| Plan Review Stops For Permit 99100477 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
1999-12-29 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
1999-11-10 |
Time |
12:20 |
Rev Time |
0.45 |
| Received By |
jcaloger |
Date |
1999-11-10 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1-SEE PAGE #5 FOR LIST OF VIOLATIONS | | | SUBMIT INFORMATION AS REQUIRED BY | | | D. PALMER ON ORIGINAL PLAN REVIEW! | | | 12/28 APPROVED AS PER DEWEY PALMER |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
1999-12-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-10-19 |
Time |
18:20 |
Rev Time |
0.00 |
| Received By |
jcaloger |
Date |
1999-10-19 |
Time |
18:19 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************DENIED********************* | | | ************SEE LIST******************** | | | | | | 1)NOTE:AS PER ARTS;215-5/110-9.NEED TO | | | SHOW AIC RATING OF MAINS AND BRANCH | | | BREAKERS.AIC RATING IS FIGUREDFROM FAULT | | | CURRENT CALCULATIONS. | | | 2)NOTE:YOU SHOW MAIN DISC.BY CODE IF | | | REQ`D.?? SOME FORM OF MAIN DISC.IS REQ`D | | | EITHER MAIN BRKR. PANEL OR MAIN DISC. | | | 3)NOTE:AS PER ART:250-81 PLEASE SHOW | | | GROUNDING ELECTRODE CONDUCTOR GOING TO | | | BLDG.STEEL ALSO. | | | 4)NOTE:PLEASE LIST ON PANEL SCHEDULE | | | CIRCUT(S) FOR BATH ROOM GFI AS PER ART; | | | 210-52D MUST BE 20 AMP.,#12 AWG. | | | 5)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTER SPACE ARE TO | | | BE GFI/GFI PROTECTED. | | | 6)NOTE:PLEASE SHOW AIR HANDLER UNIT | | | AND THE LOCATION BEING INSTALLED. | | | IF AIR HANDLER IS GOING IN ATTIC ABOVE | | | GARAGE THEN PLEASE DRAW IN RECEPT.REQ`D | | | BY 210-63. | | | 7)NOTE:AS PER 1993/1996 NFPA-72 SMOKE | | | DETECTORS ARE REQ`D AND SHALL BE | | | INSTALLED INSIDE AND OUTSIDE ALL | | | SLEEPING ROOMS IN CONSTRUCTION OF NEW | | | RESIDENTIAL DWELLINGS. | | | 8)NOTE:ALL LOW VOLTAGE MUST BE INCLUDED | | | ON PLANS AT THE TIME OF SUBMITTAL.!!! | | | IF LOW VOLTAGE IS NOT SUBMITTED AT THAT | | | TIME, THEN A SEPARATE APPLICATION AND | | | PLANS MUST BE SUBMITTED FOR REVIEWAND | | | APPROVAL. | | | | | | NEED TO COMPLETE ALL THE ABOVE,SUBMIT | | | FOR REVIEW AND APPROVAL. PLEASE CALL | | | IF YOU HAVE ANY QUESTIONS.659-8096/8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-10-18 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-10-18 |
Time |
18:35 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2000-10-18 |
Time |
18:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
1999-12-08 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
1999-11-13 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
cthirben |
Date |
1999-12-08 |
Time |
08:57 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NO A/C PLANS. | | | RECIEVED A/C PLANS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-12-08 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
1999-10-19 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
cthirben |
Date |
1999-12-08 |
Time |
08:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
1999-12-20 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-12-20 |
Time |
12:27 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
1999-12-20 |
Time |
12:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
1999-12-20 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-12-07 |
Time |
14:53 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
1999-12-07 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | FIXTURES DOWNSTREAM OF WATER CLOSET | | | SHALL BE VENTED PER SPC SEC.913.2. | | | | | | WATER CLOSETS NOT PERMITTED ON WET VENTS | | | PER COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 911.1.1. | | | | | | WASHING MACHINE SHALL NOT BE INSTALLED | | | ON 2" CROSS PER SPC SEC.409.12.3. | | | | | | LOCATION OF PLBG.FIXTURES ON SANITARY | | | RISER SHALL MATCH THE FLOOR PLAN PER | | | CITY OF WPB AMENDMENTS TO SPC. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
