Plan Review Details - Permit 99100042
Plan Review Stops For Permit 99100042
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-11 Cont ID  
Sent By dpalmer Date 1999-10-11 Time 15:25 Rev Time 0.00
Received By dpalmer Date 1999-10-11 Time 15:25 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO*****************
  
 1)NOTE:AS PER ARTS;110-9/215-5 NEED TO
 SUBMIT AIC RATING OF MAINS AND BRKRS.
 AIC RATING IS FIGURED FROM FAULT CURRENT
 CALCULATIONS.
 2)NOTE:AS PER ART:215-5 NEED TO HAVE
 RISER DIAGRAM CORRELATE WITH PANEL SCHED
 RISER DIAGRAM SHOWS MLO PANEL??NEED MAIN
 DISC. OR MAIN BRKR PANEL WHICH IS WHAT
 PANEL SCHEDULE SHOWS.
 ALSO EQUIPMENT GROUND IS ONLY USED AFTER
 FIRST MEANS OF DISC.
 3)NOTE:AS PER ART;250-81 NEED TO SHOW
 GROUNDING CONDUCTOR ON PANEL SCHEDULE
 GOING TO COLD WATER PIPE AND BLDG.STEEL
 ALSO.
 4)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 5)NOTE:PLEASE DRAW IN A/C COND. AND
 THE FOLLOWING:REQ`D BY CODE.ART;440-11
 A/C DISC. AND WP GFI AS PER 210-63
  
 NEED TO HAVE THE ABOVE SUBMITTED FOR
 REVIEW AND AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-02 Cont ID  
Sent By jleech Date 2000-03-02 Time 15:48 Rev Time 0.25
Received By jleech Date 2000-03-02 Time 15:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-07 Cont ID  
Sent By jleech Date 1999-10-07 Time 11:27 Rev Time 0.50
Received By jleech Date 1999-10-07 Time 11:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-12-08 Cont ID  
Sent By tlarge Date 1999-12-08 Time 15:30 Rev Time 0.50
Received By sgraham Date 1999-12-08 Time 15:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-12-13 Cont ID  
Sent By tlarge Date 1999-10-07 Time 06:26 Rev Time 0.33
Received By sgraham Date 1999-10-07 Time 06:26 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-12-13 Cont ID  
Sent By jcaloger Date 1999-10-28 Time 08:45 Rev Time 8.50
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-10-05 Cont ID  
Sent By gjoyce Date 1999-10-04 Time 08:55 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00SURVEY DOES NOT MATCH FLOOR PLAN