Plan Review Details - Permit 99100477
Plan Review Stops For Permit 99100477
Review Stop E ELECTRICAL
Rev No 2 Status P Date 1999-12-29 Cont ID  
Sent By jleahy Date 1999-11-10 Time 12:20 Rev Time 0.45
Received By jcaloger Date 1999-11-10 Time 12:18 Sent To  
Notes
2001-01-08 00:00:001-SEE PAGE #5 FOR LIST OF VIOLATIONS
 SUBMIT INFORMATION AS REQUIRED BY
 D. PALMER ON ORIGINAL PLAN REVIEW!
 12/28 APPROVED AS PER DEWEY PALMER

Review Stop E ELECTRICAL
Rev No 1 Status N Date 1999-12-29 Cont ID  
Sent By dpalmer Date 1999-10-19 Time 18:20 Rev Time 0.00
Received By jcaloger Date 1999-10-19 Time 18:19 Sent To  
Notes
2001-01-08 00:00:00*************DENIED*********************
 ************SEE LIST********************
  
 1)NOTE:AS PER ARTS;215-5/110-9.NEED TO
 SHOW AIC RATING OF MAINS AND BRANCH
 BREAKERS.AIC RATING IS FIGUREDFROM FAULT
 CURRENT CALCULATIONS.
 2)NOTE:YOU SHOW MAIN DISC.BY CODE IF
 REQ`D.?? SOME FORM OF MAIN DISC.IS REQ`D
 EITHER MAIN BRKR. PANEL OR MAIN DISC.
 3)NOTE:AS PER ART:250-81 PLEASE SHOW
 GROUNDING ELECTRODE CONDUCTOR GOING TO
 BLDG.STEEL ALSO.
 4)NOTE:PLEASE LIST ON PANEL SCHEDULE
 CIRCUT(S) FOR BATH ROOM GFI AS PER ART;
 210-52D MUST BE 20 AMP.,#12 AWG.
 5)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTER SPACE ARE TO
 BE GFI/GFI PROTECTED.
 6)NOTE:PLEASE SHOW AIR HANDLER UNIT
 AND THE LOCATION BEING INSTALLED.
 IF AIR HANDLER IS GOING IN ATTIC ABOVE
 GARAGE THEN PLEASE DRAW IN RECEPT.REQ`D
 BY 210-63.
 7)NOTE:AS PER 1993/1996 NFPA-72 SMOKE
 DETECTORS ARE REQ`D AND SHALL BE
 INSTALLED INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS IN CONSTRUCTION OF NEW
 RESIDENTIAL DWELLINGS.
 8)NOTE:ALL LOW VOLTAGE MUST BE INCLUDED
 ON PLANS AT THE TIME OF SUBMITTAL.!!!
 IF LOW VOLTAGE IS NOT SUBMITTED AT THAT
 TIME, THEN A SEPARATE APPLICATION AND
 PLANS MUST BE SUBMITTED FOR REVIEWAND
 APPROVAL.
  
 NEED TO COMPLETE ALL THE ABOVE,SUBMIT
 FOR REVIEW AND APPROVAL. PLEASE CALL
 IF YOU HAVE ANY QUESTIONS.659-8096/8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-10-18 Cont ID  
Sent By jleech Date 2000-10-18 Time 18:35 Rev Time 0.33
Received By jleech Date 2000-10-18 Time 18:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-12-08 Cont ID  
Sent By jleech Date 1999-11-13 Time 12:30 Rev Time 0.00
Received By cthirben Date 1999-12-08 Time 08:57 Sent To  
Notes
2001-01-08 00:00:00NO A/C PLANS.
 RECIEVED A/C PLANS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-08 Cont ID  
Sent By jleech Date 1999-10-19 Time 14:52 Rev Time 0.00
Received By cthirben Date 1999-12-08 Time 08:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 1999-12-20 Cont ID  
Sent By tlarge Date 1999-12-20 Time 12:27 Rev Time 0.33
Received By tlarge Date 1999-12-20 Time 12:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 1999-12-20 Cont ID  
Sent By tlarge Date 1999-12-07 Time 14:53 Rev Time 0.65
Received By tlarge Date 1999-12-07 Time 14:53 Sent To  
Notes
2001-01-08 00:00:00FIXTURES DOWNSTREAM OF WATER CLOSET
 SHALL BE VENTED PER SPC SEC.913.2.
  
