| 2001-01-08 00:00:00 | **************PROVISO***************** |
| | |
| | *1)NOTE:AS PER ARTS;110-9/215-5 NEED TO |
| | SUBMIT AIC RAING OF NEW EQUIPMENT TO |
| | INCLUDE MAINS AND BREAKERS. FIGURED |
| | FROM FAULT CURRENT CALCULATIONS. |
| | HAVE AIC RATING DRAWN ON PANEL SCHEDULE. |
| | *2)NOTE:PANEL SCHEDULE SHOW 150AMP |
| | MAIN BRKR. NEEDS TO BE 200 AMPS |
| | TO MATCH WHAT IS DRAWN ON RISER DIAGRAM. |
| | 215-5 |
| | *3)NOTE:NEED TO BOND STEEL OF NEW |
| | ADDITION TO GROUNDING ELECTRODE COND. |
| | ART;250-81 |
| | *4)NOTE:LOAD CALCULATIONS SHOW 1700 SQ. |
| | FT. USED, YET SHEET A-1 SHOW SQ.FT. |
| | BEING 1872 SQ.FT. WITHOUT THE GARAGE. |
| | PLEASE REDO LOAD CALCULATIONS TO |
| | CORRELATE TO A-1 |
| | *5)NOTE:AS PER ART:210-52 OUTLET SPACING |
| | TO MEET NEC. |
| | *6)NOTE:AS PER ART:210-52D A SEPARATE |
| | 20 AMP CIRCUT IS REQ`D FOR BATH GFI REC. |
| | *7)NOTE: MASTER BEDROOM SHOWS SWITCH?? |
| | DOES IT SERVE FOR MEANS OF EGRESS LIGHT- |
| | -ING WHICH IS REQ`D BY ART:210-70 |
| | *8)NOTE: AS REQ`D BY 1993/1996 NFPA-72 |
| | SEC.2-2.1.1.1 SMOKE DETECTORS ARE REQ`D |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS |
| | IN RESIDENTIAL DWELLINGS OF NEW |
| | CONSTRUCTION. |
| | |
| | NOTE:ON NOTES ON YOUR PLANS YOU SHOW |
| | EACH APARTMENT???PLEASE REMOVE IF NOT |
| | NEEDED. |
| | |
| | |
| | NEED TO HAVE PLANS CORRECTED AND DRAWN |
| | OVER TO REFLECT CHANGES REQUESTED. |
| | PLEASE SUBMIT FOR REVIEW AND APPROVAL |
| | BEFORE FIRST ELECTRICAL INSPECTION IS |
| | CALLED IN. |