Plan Review Details - Permit 99100387
Plan Review Stops For Permit 99100387
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-04-21 Cont ID  
Sent By hpiskura Date 2000-04-21 Time 14:12 Rev Time 0.00
Received By hpiskura Date 2000-04-20 Time 16:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-03-03 Cont ID  
Sent By hpiskura Date 2000-03-03 Time 15:26 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00SAME AS FIRST

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-12-16 Cont ID  
Sent By hpiskura Date 1999-12-16 Time 13:55 Rev Time 0.00
Received By hpiskura Date   Time   Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-09-21 Cont ID  
Sent By dpalmer Date 2000-09-21 Time 12:44 Rev Time 0.00
Received By dpalmer Date 2000-09-21 Time 12:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-08-29 Cont ID  
Sent By dpalmer Date 2000-08-29 Time 20:46 Rev Time 0.00
Received By dpalmer Date 2000-08-29 Time 20:46 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE:AS ASKED FOR ON FIRST SET OF NOTE
 -S. PLEASE SUBMIT LOAD CALCULATIONS.
 PLEASE SHOW,,,WITH SQFT/CONTINUOUS LOADS
 AT 125% ETC.
  
 2)NOTE: PLEASE SUBMIT AND SHOW ALL AIC
 RATING FOR ALL MAINS/PANELS BEING INSTAL
 -LED.EQUIPMENT MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT PER 110-9
  
 \\3)NOTE PLEAS SUBMIT AND SHOW GROUNDING
 ELECTRODE SYSTEM. 250-50 BLDG STEEL AND
 COLD WATER ETC.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMAITON
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-11-01 Cont ID  
Sent By dpalmer Date 1999-11-01 Time 07:55 Rev Time 0.00
Received By dpalmer Date 1999-11-01 Time 20:44 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO****************
  
 1)NOTE:NEED TO SUBMIT LOAD CALCULATIONS
 OF SERVICE AND LOAD CALCULATION FOR EACH
 PANEL.AS PER 215-5
 2)SUBMIT LOAD ON COOK CENTER PANEL.
 NEED TO SUBMIT THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE ROUGH
 SLAB INSPECTION IS CALLED IN!!!!

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2000-08-23 Cont ID  
Sent By mgonzale Date 1999-11-30 Time 10:56 Rev Time 0.25
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLANS HAVE BEEN REVIEWED AT UTILITIES
 DEPARTMENT AT 45TH ST. ON OCT 22, 1999

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2000-08-23 Cont ID  
Sent By dlauderm Date 1999-11-08 Time 12:07 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 1999-11-04 Cont ID  
Sent By dlauderm Date 1999-11-04 Time 10:40 Rev Time 0.25
Received By dlauderm Date   Time   Sent To  
Notes
2001-01-08 00:00:00STORMWATER, WATER AND SANITARY ALREADY
 APPROVED THRU SEPARATE REVIEWS AT ENG.
 SERVICES.SERVIES FOR SW, SS,WILL
 BE INSTALLED VIA HOME DEPOT PLAN.
 SANITATION COMMENTS.APPROVED WITH
 PREVISO: OPENING OF STANDARD TRASH
 ENCLOSURE PLANS, ON PAGE C6 (BOT. RIGHT
 AND TOP RIGHT)DO NOT MATCH. THE GATES
 MUST HAVE A 12' OPENING BETWEEN THE
 GATE POSTS.ADDITIONALLY THE WIDTH OF
 THE OPEN AREA BETWEEN THE CONCRETE WALLS
 IS 22' - 8", IT MUST BE OVER 24' WIDE TO
 TAKE TWO GATES AND TWO GATE POSTS AS
 SHOWN ON THE TOP RIGHT DRAWING OF PAGE
 C6.THE DRAWING ALSO CONFLICTS WITH THE
 DRAWING ON PAGE 2 OF THE BUILDING PLAN
 IT SHOWS ONLY 11' FROM THE CENTER OF THE
 GATE POSTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-22 Cont ID  
Sent By mcarsill Date 2000-08-22 Time 16:07 Rev Time 0.00
Received By mcarsill Date 2000-08-22 Time 16:06 Sent To  
Notes
2001-01-08 00:00:00PLAN WAS APPROVED PROVISO BY RHETT
 TURNQUEST ON 12/7/99

