Plan Review Details - Permit 99100264
Plan Review Stops For Permit 99100264
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-19 Cont ID  
Sent By lmartine Date 1999-10-19 Time 12:20 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-09-27 Cont ID  
Sent By mcarsill Date 2000-09-27 Time 15:09 Rev Time 0.00
Received By mcarsill Date 2000-09-27 Time 15:09 Sent To  
Notes
2001-01-08 00:00:00ON SEPTEMBER 27,2000, WRITER EXAMINED
 PLANS FOR THE FIRE ALARM SYSTEM
 SUBMITTED BY TYPHOON SERVICES.
 1) NO CUT SHEETS FOR FIRE ALARM DEVICES
 PLANNED FOR USE WERE PROVIDED.
 2) FIRE ALARM SYSTEM TO BE CLASS A OR
 ADDRESSABLE.
 3) PLANS DISPLAY MANUAL PULL STATIONS
 ONLY AT THE FIRST FLOOR LEVEL. A REVIEW
 OF THE LIFE SAFETY CODE, REQUIRES
 MANUAL PULL STATIONS NEAR EACH REQUIRED
 EXIT.
 4) FIRE ALARM SYSTEMS TO BE MONITORED
 BY A UL LISTED CENTRAL STATION.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-19 Cont ID  
Sent By lmartine Date 1999-10-19 Time 12:21 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-10-19 Cont ID  
Sent By lmartine Date 1999-10-19 Time 12:21 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-10-25 Cont ID  
Sent By lmartine Date 1999-10-25 Time 13:54 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***