Plan Review Details - Permit 99100076
Plan Review Stops For Permit 99100076
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-11-24 Cont ID  
Sent By hpiskura Date 1999-11-24 Time 10:55 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-03-23 Cont ID  
Sent By dpalmer Date 2000-03-23 Time 06:56 Rev Time 0.00
Received By dpalmer Date 2000-03-23 Time 06:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-03-03 Cont ID  
Sent By dpalmer Date 2000-03-03 Time 06:30 Rev Time 0.00
Received By dpalmer Date 2000-03-03 Time 06:29 Sent To  
Notes
2001-01-08 00:00:00************ NOTE **********************
  
 THERE STIL A PROVISO THAT HAS NOT BEEN
 ADRESSED!! SEE ATTACHED NOTES FROM JAN.
 8TH.
 PLEASE NOTE THAT THE PROVISO MUST BE
 TAKEN CARE OF BEOFORE ANY ELECTRICAL
 INSPECTION IS CALLED IN.
 IF YOU HAVE ANY QUESTIONS PLEASE DO NOT
 HESITATE IN CONTACTING US.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-01-08 Cont ID  
Sent By dpalmer Date 2000-01-08 Time 20:00 Rev Time 0.00
Received By dpalmer Date 2000-01-08 Time 20:00 Sent To  
Notes
2001-01-08 00:00:00************* PROVISO*******************
  
 1)NOTE:PLEASE CORRECT SIZE OF EQUIPMENT
 GROUNDING CONDUCTOR. SIZE AS REQ`D BY
 ART;250-95 OF THE NEC.
  
 2)NOTE: PLEASE SUBMIT MORE DETAILED
 GROUNDING SYSTEM. TO INCLUDE ANY GROUND-
 ING PLATES BEING USED.
 PLEASE SHOW,,,,GROUNDING ELECTRODE
 CONDUCTOR GOING TO ALL THE MEANS OF
 GROUNDING. TO INCLUDE GROUND RODS(S),
 BLDG.STEEL,AND COLD WATER PIPE. ALL
 AS PART OF THE SYSTEM. AS REQ`D BY ART;
 250-81 AND 215-5 OF THE NEC.
 PLEASE SHOW GROUNDING THAT IS BEING
 REQ`D FOR TELEPHONE AND COMPUTER SYSTEMS
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL
 BEFORE ANY ELECTRICAL INSPECTION IS
 CALLED IN.IF THERE ARE ANY QUESTIONS;
 CALL 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-20 Cont ID  
Sent By jleahy Date 1999-10-20 Time 16:02 Rev Time 1.15
Received By jleahy Date 1999-10-20 Time 16:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-10-12 Cont ID  
Sent By ndenmark Date 1999-10-12 Time 11:10 Rev Time 0.15
Received By ndenmark Date 1999-10-12 Time 11:09 Sent To  
Notes
2001-01-08 00:00:00PROVIDE PERMIT AND SHOPDRAWINGS FOR
 FIRE SPRINKLER REMODEL

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-25 Cont ID  
Sent By ndenmark Date 1999-10-25 Time 08:51 Rev Time 1.00
Received By ndenmark Date 1999-10-25 Time 08:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-03-04 Cont ID  
Sent By tlarge Date 2000-03-04 Time 08:36 Rev Time 0.00
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 CLEARLY INDICATE AREAS OF REVISIONS ON
 PLANS AND PROVIDE CORRECT PERMIT NUMBER.

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-12-02 Cont ID  
Sent By tlarge Date 1999-12-02 Time 09:58 Rev Time 1.00
Received By tlarge Date 1999-12-02 Time 09:58 Sent To  
Notes
2001-01-08 00:00:00SEE NOTE ATTACHED TO PLANS REGARDING
 OCCUPANT LOAD.

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-11-30 Cont ID  
Sent By tlarge Date 1999-11-30 Time 09:44 Rev Time 2.50
Received By tlarge Date 1999-11-30 Time 09:43 Sent To  
Notes
2001-01-08 00:00:00THE NUMBER AND TYPE OF REQD.PLUMBING
 FIXTURES SHALL COMPLY W/SPC TABLE 407.
  
 OCCUPANT LOAD SHALL BE BASED ON SQUARE
 FOOTAGE OF HABITABLE FLOOR SPACE PER SPC
 SEC.407.1.3.
  
 SHT.M-1.-LOOP VENT SHALL REMAIN 1/2 PIPE
 SIZE OF HORIZONTAL WASTE LINE.(3" VTR.)
  
 HOSE BIBBS SHALL BE VALVED PER SPC
 610.4.1.
  
 WATER TREATMENT UNIT SHALL BE NSF
 APPROVED PER SPC SEC.615.1.
  
 EMERGENCY PAN DRAIN SHALL DISCHARGE TO
 AN OBSERVABLE POINT.REFER TO MECH.CODE.

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-10-17 Cont ID  
Sent By pschmitz Date 1999-10-17 Time 17:04 Rev Time 1.00
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW UNSAT
 (1) SHT M-1 MENS RM H/C STALL,LAVATORY
 CLEARANCE,A CLEAR FLR SPACE OF 30"X48"
 SHALL BE PROVIDED IN FRONT OF LAVATORY.
 FACBC 4.19.3 DOOR SHOULD SWING OUT.
 (2) DISH WASHING MACHINE P-7,WASTE TO
 SANITARY SEWER LOCAL ORDINANCE.
 (3) SHOW CALCULATIONS TO COMPLY WITH
 MINIMUM FAILITIES SPC TAB 407
 NUMBER OF PLUMBING FIXTURES REQUIRED.
 END OF COMMENTS