Plan Review Details - Permit 99100641
Plan Review Stops For Permit 99100641
Review Stop E ELECTRICAL
Rev No 2 Status P Date 1999-12-22 Cont ID  
Sent By fknapp Date 1999-12-22 Time 10:10 Rev Time 0.00
Received By fknapp Date 1999-12-22 Time 10:10 Sent To  
Notes
2001-01-08 00:00:00APPROVED PER D PALMER

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1999-11-08 Cont ID  
Sent By jleahy Date 1999-11-08 Time 09:43 Rev Time 0.45
Received By jleahy Date 1999-11-08 Time 09:39 Sent To  
Notes
2001-01-08 00:00:001-NEED LOAD CALCULATION FOR EXISTING
 SERVICE. SHOW ADDITIONAL LOADS!!!!
  
 2-NEED PANEL SCHEDULE.
  
 3-NEED RISER DIAGRAM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 1999-12-20 Cont ID  
Sent By ndenmark Date 1999-12-20 Time 07:38 Rev Time 0.25
Received By ndenmark Date 1999-12-20 Time 07:37 Sent To  
Notes
2001-01-08 00:00:00NO MECH INCLUDED PROVIDE INFORMATION AT
 TIME OF MECHANICAL PERMIT APPLICATION
 FOR REVIEW PRIOR TO ANY MECHANICAL WORK
 AT SITE

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-12-20 Cont ID  
Sent By tlarge Date 1999-12-20 Time 16:39 Rev Time 0.30
Received By tlarge Date 1999-12-20 Time 16:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-12-18 Cont ID  
Sent By pschmitz Date 1999-12-18 Time 07:44 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED SHOW LOCATION OF PLBG FIXTURES,
 ON PLAN VIEW.
 ISOMETRIC NOT DRAWING TO CODE.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 1999-12-22 Cont ID  
Sent By fknapp Date 1999-12-22 Time 09:28 Rev Time 4.00
Received By fknapp Date 1999-12-22 Time 09:28 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 1999-12-08 Cont ID  
Sent By fknapp Date 1999-12-08 Time 08:25 Rev Time 3.00
Received By fknapp Date 1999-12-08 Time 08:25 Sent To  
Notes
2001-01-08 00:00:00 
  
 ****************DENIED******************
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR:
 NEW EXTERIOR DOORS
 ROOF COVERING
 MISSILE IMPACT PROTECTION INFO
  
 2)PROVIDE ENERGY CODE CALCULATIONS
  
 3)PROVIDE NAME AND ADDRESS OF DESIGNER
  
 4)PROVIDE DIMEMSIONS OF FOOTINGS
  
 5)PROVIDE BEAM HEIGHT ELEVATIONS
  
 6)PROVIDE ROOF FRAMING PLAN WITH DETAILS
 OF ALL CONNECTORS
  
 7)PROVIDE ROOF SHEATHING NAILING ZONES
 THAT COMPLIES WITH SBC FIG.2306.1
  
 8)PROVIDE ROOF VENTILATION SBC 2309.7.2
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED,IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-11-02 Cont ID  
Sent By gjoyce Date 1999-11-02 Time 08:56 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***