 WATER CLOSETS NOT PERMITTED ON WET VENTS
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 911.1.1.
  
 WASHING MACHINE SHALL NOT BE INSTALLED
 ON 2" CROSS PER SPC SEC.409.12.3.
  
 LOCATION OF PLBG.FIXTURES ON SANITARY
 RISER SHALL MATCH THE FLOOR PLAN PER
 CITY OF WPB AMENDMENTS TO SPC.

Review Stop P PLUMBING
Rev No 2 Status N Date 1999-12-20 Cont ID  
Sent By tlarge Date 1999-11-09 Time 06:41 Rev Time 0.50
Received By tlarge Date 1999-11-09 Time 06:41 Sent To  
Notes
2001-01-08 00:00:00WET VENTS SHALL RECEIVE THE DISCHARGE
 FROM FIXTURE DRAINS ONLY PER CITY OF
 WEST PALM BEACH AMENDMENTS TO THE STD.
 PLUMBING CODE SEC.911.1.1.
  
 LOCATION OF FIXTURES ON PLUMBING RISER
 SHALL MATCH THE FLOOR PLAN.CITY OF WPB
 AMENDMENTS TO STD.PLBG.CODE SEC.104.2.1.
  
 MIN.SIZE OF OF DRAINAGE PIPE U/G SHALL
 BE 2" PER SPC SEC.714.4.
  
 NUMBER OF WATER CLOSETS SHOWN ON PLBG.
 RISER DOESN'T MATCH FLOOR PLAN.(4 NOTED
 ON RISER,3 SHOWN ON FLOOR PLAN.)
  
 VENTS CANNOT BE LARGER THAN HORIZONTAL
 DRAIN CONNECTED THERETO.SPC SEC.905.2.
 (PERMITTED ONLY WHERE FROST IA A PROBLEM

Review Stop P PLUMBING
Rev No 1 Status N Date 1999-12-20 Cont ID  
Sent By tlarge Date 1999-10-19 Time 06:54 Rev Time 0.50
Received By tlarge Date 1999-10-19 Time 06:54 Sent To  
Notes
2001-01-08 00:00:00ISOMETRIC SHALL MATCH FLOOR PLAN AND
 COMPLY W/THE STANDARD PLBG.CODE.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 1999-12-29 Cont ID  
Sent By fknapp Date 1999-12-23 Time 10:52 Rev Time 0.00
Received By jcaloger Date 1999-12-28 Time 15:18 Sent To  
Notes
2001-01-08 00:00:00 
 ***************DENIED*******************
  
 SBC 104.2.2
  
 1)PROVIDE OWNER SIGNATURE ON ENERGY
 CALCULATIONS
  
 2)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR:
 EXTERIOR ENTRY DOOR
 ARCH TRANSOMS
 ROOF COVERING
  
 NOTE:PROVIDE 2 COPIES OF ALL PRODUCT
 APPROVALS
  
 3)PROVIDE STORM PANEL INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS TO BE USED
  
 4)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED,IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 1999-12-29 Cont ID  
Sent By fknapp Date 1999-10-21 Time 07:05 Rev Time 0.00
Received By jcaloger Date 1999-11-17 Time 12:47 Sent To  
Notes
2001-01-08 00:00:00DENIED:
  
 1)PROVIDE 2 COPIES OF CURRENT SIGN AND
 SEAL SURVEY.
  
 2)PROVIDE 2 COPIES OF ENERGY CALCULATION
 AND INCLUDE MANUEL J.
  
 3)PROVIDE SOIL TEST REPORT.
  
 4)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR:
 WINDOWS AND ARCH TRANSOMS
 EXTERIOR DOORS,GARAGE DOOR,SLIDING
 GLASS DOOR.
 ROOF COVERING
 STORM PANELS INCLUDING INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS TO BE USED.
  
 5)ZONING APPROVAL
  
 6)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED,IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE PINK RECIEPT ATTACHED TO
 THE PERMIT APPLICATION.
  
 1997 SBC 104.2.2

Review Stop Z ZONING
Rev No 2 Status P Date 1999-12-21 Cont ID  
Sent By gjoyce Date 1999-12-21 Time 10:29 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 1999-12-29 Cont ID  
Sent By gjoyce Date 1999-10-18 Time 12:15 Rev Time 0.50
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEED SURVEY, NO PHONE NUMBER PASSED ONTO