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-09-05 Cont ID  
Sent By ndenmark Date 2000-09-05 Time 10:58 Rev Time 0.33
Received By ndenmark Date 2000-09-05 Time 10:58 Sent To  
Notes
2001-01-08 00:00:00NOTE:
 SEPARATE PERMIT REQUIRED FOR HOOD, SUPP-
 RESSION SYSTEM AND WALKIN COOLER FREEZER
 PROVIDE PLANS AT TIME OF PERMIT APPLICA-
 TION FOR THESE SYSTEMS.
 DUCT WRAP FOR GREASE EXHAUST DUCT TO
 HAVE SUBMITTED AT TIME OF PERMIT APPLIC-
 ATION THE PRODUCT APPROVAL INFORMATION
 FOR THE DUCT WRAP MATERIAL FOR APPROVAL
 PRIOR TO INSTALLATION

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-12-02 Cont ID  
Sent By ndenmark Date 1999-12-02 Time 07:35 Rev Time 0.50
Received By ndenmark Date 1999-12-02 Time 07:35 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 ADDITIONAL MECHANICAL PERMITS REQUIRED
 FOR HOODS, SUPPRESSION SYSTEMS, AND WALK
 IN COOLER/ FREEZER. SUBMIT PLANS WITH
 MECHANICAL PERMIT APPLICATIONS
 CLEARANCE TO COMBUSTIBLES FOR HOOD AND
 DUCT TO BE 18" MIN. OR CLEARANCE REDUCT-
 ION IN ACCORDANCE WITH 1997 SMC 504.4
 AND 505.12
 EXHAUST TERMINATION TO BE MIN. 10' FROM
 ANY OUTSIDE AIR INTAKE

Review Stop P PLUMBING
Rev No 5 Status F Date 2000-09-03 Cont ID  
Sent By tlarge Date 2000-09-03 Time 06:44 Rev Time 0.65
Received By tlarge Date 2000-09-03 Time 06:35 Sent To  
Notes
2001-01-08 00:00:001)HORIZONTAL DRY VENTS NOT PERMITTED PER
 SPC SEC.906.2.1.(SEE FLOOR SINKS,FLOOR
 DRAINS.)
  
 2)GREASE INTERCEPTOR SHALL COMPLY W/CITY
 OF WPB ENGINEERING STANDARDS.
  
 3)WATER SUPPLY CONTROL SHALL COMPLY W/
 SPC SEC.610.4.1,610.4.2.
  
 4)SERIES OF FLOOR DRAINS AND FLOOR SINKS
 SHALL COMPLY W/SPC SEC.921 FOR HORIZ.
 COMBINATION WASTE AND VENT SYSTEM.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-04-24 Cont ID  
Sent By tlarge Date 2000-04-24 Time 07:59 Rev Time 1.00
Received By tlarge Date 2000-04-24 Time 07:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-02-28 Cont ID  
Sent By tlarge Date 2000-02-28 Time 10:34 Rev Time 3.25
Received By tlarge Date 2000-02-28 Time 10:33 Sent To  
Notes
2001-01-08 00:00:00SIZE AND DESIGN OF GREASE TRAP SHALL BE
 APPROVED BY CITY OF WPB UTILITIES.SUBMIT
 APPROVAL FORM FROM UTILITIES.CONTACT
 R.COMPO AT (561)835-7423 FOR INFO.
  
 PLANS SHALL BE ROUTED TO FLA.DEPT.OF
 BUSINESS REGULATION FOR REVIEW AND
 APPROVAL PRIOR TO REVIEW BY THIS DEPT.
 COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7
  
 URINAL SHALL BE ARRANGED TO ALLOW FOR
 PRIVACY PER SPC SEC.404.3.(URINAL IS
 LOCATED IN LINE OF SIGHT FROM CORRIDOR)
  
 HUB DRAINS NOT PERMITTED PER SPC.FLOOR
 DRAINS OR FLOOR SINKS SHALL BE INSTALLED
 PER SPC 407 & 408.
  