1999-12-20 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-11-09 |
Time |
06:41 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
1999-11-09 |
Time |
06:41 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | WET VENTS SHALL RECEIVE THE DISCHARGE | | | FROM FIXTURE DRAINS ONLY PER CITY OF | | | WEST PALM BEACH AMENDMENTS TO THE STD. | | | PLUMBING CODE SEC.911.1.1. | | | | | | LOCATION OF FIXTURES ON PLUMBING RISER | | | SHALL MATCH THE FLOOR PLAN.CITY OF WPB | | | AMENDMENTS TO STD.PLBG.CODE SEC.104.2.1. | | | | | | MIN.SIZE OF OF DRAINAGE PIPE U/G SHALL | | | BE 2" PER SPC SEC.714.4. | | | | | | NUMBER OF WATER CLOSETS SHOWN ON PLBG. | | | RISER DOESN'T MATCH FLOOR PLAN.(4 NOTED | | | ON RISER,3 SHOWN ON FLOOR PLAN.) | | | | | | VENTS CANNOT BE LARGER THAN HORIZONTAL | | | DRAIN CONNECTED THERETO.SPC SEC.905.2. | | | (PERMITTED ONLY WHERE FROST IA A PROBLEM |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
1999-12-20 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-10-19 |
Time |
06:54 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
1999-10-19 |
Time |
06:54 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ISOMETRIC SHALL MATCH FLOOR PLAN AND | | | COMPLY W/THE STANDARD PLBG.CODE. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
1999-12-29 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
1999-12-23 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
jcaloger |
Date |
1999-12-28 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | ***************DENIED******************* | | | | | | SBC 104.2.2 | | | | | | 1)PROVIDE OWNER SIGNATURE ON ENERGY | | | CALCULATIONS | | | | | | 2)PROVIDE 2 CURRENT COPIES OF PRODUCT | | | APPROVALS FOR: | | | EXTERIOR ENTRY DOOR | | | ARCH TRANSOMS | | | ROOF COVERING | | | | | | NOTE:PROVIDE 2 COPIES OF ALL PRODUCT | | | APPROVALS | | | | | | 3)PROVIDE STORM PANEL INSTALLATION | | | SCHEDULE AND KEY PLAN WITH SPECIFIC | | | ANCHORS TO BE USED | | | | | | 4)BEFORE A PERMIT TO CONSTRUCT CAN BE | | | ISSUED,IMPACT FEES MUST BE PAID TO PALM | | | BEACH CO.,THE PERMIT PLANS STAMPED BY | | | THEM AND THE RECIEPT ATTACHED TO THE | | | PERMIT APPLICATION |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
1999-12-29 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
1999-10-21 |
Time |
07:05 |
Rev Time |
0.00 |
| Received By |
jcaloger |
Date |
1999-11-17 |
Time |
12:47 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | | | | 1)PROVIDE 2 COPIES OF CURRENT SIGN AND | | | SEAL SURVEY. | | | | | | 2)PROVIDE 2 COPIES OF ENERGY CALCULATION | | | AND INCLUDE MANUEL J. | | | | | | 3)PROVIDE SOIL TEST REPORT. | | | | | | 4)PROVIDE 2 CURRENT COPIES OF PRODUCT | | | APPROVALS FOR: | | | WINDOWS AND ARCH TRANSOMS | | | EXTERIOR DOORS,GARAGE DOOR,SLIDING | | | GLASS DOOR. | | | ROOF COVERING | | | STORM PANELS INCLUDING INSTALLATION | | | SCHEDULE AND KEY PLAN WITH SPECIFIC | | | ANCHORS TO BE USED. | | | | | | 5)ZONING APPROVAL | | | | | | 6)BEFORE A PERMIT TO CONSTRUCT CAN BE | | | ISSUED,IMPACT FEES MUST BE PAID TO PALM | | | BEACH CO.,THE PERMIT PLANS STAMPED BY | | | THEM AND THE PINK RECIEPT ATTACHED TO | | | THE PERMIT APPLICATION. | | | | | | 1997 SBC 104.2.2 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
1999-12-21 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
1999-12-21 |
Time |
10:29 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
1999-12-29 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
1999-10-18 |
Time |
12:15 |
Rev Time |
0.50 |
| Received By |
jcaloger |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NEED SURVEY, NO PHONE NUMBER PASSED ONTO | | | BUILDING |
|
|