Plan Review Details - Permit 99100485
Plan Review Stops For Permit 99100485
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-10-28 Cont ID  
Sent By hpiskura Date 1999-10-28 Time 14:33 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-11-05 Cont ID  
Sent By dpalmer Date 1999-10-19 Time 10:31 Rev Time 0.00
Received By tlarge Date 1999-10-19 Time 10:31 Sent To  
Notes
2001-01-08 00:00:00U*************UNSAT********************
  
 1)NOTE:AS PER ART;210-70 NEED TO SHOW
 EGRESS LIGHTING FROM SECOND FLOOR AND
 FROM FIRST FLOOR FRONT ROOM.MAYBE ON
 3-WAY FROM FRONT ENTRY.
 2)NOTE:AS PER ART;210-63 NEED WP GFI REC
 FOR A/C EQUIPMENT .
 3)NOTE:AS PER ARTS;215-5/110-9 NEED TO
 SHOW COMPLETE RISER DIAGRAM TO INCLUDE
 METER,MAINS,PANEL(S) GROUNDING SYSTEM,
 CONDUIT SIZES, WIRE SIZES ETC.
 NEED TO SUBMIT THE AIC RATING OF THE
 EQUIPMENT AND BREAKERS.AIC RATING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS.
 NEED TO SUBMIT COMPLETE PANEL SCHEDULE
 AND LOAD CALCULATIONS.
 4)NOTE:AS PER ART 250-81 NEED TO INCLUDE
 GROUND ROD,COLD WATER PIPE AS A PART OF
 THE GROUNDING ELECTRODE SYSTEM.
  
  
 NEED TO SUBMIT THE ABOVE FOR REVIEW
 AND APPROVAL.
  
  
  
 APPROVED BY D. PALMER ON 11/3/99.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-11-05 Cont ID  
Sent By tlarge Date 1999-11-05 Time 10:44 Rev Time 0.00
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLANS SIGNED AND APPROVED BY R.TURNQUIST
 ON 10/13/99.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-11-05 Cont ID  
Sent By ndenmark Date 1999-11-05 Time 08:37 Rev Time 0.25
Received By ndenmark Date 1999-11-05 Time 08:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-05 Cont ID  
Sent By ndenmark Date 1999-10-15 Time 14:10 Rev Time 0.33
Received By ndenmark Date 1999-10-15 Time 14:10 Sent To  
Notes
2001-01-08 00:00:00****CORRECTED ON REVISION***************
 1) PROVIDE OUTSIDE AIR CALCULATONS PER
 ASHRAE 62-89
 2) BATHROOM WINDOWS TO HAVE MIN. 3 SQ.FT
 OPEN AREA OR BATHROOM EXHAUST FANS PER
 503.3.1
 3) CEILING FANS BLADES TO BE MIN. 8'
 FROM FINISHED FLOOR SMC 404.3.2
 4) SHOW RETURN AIR PATH TO AHU #1
 5) OVERFLOW PROTECTION REQUIRED FOR BOTH
 UNITS SMC 304.8.6
 6) DUCTS SHALL NOT BE INSTALLED WITHIN
 6" OF GROUND EXCEPT AS PROTECTED PER
 SMC 607 1997 SMC 605.4

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-11-05 Cont ID  
Sent By tlarge Date 1999-11-05 Time 10:38 Rev Time 0.50
Received By tlarge Date 1999-11-05 Time 10:38 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
 PLUMBING RISER SHALL BE SUBMITTED PRIOR
 TO ROUGH PLUMBING INSP.

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-10-18 Cont ID  
Sent By tlarge Date 1999-10-18 Time 15:11 Rev Time 0.75
Received By tlarge Date 1999-10-18 Time 15:11 Sent To  
Notes
2001-01-08 00:00:00CLEARLY SHOW LENGTH AND WIDTH OF HANDI-
 CAP TOILET ROOM ON PLANS.COMPLY W/FACBC
 FIG.28.
  
 WALLS AND FLOORS OF TOILET ROOMS SHALL
 BE NON-ABSORBENT MATERIAL TO A HEIGHT OF
 4 FEET PER SBC SEC.1204.2.
  
 SUBMIT WATER RISER FOR REVIEW.SPC 104.2
  
 SHOW FIXTURE CLEARANCE OF H.C.WATER
 CLOSET AND STANDARD WATER CLOSET PER
 FACBC AND SPC SEC.403.4.
  
 A DRINKING FOUNTAIN IS REQD.PER TABLE
 407 OF SPC.