Plan Review Details - Permit 99100065
Plan Review Stops For Permit 99100065
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date 1999-10-12 Cont ID  
Sent By bstaples Date 1999-10-12 Time 14:29 Rev Time 0.00
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1999-10-13 Cont ID  
Sent By dpalmer Date 1999-10-13 Time 18:53 Rev Time 0.00
Received By dpalmer Date 1999-10-13 Time 18:53 Sent To  
Notes
2001-01-08 00:00:00***************DENIED******************
  
 1)NOTE:ELECTRICAL RISER DIAGRAM IS NOT
 CORRECT!!! MAIN CIRCUT BREAKER PANEL
 IS REQ`D OR MAIN DISC. YOU SHOW MAIN
 LUG ONLY AND NO FORM OF MAIN DISC.
 2)NOTE;ALSO GROUNDING ELECTRODE
 CONDUCTOR IS ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISC. YOU SHOW GRND.
 BEING INSTALLED FROM METER TO PANEL????
 3)NOTE:AS PER 250-81MORE THAN ONE
 GROUNDING ELECTRODE IS REQ`D.
 4)NOTE;LOAD CALCULATIONS ARE NOT CORRECT
 LOAD CANNOT BE DERATED FOR CONTINOUS
 LIGHTING LOAD.!!!
 PLEASE DOUBLE CHECK TRAILER FOR OTHER
 LOADS ;;;SUCH AS AIR CONDITIONING,FRIG,
 HOT WATER HEATER ETC.LEASING TRAILER
 WOULD MOST LIKELY HAVE A/C.
 PLEASE REDO LOAD CALCS.
  
 ALL THE ABOVE MUST BE DONE AND SUBMITTED
 FOR REVIEW AND APPROVAL.
 THE ABOVE FALLS UNDER ART;215-5

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-10-12 Cont ID  
Sent By bstaples Date 1999-10-12 Time 14:38 Rev Time 0.10
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE SMOKE DETECTOR & 2A RATED 10BC
 FIRE EXTINGUISHER

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 1999-10-18 Cont ID  
Sent By ndenmark Date 1999-10-18 Time 07:19 Rev Time 0.25
Received By ndenmark Date 1999-10-18 Time 07:19 Sent To  
Notes
2001-01-08 00:00:00NO MECHANICAL

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-10-17 Cont ID  
Sent By pschmitz Date 1999-10-17 Time 15:18 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW UNSAT
 (1) SHT-A1 SPC 94 SEC 301.11.1
 CONNECTIONS TO THE DRAINAGE SYSTEM
 REQIRED, THE USE OF SEWAGE HOLDING TANKS
 NEEDS TO BE APPROVED BY PALM BCH COUNTY
 HEALTH DEPT. CONTACT STEVE KOPROW
 561-233-5150.
 (2) WATER SUPPLY TO TRAILER TO BE
 PROTECTED WITH A REDUCED PSI TYPE BACK
 FLOW PREVENTER,SPC 94 SEC 601.6
 END OF COMMENTS