 VENTING OF FLOOR DRAINS AND FLOOR SINKS
 SHALL COMPLY W/TABLE 908.1.
  
 WATER SUPPLY CONTROL FOR THE RESTROOMS
 SHALL COMPLY W/SPC SEC.610.4.1.
  
 DRY VENTS NOT PERMITTED PER SPC 906.4
  
 SHOW HEIGHT OF TOILET PAPER DISPENSER
 PER FACBC FIG.30.
  
 SHOW VTR FOR TOILET ROOM OR CONNECTION
 TO STACK VENT.SPC SEC.904.2.1.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-02-20 Cont ID  
Sent By tlarge Date 2000-02-20 Time 12:26 Rev Time 0.50
Received By tlarge Date 2000-02-20 Time 12:26 Sent To  
Notes
2001-01-08 00:00:00TWO COMPLETE COPIES OF PLANS SHALL BE
 SUBMITTED.THE COPIES ARE EXTREMELY
 DISORGANIZED AND DIFFICULT TO REVIEW IN
 THIS MANNER.PLANS,SPECIFICATIONS,DETAILS
 AND REVISIONS SHALL BE COMPILED BY
 OWNER'S REPRESENTATIVE IN AN ORDERLY
 FASHION FOR A PROPER AND THOROUGH PLAN
 REVIEW BY THIS DEPT.COUNTYWIDE AMENDMENT
 TO SPC SEC.104.2.1`.

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-11-01 Cont ID  
Sent By tlarge Date 1999-11-01 Time 11:39 Rev Time 3.25
Received By tlarge Date 1999-10-26 Time 11:38 Sent To  
Notes
2001-01-08 00:00:00INDICATE SIZE OF GREASE TRAP ON PLANS.
 CONTACT RODNEY COMPO AT CITY OF W.P.B.
 REGIONAL WASTEWATER TREATMENT PLANT AT
 (561)835-7423 FOR SIZE REQS.
  
 PLANS SHALL BE ROUTED TO DEPT.OF
 BUSINESS AND PROFESSIONAL REGULATION FOR
 REVIEW AND APPROVAL PRIOR TO REVIEW BY
 THIS AGENCY.SPC SEC.101.4.7.
  
 URINAL SHALL BE ARRANGED TO ALLOW FOR
 PRIVACY PER SPC SEC.404.3.(LOCATED IN
 LINE OF SIGHT IN CORRIDOR.)
  
 HUB DRAINS NOT PERMITTED BY SPC.FLOOR
 DRAINS OR FLOOR SINKS SHALL BE INSTALLED
 PER SPC 407 AND SPC 807.
  
 LOCATION OF GREASE TRAP SHALL COMPLY W/
 SBC SEC.1803.1.3.
  
 FLOOR DRAINS ARE NOT PROPERLY VENTED PER
 SPC 901.2 AND TABLE 908.1.
  
 VENTS CANNOT BE INCREASED IN SIZE .(ONLY
 IN AREAS WHERE FROST IS A FACTOR.)SPC
 SEC.905.2.
  
 WATER CLOSETS ARE NOT PROPERLY VENTED
 PER SPC SEC.901.2
  
 SIZE THE WATER SUPPLY SYSTEM IN ITS
 ENTIRETY.SPC SEC.104.2.1.
  
 WATER SUPPPLY CONTROL FOR THE RESTROOMS
 SHALL COMPLY W/SPC SEC.610.4.2.
  
 SUBMIT GAS DRAWING IF APPLICABLE.SPC
 104.2.1.
  
 DRY VENTS ARE NOT PERMITTED ON W.C.'S
 PER SPC SEC.906.4.
  
 SHOW HT. OF TOILET PAPER DISPENSER
 ON PLANS .COMPLY W/FACBC FIG 30.

Review Stop Z ZONING
Rev No 2 Status P Date 2000-08-23 Cont ID  
Sent By lsmith Date 2000-08-23 Time 08:54 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER A JONES

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By hpiskura Date 1999-12-16 Time 14:36 Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***