Plan Review Details - Permit 99091064
Plan Review Stops For Permit 99091064
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-07 Cont ID  
Sent By dpalmer Date 1999-10-07 Time 18:05 Rev Time 0.00
Received By dpalmer Date 1999-10-07 Time 18:05 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*****************
  
 *1)NOTE:AS PER ARTS;110-9/215-5 NEED TO
 SUBMIT AIC RAING OF NEW EQUIPMENT TO
 INCLUDE MAINS AND BREAKERS. FIGURED
 FROM FAULT CURRENT CALCULATIONS.
 HAVE AIC RATING DRAWN ON PANEL SCHEDULE.
 *2)NOTE:PANEL SCHEDULE SHOW 150AMP
 MAIN BRKR. NEEDS TO BE 200 AMPS
 TO MATCH WHAT IS DRAWN ON RISER DIAGRAM.
 215-5
 *3)NOTE:NEED TO BOND STEEL OF NEW
 ADDITION TO GROUNDING ELECTRODE COND.
 ART;250-81
 *4)NOTE:LOAD CALCULATIONS SHOW 1700 SQ.
 FT. USED, YET SHEET A-1 SHOW SQ.FT.
 BEING 1872 SQ.FT. WITHOUT THE GARAGE.
 PLEASE REDO LOAD CALCULATIONS TO
 CORRELATE TO A-1
 *5)NOTE:AS PER ART:210-52 OUTLET SPACING
 TO MEET NEC.
 *6)NOTE:AS PER ART:210-52D A SEPARATE
 20 AMP CIRCUT IS REQ`D FOR BATH GFI REC.
 *7)NOTE: MASTER BEDROOM SHOWS SWITCH??
 DOES IT SERVE FOR MEANS OF EGRESS LIGHT-
 -ING WHICH IS REQ`D BY ART:210-70
 *8)NOTE: AS REQ`D BY 1993/1996 NFPA-72
 SEC.2-2.1.1.1 SMOKE DETECTORS ARE REQ`D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 IN RESIDENTIAL DWELLINGS OF NEW
 CONSTRUCTION.
  
 NOTE:ON NOTES ON YOUR PLANS YOU SHOW
 EACH APARTMENT???PLEASE REMOVE IF NOT
 NEEDED.
  
  
 NEED TO HAVE PLANS CORRECTED AND DRAWN
 OVER TO REFLECT CHANGES REQUESTED.
 PLEASE SUBMIT FOR REVIEW AND APPROVAL
 BEFORE FIRST ELECTRICAL INSPECTION IS
 CALLED IN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-08 Cont ID  
Sent By jleech Date 1999-10-08 Time 08:59 Rev Time 0.35
Received By jleech Date 1999-10-08 Time 08:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-06 Cont ID  
Sent By pschmitz Date 1999-10-06 Time 15:09 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 1999-11-10 Cont ID  
Sent By fknapp Date 1999-11-10 Time 09:51 Rev Time 2.00
Received By fknapp Date 1999-11-10 Time 09:50 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 1999-11-10 Cont ID  
Sent By fknapp Date 1999-10-12 Time 07:46 Rev Time 3.00
Received By fknapp Date 1999-10-08 Time 16:26 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 SBC 104.2.2
 1)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVAL FOR
 FRENCH DOORS
 FIX WINDOWS
 ROOF COVERING
  
 2)PROVIDE SIGNATURE OF OWNER ON ENERGY
 CALCULATIONS.
  
 3)PROVIDE SECTION DETAILS OF WALL THAT
 IS TO BE REMOVED.
  
 4)PROVIDE STORM PANEL INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC
 MOUNTING ANCHORS TO BE USED.
  
 5)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED,IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE PINK RECEIPT ATTACHED TO
 THE PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-10-01 Cont ID  
Sent By gjoyce Date 1999-10-01 Time 12:15 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***