Plan Review Details - Permit 99100445
Plan Review Stops For Permit 99100445
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-11-18 Cont ID  
Sent By hpiskura Date 1999-11-18 Time 10:37 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-04-12 Cont ID  
Sent By dpalmer Date 2001-04-12 Time 12:26 Rev Time 0.00
Received By dpalmer Date 2001-04-12 Time 12:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-11-16 Cont ID  
Sent By dpalmer Date 2000-11-16 Time 20:32 Rev Time 0.00
Received By dpalmer Date 2000-11-16 Time 20:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-04-19 Cont ID  
Sent By dpalmer Date 2000-04-19 Time 20:41 Rev Time 0.00
Received By dpalmer Date 2000-04-19 Time 20:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-25 Cont ID  
Sent By dpalmer Date 1999-10-25 Time 07:05 Rev Time 0.00
Received By dpalmer Date 1999-10-25 Time 07:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-03-27 Cont ID  
Sent By mcarsill Date 2001-03-27 Time 14:56 Rev Time 0.00
Received By mcarsill Date 2001-03-27 Time 14:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-11-30 Cont ID  
Sent By mcarsill Date 2000-11-30 Time 09:43 Rev Time 0.00
Received By mcarsill Date 2000-11-30 Time 09:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-04-25 Cont ID  
Sent By rturnque Date 2000-04-25 Time 13:54 Rev Time 0.45
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00FIRE ALARM SYSTEM SHALL BE CLASS "A" OR
 ADDRESSABLE.
 PROVIDE PERMIT AND SHOP DRAWINGS FOR
 FIRE ALARM SYSTEM AND FIRE SPRINKLER
 SYSTEM.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-04-05 Cont ID  
Sent By tlarge Date 2000-04-05 Time 08:48 Rev Time 0.00
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLANS REVIEWED AND SIGNED BY R.TURNQUIST
 ON 11/3/99.SEE PLANS AND APPLICATION.
 PER TKL.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-11-30 Cont ID  
Sent By ndenmark Date 2000-11-30 Time 14:13 Rev Time 0.25
Received By ndenmark Date 2000-11-30 Time 14:13 Sent To  
Notes
2001-01-08 00:00:00NOTE: SEPARATE PERMIT REQUIRES FOR
 MEDICAL GAS. SUBMIT PLANS AT TIME OF
 MECHANICAL PERMIT APPLICATION SHOWING
 COMPLIANCE W/1999NFPA 99C.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-04-14 Cont ID  
Sent By ndenmark Date 2000-04-14 Time 07:49 Rev Time 0.50
Received By ndenmark Date 2000-04-14 Time 07:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-04-14 Cont ID  
Sent By ndenmark Date 1999-11-22 Time 11:19 Rev Time 1.00
Received By ndenmark Date 1999-11-22 Time 11:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-11-04 Cont ID  
Sent By tlarge Date 2000-11-04 Time 10:54 Rev Time 1.00
Received By tlarge Date 2000-11-04 Time 09:50 Sent To  
Notes
2001-01-08 00:00:001)SHT.A-1-DRY VENTS ARE NOT PERMITTED
 PER SPC SEC.906.2.1.
  
 2)DESIGN OF CIRCUIT AND LOOP SYSTEM
 SHALL COMPLY W/SPC SEC.914.1.VENTS SHALL
 COMPLY W/SPC SEC.920.3.SIZE ALL VENTS.
  
 3)SUBMIT A WATER RISER DIAGRAM FOR
 REVIEW.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 4)THE HANDICAP STALLS DO NOT COMPLY W/
 THE FACBC.SEE FACBC SEC.4.17.3(NEW
 CONSTRUCTION.)
  
 5)SUBMIT OCCUPANT LOAD FOR COMPLIANCE W/
 SPC TABLE 407 FOR MIN.NUMBER OF REQD.
 FACILITIES.SEE 407.1.3.
  
 6)FLOORS AND WALLS IN RESTROOMS SHALL BE
 NONABSORBENT TO 4' PER SBC 1204.2(B).
  
 7)FLOOR DRAINS ARE READ.IN THE RESTROOMS
 PER SPC SEC.409.4.1.1
  
 8)DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 9)SINK SHALL COMPLY W/FACBC SECS.4.24.1-
 4.24.7.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-04-04 Cont ID  
Sent By tlarge Date 2000-04-04 Time 19:29 Rev Time 1.25
Received By tlarge Date 2000-04-04 Time 19:28 Sent To  
Notes
2001-01-08 00:00:00*******************PROVISO**************
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-10-21 Cont ID  
Sent By tlarge Date 1999-10-21 Time 15:14 Rev Time 5.00
Received By tlarge Date 1999-10-21 Time 15:14 Sent To  
Notes
2001-01-08 00:00:00DRINKING FOUNTAIN SHALL BE HANDICAP
 ACCESSIBLE AND COMPLY W/ FACBC SEC.
 4.1.3(10)(A) AND FIGURE 27.
  
 FLOOR DRAINS ARE REQD.IN THE TOILET
 ROOMS PER SPC SEC.409.4.1.1.
  
 CLEARLY SHOW ON PLANS THAT WALLS AND
 FLOORS ARE NON-ABSORBENT TO A HEIGHT OF
 4 FEET PER SBC SEC.1204.2.(INDICATE ON
 FINISH SCHEDULE.)
  
 EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY W/FACBC SEC.4.1.3.(11),
 4.22.
  
 PUBLIC AND COMMON USE BATHING ROOMS
 SHALL COMPLY W/FACBC SEC.4.23 PER FACBC
 SEC.4.1.3.(11).
  
 WATER FILTER SYSTEM SHALL BE NSF
 APPROVED PER SPC SEC.615.1.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.2.(CONTROL VALVES REQD.ON
 BRANCH LINES.)
  
 SIZING OF VENTS FOR SINKS IN EXAM ROOMS
 SHALL COMPLY W/TABLE 920.2.(2" EXCEEDS
 LIMITS.)
  
 NOTE OCCUPANT LOAD ON PLANS TO ENSURE
 COMPLIANCE W/SPC TABLE 407.COMPLY W/SEC.
 407.1.3.