE
 CONDUCTOR TO GO TO CWP(IFANY)
  
 NOTE:DETACHED STRUCTURES TO BE LABELED
 AS TO WHERE FEEDS ARE FROM.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW AND
 APPROVAL BEFORE FIRST ROUGH ELECTRICAL
 INSPECTION IS CALLED IN.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-23 Cont ID  
Sent By tlarge Date 1999-10-23 Time 07:40 Rev Time 0.33
Received By tlarge Date 1999-10-23 Time 07:40 Sent To  
Notes
***NONE***