Plan Review Details - Permit 99100040
Plan Review Stops For Permit 99100040
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-12 Cont ID  
Sent By dpalmer Date 1999-10-12 Time 07:02 Rev Time 0.00
Received By dpalmer Date 1999-10-12 Time 07:02 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO*****************
  
 1)NOTE:THE RISER DIAGRAM SHOWS (MLO)
 PANELS, NEED TO SHOW THEM AS (MCB)
 PANELS,AS SOME FORM OF MAIN DISC.IS REQ`
 ALSO EQUIPMENT GROUND IS SHOWN FROM
 METER TO PANEL,,,,EQUIPMENT GROUND IS
 ONLY TO BE INSTALLED AFTER FIRST MEANS
 OF DISC.ALL THE ABOVE PER 215-5
 2)NOTE:AS PER ART;250-81 GROUNDING
 ELECTRODE CONDUCTOR IS REQ`D TO GO TO
 COLD WATER PIPE AND BLDG.STEEL.PLEASE
 SHOW.AS PER 215-5
 3)NOTE;AS PER 110-9/215-5 NEED TO SUBMIT
 AIC RATING OF EQUIPMENT:TO INCLUDE MAINS
 AND BRANCH CIRCUT BRKRS. AIC RATING IS
 FIGURED FROM FAULT CURRENT CALCULATIONS
 4)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 SMOKE DETECTOR IS REQ`D OUTSIDE ALL
 SLEEPING ROOMS IN RESIDENTIAL DWELLINGS.
 5)NOTE:NEED TO SHOW A/C EQUIPMENT TO
 INCLUDE DISC.AS PER 440-11 AND REQ`D
 WP GFI RECEPT. PER 210-63
  
 NEED TO HAVE THE ABOVE SUBMITTED FOR
 REVIEW AND APPROVAL BEFORE FIRST
 ROUGH ELECTRICAL INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-01-06 Cont ID  
Sent By jleech Date 2000-01-06 Time 08:30 Rev Time 0.35
Received By jleech Date 2000-01-06 Time 08:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-01-06 Cont ID  
Sent By jleech Date 1999-10-12 Time 13:42 Rev Time 0.35
Received By jcaloger Date 1999-10-12 Time 13:42 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 A/C PLAN AND FLOOR PLAN ARE NOT THE SAME

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-01-04 Cont ID  
Sent By tlarge Date 2000-01-04 Time 17:51 Rev Time 0.33
Received By tlarge Date 2000-01-04 Time 17:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-01-04 Cont ID  
Sent By tlarge Date 1999-10-07 Time 06:35 Rev Time 0.33
Received By tlarge Date 1999-10-07 Time 06:35 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-01-06 Cont ID  
Sent By jcaloger Date 1999-12-08 Time 13:43 Rev Time 2.00
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00THE ARCHITECT & ENGINEERING PLANS NEED
 THERE ORGINAL SIGNATURE ON EACH PLAN.
  
 THE FRONT ENTRY DOOR IS REQUIRED TO
 PROVIDE 32" CLEAR OPENING WHEN ONE LEAF
 IS OPENED.ATTACHED IS A COPY OF THE
 SBCCI INTERPERTATION WHICH THE BUILDING
 OFFICIALS SUPPORTS. PLANS NEED TO BE
 REVISED.
  
 PROVIDE ATTIC ACESS TO THE LOW ROOF
 WHICH IS LOCATED OVER THE KITCHEN AREA.
  
 SPECIFY AND LOCATE ON THE PLANS THE
 BEARING WALLS AND COLUMNS, STUD SPACING.
  
 SPECIFY ON THE WALL SECTION THE STUCCO
 THICKNESS,INTERIOR WALL FINISH, FURRING
 SPACE, CEILING FINISH, FOOTER RECESS
 DIMENSION, ROOF UNDERLAYMENT FELT PAPER,
 ROOF FINISH AND ATTACHMENT.
  
 THE TRUSSLAYOUT FROM THE TRUSS COMPANY
 SPECIFYS THAT FG2 TRUSS HAS A CONNECTION
 WITH A 11,311LBS.PROVIDE THE CONNECTIO
 DETAIL.
  
 PROVIDE ALL ENGINEERING DETAILS WHICH
 WERE PROVIDED WITH THE PLANS FOR LOT 10.
  
 THE LEFT RIGHT ELEVATION EXCEEDS THE
 PERCENTAGE OF OPENINGS ALLOWED BY TABLE
 600.WALL AREA IS AS FOLLOWS:
 12 X 10= 120SF
 7'6" X 18= 135SF
 255SF X 40 %=102SF ALLOWED
 WALL OPENINGS8X8=64SF
 6X8=48
 2X2=4
 116-102=14SF OVER ALOW
  
 ATTACHED IS A COPY OF THE REVISED
 DESIGN COMPLIANCE FORM WHICH NEEDS TO
 BE COMPLETED.
  
 NEEDS COUNTY IMPACT FEES PAID.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-10-05 Cont ID  
Sent By gjoyce Date 1999-10-04 Time 08:56 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00SURVEY DOES NOT MATCH FLOOR PLAN