Plan Review Details - Permit 99100065
| Plan Review Stops For Permit 99100065 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
|
Date |
1999-10-12 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
1999-10-12 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
1999-10-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-10-13 |
Time |
18:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
1999-10-13 |
Time |
18:53 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************DENIED****************** | | | | | | 1)NOTE:ELECTRICAL RISER DIAGRAM IS NOT | | | CORRECT!!! MAIN CIRCUT BREAKER PANEL | | | IS REQ`D OR MAIN DISC. YOU SHOW MAIN | | | LUG ONLY AND NO FORM OF MAIN DISC. | | | 2)NOTE;ALSO GROUNDING ELECTRODE | | | CONDUCTOR IS ONLY INSTALLED AFTER THE | | | FIRST MEANS OF DISC. YOU SHOW GRND. | | | BEING INSTALLED FROM METER TO PANEL???? | | | 3)NOTE:AS PER 250-81MORE THAN ONE | | | GROUNDING ELECTRODE IS REQ`D. | | | 4)NOTE;LOAD CALCULATIONS ARE NOT CORRECT | | | LOAD CANNOT BE DERATED FOR CONTINOUS | | | LIGHTING LOAD.!!! | | | PLEASE DOUBLE CHECK TRAILER FOR OTHER | | | LOADS ;;;SUCH AS AIR CONDITIONING,FRIG, | | | HOT WATER HEATER ETC.LEASING TRAILER | | | WOULD MOST LIKELY HAVE A/C. | | | PLEASE REDO LOAD CALCS. | | | | | | ALL THE ABOVE MUST BE DONE AND SUBMITTED | | | FOR REVIEW AND APPROVAL. | | | THE ABOVE FALLS UNDER ART;215-5 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
1999-10-12 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
1999-10-12 |
Time |
14:38 |
Rev Time |
0.10 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVIDE SMOKE DETECTOR & 2A RATED 10BC | | | FIRE EXTINGUISHER |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
1999-10-18 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-10-18 |
Time |
07:19 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
1999-10-18 |
Time |
07:19 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NO MECHANICAL |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
1999-10-17 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
1999-10-17 |
Time |
15:18 |
Rev Time |
0.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW UNSAT | | | (1) SHT-A1 SPC 94 SEC 301.11.1 | | | CONNECTIONS TO THE DRAINAGE SYSTEM | | | REQIRED, THE USE OF SEWAGE HOLDING TANKS | | | NEEDS TO BE APPROVED BY PALM BCH COUNTY | | | HEALTH DEPT. CONTACT STEVE KOPROW | | | 561-233-5150. | | | (2) WATER SUPPLY TO TRAILER TO BE | | | PROTECTED WITH A REDUCED PSI TYPE BACK | | | FLOW PREVENTER,SPC 94 SEC 601.6 | | | END OF COMMENTS |
|
|
|