| Plan Review Stops For Permit 99091126 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
1999-11-01 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-11-01 |
Time |
16:07 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-10-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
1999-10-20 |
Time |
14:21 |
Rev Time |
1.30 |
| Received By |
jleahy |
Date |
1999-10-20 |
Time |
14:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
P |
Date |
2000-12-12 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2000-12-12 |
Time |
07:11 |
Rev Time |
0.50 |
| Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PASSED | | | DRAINAGE AS-BUILTS RECEIVED. C5 | | | MUST SUBMITT DISK TO | | | MANNY GONZALEZ | | | PUBLIC UTILITIES ENGINEERING | | | 1000 45TH ST. WPB, FL 33407 | | | OR YOU MAY E-MAIL TO | | | [email protected] | | | THANK YOU. | | | PLEASE INCLUDE WATER AND SEWER AS-BUILTS | | | AS WELL. 2 MYLAR SETS WILL NEED TO | | | BE SUBMITTED FOR WATER AND SEWER SHEET. | | | IF ANY QUESTIONS FEEL FREE TO CONTACT | | | OUR OFFICE AT 561 659 8040 EXT. 2306 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
1999-12-28 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
1999-12-28 |
Time |
11:12 |
Rev Time |
1.00 |
| Received By |
dlauderm |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PER DEAN LOUDERMILK 12/28/99 LS |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2000-05-30 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
1999-11-30 |
Time |
14:49 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
1999-11-30 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | COMMENTS BY MANNY GONZALEZ AS PROVISOS | | | 1. SAMPLE POINT NEEDED AT METER | | | 2. ON CROSSING 3 AN 18" VERTICAL CLEARAN | | | CE REQUIRED BETWEEN WATER AND SANITARY | | | 3. SHOW PROPOSED SEWER LINE BOLDER | | | 4. REVISE ALL CROSSINGS TO REFLECT THE | | | PROPER PIPE SIZE | | | APPROVED WITH PROVISOS | | | I HAVE NOTIFIED PETER VANRENZ | | | AT KIMLEY HORN TO SUBMITT TRASH | | | ENCLOUSURE AND DETAILS. | | | | | | THE STORM SEWER WAS REVIEWED ON THE | | | OVER ALL HOME DEPOT SITE PROJECT | | | | | | SANITATION: | | | NO DUMPSTER ENCLOSURE SHOWN. STATE IF IT | | | IS TO BE CITY PICK UP OR PRIVATE.IF | | | CITY PICKUP THEN THE FOLLOWING | | | REQUIREMENTS MUST BE MET; DUMPSTER MUST | | | HAVE A MINIMUM OF 12' OPENING BETWEEN | | | THE GATE POSTS.INTERIOR DIMENSIONS OF | | | THE ENCLOSURE MUST BE A MINIMUM OF 12' | | | WIDE AND 12' DEEP.A CONCRETE PARKING | | | STOP BAR MUST BE CENTERED (FROM GATES) | | | AND INSTALLED 18" FROM THE BACK WALLED. | | | STEEL BARS WILL BE DRILLED OR THRU THE | | | STOP BAR AND INTO THE INTERIOR FLOOR OF | | | THE ENCLOSURE TO STOP THE BAR FROM MOVIN | | | WHEN THE DUMPSTER IS SET INSIDE. THE | | | OPENING OF THE DUMPSTER ENCLOSURE MUST | | | BE PLACED SO THAT A 40' LONG TRUCK WITH | | | THE FORKS EXTENDED CAN APPROACH THE | | | OPENING AND PICK UP THE DUMPSTER WITHOUT | | | TURNING A SHARP TURN. NOTHING MAY BE | | | PLACED OVERHEAD IN THE AREA WHERE THE | | | DUMPSTER ENCLOSURE IS SO THAT WHEN THE | | | DUMPSTER IS PICKED UP AND DUMPED THE | | | DUMPSTER NOR THE TRUCK OR TRUCK FORKS | | | WILL BE IMPEDED. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
1999-11-01 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-11-01 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
mgonzale |
Date |
1999-10-06 |
Time |
11:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-10-20 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-10-20 |
Time |
07:46 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
1999-10-20 |
Time |
07:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1) FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | REQUIRED FOR AHUS 1,2,3 PER 1997 SMC | | | 406.1 | | | 2)NOTIFICATION BY HORN AND STROBE OF FAN | | | SHUT DOWN REQUIRED BY NFPA 4-4.4.3 | | | 3)ADDITIONAL MECHANICAL PERMITS REQUIRED | | | FOR FUEL AND WALK IN COOLER |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-12-09 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-12-09 |
Time |
10:11 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2000-12-09 |
Time |
10:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-11-27 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-27 |
Time |
13:22 |
Rev Time |
0.75 |
| Received By |
jleech |
Date |
2000-11-27 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | AS BUILDS CAR WASH DRAINAGE AND WATER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
1999-11-27 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-11-27 |
Time |
09:57 |
Rev Time |
1.25 |
| Received By |
tlarge |
Date |
1999-11-27 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************PROVISO***************** | | | SUBMIT SHOP DWGS.FOR AIR/WATER & OIL INT | | | AT CAR WASH. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
1999-10-13 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-10-13 |
Time |
06:47 |
Rev Time |
2.50 |
| Received By |
tlarge |
Date |
1999-10-13 |
Time |
06:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CLEARLY SHOW LOCATION OF GREASE | | | INTERCEPTOR ON PLANS.SPC 104.2.1. | | | | | | CONTACT RODNEY COMPO AT CITY OF W.P.B. | | | REGIONAL WASTEWATER TREATMENT PLANT FOR | | | GREASE TRAP REQS.(561)835-7423. | | | | | | MULTIPLE CONDENSATE DRAINS SHALL BE | | | SIZED PER STD.MECH.CODE SEC.304.8.4. | | | | | | RECEPTACLES FOR INDIRECT WASTES SHALL BE | | | FLOOR DRAINS OR FLOOR SINKS PER SPC SEC. | | | 807. | | | | | | CLEARLY SHOW TERMINATION PT.OF TRENCH | | | DRAIN AT CAR WASH.SPC 104.2.1. | | | | | | VENTING FOR SANITARY SYSTEM SHALL COMPLY | | | W/SPC SEC.920.2. | | | | | | SPACING FOR COPPER TUBE SHALL BE 10'MAX. | | | FOR SIZES 2" AND HIGHER PER SPC SEC. | | | 310.3.4.(REVISE SPECS.) | | | | | | HOT WATER TO RESTROOMS SHALL BE 110 | | | DEGREES MAX.PER FLA.ENERGY CODE SEC. | | | 412.1ABCD.2.3.2. | | | | | | CONDENSATE DRAINS SHALL TERMINATE PER | | | SEC.804.3 OF COUNTYWIDE AMENDMENTS TO | | | STD.PLBG.CODE. | | | | | | DRAINS FROM SODA FOUNTAINS SHALL DRAIN | | | TO GREASY WASTE SYSTEM.SPC 1004.1. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
1999-12-28 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
1999-12-28 |
Time |
11:15 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PER SEAN & GRACE 12/28/99 |
|
|