Plan Review Details - Permit 99100116
Plan Review Stops For Permit 99100116
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-15 Cont ID  
Sent By dpalmer Date 1999-10-15 Time 07:26 Rev Time 0.00
Received By dpalmer Date 1999-10-15 Time 07:26 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*****************
  
 1)NOTE: AS PER ARTS:110-9/215-5 NEED TO
 SUBMIT AIC RATING OF EQUIPMENT BEING
 INSTALLED AND BRANCH BREAKERS.
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
 2)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED. AND ALL OTHER OUTLETS
 WITHIN 6`.
 3)AS PER ART:210-52D BATH CICUTS ARE
 REQ`D TO BE 20AMP WITH #12 AWG AND TO BE
 DEDICATED FOR ONLY BATH RECEPTS.
 4)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS IN DWELLINGS
 OF NEW CONSTRUCTION.
  
 NEED TO SUBMIT THE ABOVE FOR REVIEW AND
 APPROVAL BEFORE FIRST ROUGH ELECTRICAL
 INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-12 Cont ID  
Sent By jleech Date 1999-10-12 Time 14:10 Rev Time 0.50
Received By jleech Date 1999-10-12 Time 14:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-06 Cont ID  
Sent By pschmitz Date 1999-10-06 Time 16:04 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 1999-11-08 Cont ID  
Sent By jgomez Date 1999-11-08 Time 15:54 Rev Time 1.00
Received By jgomez Date 1999-11-08 Time 15:54 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PLEASE REVISE ALL ORIGINAL DRAWINGS
 SHOWING ALL CORRECTIONS REQUESTED ON
 PLANS.
 2-REVISE FOOTING F-2. SEE RECOMMENDATION
 ON SOIL TEST REPORT FOR MINIMUM SIZE
 OF CONTINUOUS FOOTING. MIN. DEPTH OF
 F-2 TO BE 16" AS PER SEC 1804.1.3 SBC
 1997 AND 1804.1.9 CITY AMENDMENTS.
 3-PROVIDE PRODUCT APPROVAL FOR: ENTRY
 DOORS WITH SIDELITES ASSEMBLY, WINDOW
 AND DOOR MULLIONS, ROOF TILE, GARAGE
 DOOR.
 NOTE: NORANDEX PRODUCT APPROVALS ARE
 NOT ACCEPTED UNLESS THEY PROVIDE SITE
 SPECIFIC COMPLETE ENGINEERING CALCS
 AND SPECIFICATIONS OR APPROVED PRODUCT
 APPROVAL.
 4-STORM PANELS:
 -INSTALLATION SCHEDULE, KEY PLAN AND
 ENGINEER FLOOR PLANS DON'T MATCH.
 -PROVIDE COMPLETE INSTALLATION SCHEDULE
 AS PER CITY SAMPLE, ATTACHED.
 5-PROVIDE SAFETY GLASS AS REQUIRED. SEE
 PLANS FOR COMMENTS. SEC 2405.2 SBC/97.
 6-MASTER BEDROOM OPTION OF HAVING 34/5
 SINGLE HUNG WINDOW (SHEET A-2) DOESN'T
 MEET THE MINIMUM EGRESS REQUIREMENTS.
 REVISE AS REQ'D. SEC 1005.4.4 SBC/97.
 7-UPDATE ALL ENGINEERED TRUSSES:
 -REVISE MEAN ROOF HEIGHT.
 -DESIGN CRITERIA ACCEPTED BY THIS
 OFFICE IS SBC 1997 OR ASCE 7-95 AND
 MUST BE INCORPORATED IN THE ENGINEERED
 TRUSSES.
 8-PROVIDE COMPLETE SECTION/DETAIL AT
 MIDDLE BEARING POINT OF TRUSS D-16.
 SPECIFY ALL CONNECTORS (TOP & BOTTOM)
 AND COLUMN. SEC 104.2.2 CITY AMENDMENT
 9-PROVIDE COMPLETE BUCK DETAILS FOR ALL
 EXTERIOR WINDOW TYPES, DOOR TYPES AND
 GARAGE DOOR.SEC 104.2.2 CITY AMENDMENT
 10-NOTE:
 FLOOD ZONE "A-8". PROVIDE ELEVATION
 CERTIFICATE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 1999-11-04 Cont ID  
Sent By jgomez Date 1999-11-04 Time 14:17 Rev Time 0.00
Received By jgomez Date 1999-11-08 Time 15:53 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PLEASE REVISE ALL ORIGINAL DRAWINGS
 SHOWING ALL THE CORRECTIONS/
 CLARIFICATIONS REQUESTED ON PLANS.
 2-REVISE FOOTING F-2. SEE RECOMMENDATION
 ON SOIL TEST REPORT FOR MINIMUM SIZE
 OF CONTINUOUS FOOTINGS. REVISE DWG.
 3-PROVIDE PRODUCT APPROVAL FOR: ENTRY
 DOORS WITH SIDELITES ASSEMBLY, WINDOW
 AND DOOR MULLIONS, ROOF TILE, GARAGE
 DOOR.
 NOTE: NORANDEX PRODUCT APPROVALS ARE
 NOT ACCEPTED UNLESS THEY PROVIDE SITE
 SPECIFIC COMPLETE ENGINEERING
 CALCULATIONS OR APPROVED PRODUCT
 APPROVAL.
 4-STORM PANELS:
 -INSTALLATION SCHEDULE, KEY PLAN AND
 ENGINEER FLOOR PLANS DON'T MATCH.
 REVISE AS REQUIRED.
 5-PROVIDE SAFETY GLASS AS REQUIRED. SEE
 PLANS FOR COMMENTS.SEC 2405.2 SBC 1997
 6-MASTER BEDROOM OPTION OF HAVING 34/5
 SINGLE HUNG WINDOW (SHEET A-2) DOESN'T
 MEET THE MINIMUM EGRESS REQUIREMENTS
 SEC. 1005.4.4 SBC 1997.
 7-UPDATE ALL ENGINEERED TRUSSES:
 -REVISE MEAN ROOF HEIGHT.SEE ELEVATIONS
 -DESIGN CRITERIA ACCEPTED BY THIS
 OFFICE IS SBC 1997 OR ASCE 7-95 AND
 MUST BE INCORPORATED IN THE ENGINEERED
 TRUSSES (CUT AND PASTE JOB WILL NOT BE
 ACCEPTED).
 8-PROVIDE COMPLETE SECTION/DETAIL AT
 MIDDLE BEARING POINT OF TRUSS D-16.
 SPECIFY ALL CONNECTORS (TOP & BOTTOM)
 SEC. 104.2.2 CITY AMENDMENTS.
 NOTE: ENGINEERED TRUSS DRAWING D-16
 CALLS FOR A BEARING SIZE OF 5".8.CHECK
 9-PROVIDE COMPLETE BUCK DETAILS FOR ALL
 EXTERIOR WINDOW TYPES, ALL EXTERIOR
 DOOR TYPES AND GARAGE DOOR.
 10-NOTE:
 FLOOD ZONE A8. PROVIDE ELEVATION
 CERTIFICATE.
 11-PAY IMPACT FEES TO THE COUNTY.
 12-OWES $25.36 TO CITY FOR RADON FEES.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-10-05 Cont ID  
Sent By gjoyce Date 1999-10-05 Time 11:53 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***