Plan Review Details - Permit 99100485
| Plan Review Stops For Permit 99100485 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
1999-10-28 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-10-28 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-11-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-10-19 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
tlarge |
Date |
1999-10-19 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | U*************UNSAT******************** | | | | | | 1)NOTE:AS PER ART;210-70 NEED TO SHOW | | | EGRESS LIGHTING FROM SECOND FLOOR AND | | | FROM FIRST FLOOR FRONT ROOM.MAYBE ON | | | 3-WAY FROM FRONT ENTRY. | | | 2)NOTE:AS PER ART;210-63 NEED WP GFI REC | | | FOR A/C EQUIPMENT . | | | 3)NOTE:AS PER ARTS;215-5/110-9 NEED TO | | | SHOW COMPLETE RISER DIAGRAM TO INCLUDE | | | METER,MAINS,PANEL(S) GROUNDING SYSTEM, | | | CONDUIT SIZES, WIRE SIZES ETC. | | | NEED TO SUBMIT THE AIC RATING OF THE | | | EQUIPMENT AND BREAKERS.AIC RATING IS | | | FIGURED FROM FAULT CURRENT CALCULATIONS. | | | NEED TO SUBMIT COMPLETE PANEL SCHEDULE | | | AND LOAD CALCULATIONS. | | | 4)NOTE:AS PER ART 250-81 NEED TO INCLUDE | | | GROUND ROD,COLD WATER PIPE AS A PART OF | | | THE GROUNDING ELECTRODE SYSTEM. | | | | | | | | | NEED TO SUBMIT THE ABOVE FOR REVIEW | | | AND APPROVAL. | | | | | | | | | | | | APPROVED BY D. PALMER ON 11/3/99. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
1999-11-05 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-11-05 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
tlarge |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLANS SIGNED AND APPROVED BY R.TURNQUIST | | | ON 10/13/99. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
1999-11-05 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-11-05 |
Time |
08:37 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
1999-11-05 |
Time |
08:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-11-05 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-10-15 |
Time |
14:10 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
1999-10-15 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****CORRECTED ON REVISION*************** | | | 1) PROVIDE OUTSIDE AIR CALCULATONS PER | | | ASHRAE 62-89 | | | 2) BATHROOM WINDOWS TO HAVE MIN. 3 SQ.FT | | | OPEN AREA OR BATHROOM EXHAUST FANS PER | | | 503.3.1 | | | 3) CEILING FANS BLADES TO BE MIN. 8' | | | FROM FINISHED FLOOR SMC 404.3.2 | | | 4) SHOW RETURN AIR PATH TO AHU #1 | | | 5) OVERFLOW PROTECTION REQUIRED FOR BOTH | | | UNITS SMC 304.8.6 | | | 6) DUCTS SHALL NOT BE INSTALLED WITHIN | | | 6" OF GROUND EXCEPT AS PROTECTED PER | | | SMC 607 1997 SMC 605.4 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
1999-11-05 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-11-05 |
Time |
10:38 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
1999-11-05 |
Time |
10:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | PLUMBING RISER SHALL BE SUBMITTED PRIOR | | | TO ROUGH PLUMBING INSP. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
1999-10-18 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-10-18 |
Time |
15:11 |
Rev Time |
0.75 |
| Received By |
tlarge |
Date |
1999-10-18 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CLEARLY SHOW LENGTH AND WIDTH OF HANDI- | | | CAP TOILET ROOM ON PLANS.COMPLY W/FACBC | | | FIG.28. | | | | | | WALLS AND FLOORS OF TOILET ROOMS SHALL | | | BE NON-ABSORBENT MATERIAL TO A HEIGHT OF | | | 4 FEET PER SBC SEC.1204.2. | | | | | | SUBMIT WATER RISER FOR REVIEW.SPC 104.2 | | | | | | SHOW FIXTURE CLEARANCE OF H.C.WATER | | | CLOSET AND STANDARD WATER CLOSET PER | | | FACBC AND SPC SEC.403.4. | | | | | | A DRINKING FOUNTAIN IS REQD.PER TABLE | | | 407 OF SPC. |
|
|
|