| Plan Review Stops For Permit 99091124 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-08-19 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-08-19 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
1999-12-02 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-12-02 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
1999-12-02 |
Time |
16:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
1999-11-05 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-11-05 |
Time |
08:43 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLAN REVIEW COMMENTS ATTACHED TO PLANS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-10-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-03 |
Time |
07:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-03 |
Time |
07:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-10-21 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
1999-10-21 |
Time |
14:40 |
Rev Time |
1.00 |
| Received By |
jleahy |
Date |
1999-10-21 |
Time |
14:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
1999-12-13 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-12-13 |
Time |
12:17 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED ON PUBLIX SITE PERMIT |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
1999-11-03 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
1999-11-03 |
Time |
14:48 |
Rev Time |
0.15 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-10-20 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-10-20 |
Time |
13:33 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
1999-10-20 |
Time |
13:33 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1) FAN SHUT DOWN REQUIRED FOR AHU 1,2&3 | | | BY DUCT SMOKE DETECTOR PER 1997 SMC 406 | | | 2) NOTIFICATION BY HORN AND STROBE OF | | | FAN SHUT DOWN REQUIRED BY NFPA 4-4.4.3 | | | 3) ADDITIONAL MECHANICAL PERMITS REQUIRE | | | FOR FUEL AND WALK IN COOLER |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2000-09-01 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-01 |
Time |
18:01 |
Rev Time |
0.75 |
| Received By |
pschmitz |
Date |
2000-09-01 |
Time |
17:42 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)TWO WAY CLEANOUTS REQD.ENTERING AND | | | LEAVING EACH TANK.SEE 750 GAL RECLAIM | | | TANK.SPC SEC.710.4. | | | | | | 2)SIZE OF TANKS DO NOT MATCH APPROVED | | | PLANS.SEE RECLAIM TANK AND OIL/SAND INT. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | 3)VENT SHALL RISE 6" ABOVE FLOOD LEVEL | | | OF INT.PRIOR TO OFFSETTING HORIZ.SPC | | | 906.2.1. | | | | | | 4)SUBMIT FULL SIZE BLUEPRINTS FOR REVIEW | | | THAT ARE SIGNED,DATED AND SEALED BY THE | | | DESIGN PROFESSIONAL OF RECORD.SPC SEC. | | | 104.2.3. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
1999-11-27 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-11-27 |
Time |
11:23 |
Rev Time |
1.00 |
| Received By |
tlarge |
Date |
1999-11-27 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ******************PROVISO*************** | | | SHOP DRAWINGS REQD.FOR AIR/WATER & OIL | | | SEPARATOR AT CAR WASH. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
1999-10-19 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-10-19 |
Time |
15:52 |
Rev Time |
4.75 |
| Received By |
pschmitz |
Date |
1999-10-19 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | JOB SPECS.-PG.155-SEC.3.01(C)-HANGERS | | | FOR COPPER TUBE 2" & LARGER SHALL COMPLY | | | W/SPC SEC.310.3.4. | | | | | | CONTACT RODNEY COMPO AT CITY OF W.P.B. | | | REGIONAL WASTEWATER TREATMENT PLANT FOR | | | SIZE REQS.OF GREASE AND SAND/OIL INTER- | | | CEPTORS.(561)835-7423. | | | | | | SHT.P-1-VENTS THRU ROOF CANNOT BE | | | INCREASED PER SPC 905.2.(ONLY USED FOR | | | FROST CLOSURE.) | | | | | | MULTIPLE CONDENSATE DRAINS SHALL BE | | | SIZED PER STD.MECH.CODE SEC.304.8.4. | | | | | | RECEPTACLES FOR INDIRECT WASTES SHALL | | | BE FLOOR DRAINS OR FLOOR SINKS PER SPC | | | SEC.807. | | | | | | CLEARLY SHOW TERMINATION POINT OF TRENCH | | | DRAIN AT CAR WASH.COMPLY W/SPC SEC.104.2 | | | 1004.5,1004.6. | | | | | | VENTING FOR SANITARY SYSTEM SHALL COMPLY | | | W/SPC SEC.920.2.(NOTE CAPACITY OF 1 1/2" | | | VENT.) | | | | | | SHT.4 OF 8 SHOWS 2"WATER SERVICE AND SHT | | | P2 SHOWS 1 1/2".CLARIFY.SPC 104.2.1. | | | | | | SIZE THE COOLER DRAINS ON SHT.P1.COMPLY | | | W/SPC SEC.713.3,714.2. | | | | | | INDIRECT WASTES SHALL BE TRAPPED AND | | | COMPLY W/SPC SEC.805.1.1,805.1.2. | | | | | | SUBMIT RISER DIAGRAMS FOR AIR/WATER | | | SYSTEMS.SPC 104.2.1. | | | | | | SUBMIT MANUF.DATA FOR GREASE/OIL INTER. | | | 104.2.2. | | | | | | DRAINS FROM SODA FOUNTAINS SHALL DRAIN | | | TO GREASY WASTE SYSTEM.SPC 1004.1 | | | | | | HOT WATER TO RESTROOMS SHALL BE 110 | | | DEGREES MAX PER FLA.ENERGY CODE SEC. | | | 412.1 ABCD.2.3.2. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
1999-12-13 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-12-13 |
Time |
12:15 |
Rev Time |
99.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|