Plan Review Details - Permit 99091010
Plan Review Stops For Permit 99091010
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-07 Cont ID  
Sent By dpalmer Date 1999-10-07 Time 06:56 Rev Time 0.00
Received By dpalmer Date 1999-10-07 Time 06:56 Sent To  
Notes
2001-01-08 00:00:00*************PROVISO******************
  
 1)NOTE:AS PER ARTS;110-9/215-5 PLEASE
 HAVE AIC RATING DRAWN ON PANEL SCHEDULE.
 AIC RATING FIGURED FROM FAULT CURRENT
 CALCULATIONS.
 2)NOTE:RISER DIAGRAM AND PANEL SCHEDULE
 DOESN`T MATCH, RISER SHOWS (MLO) AND
 PANEL SCHED. SHOWS (MCB).
  
 PLEASE HAVE THE ABOVE INFORMATION SUB-
 -MITTED FOR REVIEW AND APPROVAL BEFORE
 FIRST ELECTRICAL INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-10-19 Cont ID  
Sent By jleech Date 1999-10-19 Time 14:31 Rev Time 0.50
Received By jleech Date 1999-10-19 Time 14:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-19 Cont ID  
Sent By jleech Date 1999-10-06 Time 13:36 Rev Time 0.50
Received By jleech Date 1999-10-06 Time 13:36 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 1.KITCHEN EXHAUST CANNOT GO THRU ZERO
 WALL.
 2.CFM CALKS TO HIGH.A/H CAN PUSH 2000
 CFMS. DRAWING SHOWS TOTAL OF 2350CFM.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-02 Cont ID  
Sent By tlarge Date 1999-10-02 Time 06:10 Rev Time 0.33
Received By tlarge Date   Time 06:10 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-06-16 Cont ID  
Sent By jgomez Date 2000-06-16 Time 12:04 Rev Time 2.00
Received By jgomez Date 2000-06-16 Time 12:04 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-TRUSS DRAWINGS:
 -THERE IS ONLY ONE MEAN ROOF HEIGHT FOR
 ENTIRE BUILDING. TABLE 1606.2A SBC/97.
 -UPDATE ALL GENERAL DETAILS ACCORDING
 TO SBC 1997 OR ASCE 7-95.
 -CLARIFY WHY THERE ARE SOME DETAILS AND
 LETTERS SEALED BY DIFFERENT ENGINEERS.
 DATE OF DOCUMENTS TO BE THE DATE WHEN
 THEY ARE SEALED.
 -WHY IS LETTER FROM SIMPSON STRONG TIE
 SEALED BY ANOTHER ENGINEER.
 2-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS "INSWING" TYPE AS SHOWN ON
 ARCHITECT'S PLANS.
 3-PRODUCT APPROVAL FOR GOLFCART DOOR
 DOESN'T MEET THE DESIGN PRESSURES
 CALCULATED BY THE ARCHITECT.
 4-ROYAL PALM ALUMINUM LETTER FROM THE
 MANAGER OF ENGINEERING TO BE SIGNED,
 SEALED AND DATED.
 5-PRODUCT APPROVAL FOR SLIDING GLASS
 DOORS WITH TRANSOM ABOVE ASSEMBLY:
 -PROVIDE PRODUCT APPROVAL FORM WITH ALL
 REQUIRED INFORMATION FROM MANUFACTURER
 ENGINEER AND PROFESSIONAL DESIGNER OF
 RECORD FOR SITE SPECIFIC INSTALLATION.
  
  
 NOTE:
 TO AVOID UNNECESSARY DELAYS, PLEASE TELL
 THE ARCHITECT AND ENGINEER TO PROVIDE
 ALL THE INFORMATION REQUIRED BY THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION WHEN SUBMITTING DOCUMENTS FOR
 PUBLIC RECORDS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-11-01 Cont ID  
Sent By jgomez Date 1999-11-01 Time 13:24 Rev Time 2.00
Received By jgomez Date 1999-11-01 Time 13:23 Sent To  
Notes
2001-01-08 00:00:00 
 APPROVED WITH PROVISO:
 1-PROVIDE A SIGNED, SEALED AND DATED
 SURVEY.
 2-UPDATE TRUSS DRAWINGS:
 -SBC 1997 OR ASCE 7-95.
 -ENGINEER OF RECOR TO REVIEW ALL TRUSS
 DRAWINGS PRIOR TO SUBMITTAL.
 3-REVISE FOOTING F2. SOIL TEST REPORT
 CALLS FOR AN 18" MIN WIDTH OF FOOTING.
 4-REVISE ENTRY DOOR. CLEAR OPENING PER
 LEAF TO BE 32" MIN. TABLE 1004 SBC/97.
 5-REVISE ALL ORIGINALS SHOWING ALL
 CORRECTIONS/CLARIFICATIONS AS REQUIRED
 6-PROVIDE COMPLETE DETAIL SHOWING
 INSTALLATION OF WINDOWS TO STEEL
 COLUMN AT BREAKFAST AREA.
 NOTE: SPECIFICATIONS MUST MEET THE
 PRODUCT APPROVAL REQUIREMENTS OR
 SPECIFIC ENGINEERING ANALYSIS WILL BE
 REQUIRED.
 7-PROVIDE COMPLETE SET OF PRODUCT
 APPROVALS, INCLUDING ENTRY DOORS,
 SLIDING GLASS DOORS WITH TRANSOM ABOVE
 ASSEMBLY, ROUND AND OVAL WINDOWS, ETC.
 8-PROVIDE CALCULATIONS TO CLARIFY WHY
 THE DESIGN PRESSURES FOR GOLFCART DOOR
 ARE LOWER THAN THOSE FOR THE REGULAR
 GARAGE DOOR.
 9-STORM PANELS:
 -PROVIDE COMPLETE INSTALLATION SCHEDULE
 (AS PER CITY SAMPLE) AND KEY PLAN.
 -HIGHLIGHT SPECIFIC MOUNTING CONDITIONS
 AND ANCHORS SPACING.
 10-SEE ADDITIONAL COMMENTS ON PLANS AND
 REVISE/CLARIFY AS REQUIRED.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-09-30 Cont ID  
Sent By gjoyce Date 1999-09-30 Time 16:27 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***