Plan Review Details - Permit 99091140
| Plan Review Stops For Permit 99091140 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-10-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
1999-10-08 |
Time |
07:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
1999-10-08 |
Time |
07:25 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************PROVISO****************** | | | | | | 1)NOTE; AS PER ARTS:110-9/215-5 NEEED TO | | | SUBMIT AIC RATING OF EQUIPMENT,MAINS AND | | | BRKRS.AIC RATING IS DERIVED FROM FAULT | | | CURRENT CALCULATIONS. | | | 2)NOTE:NEED TO HAVE GROUND RODS INCLUDED | | | AS APART OF THE GROUNDING ELECTRODE | | | SYSTEM ON THE RISER DIAGRAM. 215-5 | | | | | | NEED TO HAVE THE ABOVE SUBMITTED FOR | | | REVIEW AND APPROVAL BEFORE FIRST ROUGH | | | ELECTRICAL INSPECTION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-10-12 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
1999-10-07 |
Time |
13:09 |
Rev Time |
0.35 |
| Received By |
jleech |
Date |
1999-10-07 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED; | | | NO A/C PLAN. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
1999-11-27 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-11-27 |
Time |
13:48 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
1999-11-27 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISED PLBG.RISER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
1999-10-07 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-10-07 |
Time |
06:51 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
1999-10-07 |
Time |
06:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2000-02-08 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2000-02-08 |
Time |
16:23 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2000-02-08 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | TRUSS DRAWINGS CHECKLIST: | | | 1-ENGINEERED TRUSS DRAWINGS NEED TO BE | | | UPDATED TO REFLECT SBC 1997. | | | ALTERNATIVE: ASCE-95. | | | 2-THERE IS ONLY ONE MEAN ROOF HEIGHT FOR | | | ENTIRE BUILDING. TABLE 1606.2A SBC/97. | | | REVISE ENGINEERED TRUSSES AS REQUIRED. | | | MEAN ROOF HEIGHT 19'-0" PLUS OR MINUS. | | | 3-ENGINEERED TRUSSES TO BE MANUALLY | | | SIGNED, NOT RUBBER STAMPED. | | | 4-ARCHITECT OF RECORD TO REVIEW ALL | | | TRUSS DRAWINGS PRIOR TO SUBMITTAL TO | | | THIS OFFICE. | | | | | | NOTE: | | | CHECK/REVISE ALL UPLIFT CONNECTOR | | | SPECIFIED TO ASCERTAIN THAT THEY WILL | | | RESIST THE UPLIFT LOADS CALCULATED ON | | | THE ENGINEERED TRUSSES. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
1999-10-21 |
|
|
Cont ID |
|
| Sent By |
jcaloger |
Date |
1999-10-21 |
Time |
11:16 |
Rev Time |
2.50 |
| Received By |
jcaloger |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
1999-10-21 |
|
|
Cont ID |
|
| Sent By |
jcaloger |
Date |
1999-10-21 |
Time |
11:16 |
Rev Time |
0.50 |
| Received By |
jcaloger |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | APPROVED BY GRACE JOYCE ON 10/4 |
|
|
|