Plan Review Details - Permit 99091140
Plan Review Stops For Permit 99091140
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-08 Cont ID  
Sent By dpalmer Date 1999-10-08 Time 07:26 Rev Time 0.00
Received By dpalmer Date 1999-10-08 Time 07:25 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO******************
  
 1)NOTE; AS PER ARTS:110-9/215-5 NEEED TO
 SUBMIT AIC RATING OF EQUIPMENT,MAINS AND
 BRKRS.AIC RATING IS DERIVED FROM FAULT
 CURRENT CALCULATIONS.
 2)NOTE:NEED TO HAVE GROUND RODS INCLUDED
 AS APART OF THE GROUNDING ELECTRODE
 SYSTEM ON THE RISER DIAGRAM. 215-5
  
 NEED TO HAVE THE ABOVE SUBMITTED FOR
 REVIEW AND APPROVAL BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-12 Cont ID  
Sent By jleech Date 1999-10-07 Time 13:09 Rev Time 0.35
Received By jleech Date 1999-10-07 Time 13:09 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 NO A/C PLAN.

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-11-27 Cont ID  
Sent By tlarge Date 1999-11-27 Time 13:48 Rev Time 0.33
Received By tlarge Date 1999-11-27 Time 13:48 Sent To  
Notes
2001-01-08 00:00:00REVISED PLBG.RISER.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-07 Cont ID  
Sent By tlarge Date 1999-10-07 Time 06:51 Rev Time 0.50
Received By tlarge Date 1999-10-07 Time 06:51 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-02-08 Cont ID  
Sent By jgomez Date 2000-02-08 Time 16:23 Rev Time 1.00
Received By jgomez Date 2000-02-08 Time 16:23 Sent To  
Notes
2001-01-08 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-ENGINEERED TRUSS DRAWINGS NEED TO BE
 UPDATED TO REFLECT SBC 1997.
 ALTERNATIVE: ASCE-95.
 2-THERE IS ONLY ONE MEAN ROOF HEIGHT FOR
 ENTIRE BUILDING. TABLE 1606.2A SBC/97.
 REVISE ENGINEERED TRUSSES AS REQUIRED.
 MEAN ROOF HEIGHT 19'-0" PLUS OR MINUS.
 3-ENGINEERED TRUSSES TO BE MANUALLY
 SIGNED, NOT RUBBER STAMPED.
 4-ARCHITECT OF RECORD TO REVIEW ALL
 TRUSS DRAWINGS PRIOR TO SUBMITTAL TO
 THIS OFFICE.
  
 NOTE:
 CHECK/REVISE ALL UPLIFT CONNECTOR
 SPECIFIED TO ASCERTAIN THAT THEY WILL
 RESIST THE UPLIFT LOADS CALCULATED ON
 THE ENGINEERED TRUSSES.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-10-21 Cont ID  
Sent By jcaloger Date 1999-10-21 Time 11:16 Rev Time 2.50
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-10-21 Cont ID  
Sent By jcaloger Date 1999-10-21 Time 11:16 Rev Time 0.50
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 APPROVED BY GRACE JOYCE ON 10/4