Plan Review Details - Permit 99091008
Plan Review Stops For Permit 99091008
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-07 Cont ID  
Sent By dpalmer Date 1999-10-07 Time 19:17 Rev Time 0.00
Received By dpalmer Date 1999-10-07 Time 19:17 Sent To  
Notes
2001-01-08 00:00:00************PROVISO********************
  
 1)NOTE:AS PER ARTS:110-9/215-5 NEED TO
 SUBMIT AIC RATING OF EQUIPMENT,MAINS,
 AND BRKRS. FIGURED FROM FAULT CURRENT
 CALCULATIONS.
 2)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 3)NOTE: EQUIPMENT GROUNDING CONDUCTOR
 IS NOT TO BE INSTALLED FROM METER TO
 FIRST MEANS OF DISC.ONLY FROM FIRST
 MEANS OF DISC.TO PANEL.
 4)NOTE; AS PER ART: 210-63 RECEPT. REQD`
 FOR A/C EQUIPMENT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-17 Cont ID  
Sent By cthirben Date 2000-03-17 Time 10:11 Rev Time 0.50
Received By cthirben Date 2000-03-17 Time 10:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-07 Cont ID  
Sent By jleech Date 1999-10-07 Time 14:42 Rev Time 0.50
Received By jleech Date 1999-10-07 Time 14:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-02-03 Cont ID  
Sent By tlarge Date 2000-02-03 Time 07:10 Rev Time 0.25
Received By tlarge Date 2000-02-03 Time 07:10 Sent To  
Notes
2001-01-08 00:00:00REVISED PLBG.RISER.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-07 Cont ID  
Sent By tlarge Date 1999-10-07 Time 07:37 Rev Time 0.33
Received By tlarge Date 1999-10-07 Time 07:37 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 1999-12-15 Cont ID  
Sent By jgomez Date 1999-12-15 Time 15:42 Rev Time 1.50
Received By jgomez Date 1999-12-15 Time 15:42 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-REVISE PANEL #23. ARCHITECT'S FRONT
 ELEVATION AT BEDROOM #3 SHOWS A ROUND
 WINDOW ABOVE THE SINGLE HUNG WINDOW.
 PANEL #3 SHOWS SQUARE WINDOW.
 2-MISSING ROOF FRAMING PLAN BY ROYAL
 WALL ENGINEER SHOWING THE HURRICANE
 ANCHOR SCHEDULE.
 3-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS (WITH LEGIBLE DRAWINGS), ROUND
 AND ARCHED WINDOWS.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 1999-12-07 Cont ID  
Sent By jgomez Date 1999-12-07 Time 13:55 Rev Time 1.50
Received By jgomez Date 1999-12-07 Time 13:55 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-ADDRESS COMMENTS ON BUILDING PLAN
 REVIEW NOTES DATED 11/22/99.
 2-REVISE ROYAL WALL DRAWINGS AS REQUIRED
 3-REVISE ROYAL WALL FIRE RATING
 CALCULATIONS.
 4-PROVIDE DETAILED DRAWINGS FOR ROYAL
 WALL PANELS AND KEY PLAN.
 5-PROVIDE COPIES OF THE APPROVED DWGS
 FOR ROYAL WALL PRODUCT APPROVAL BY
 DADE COUNTY.
 6-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS (WITH LEGIBLE DRAWINGS), ROUND
 AND ARCHED WINDOWS.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 1999-11-22 Cont ID  
Sent By jgomez Date 1999-11-22 Time 09:58 Rev Time 2.00
Received By jgomez Date 1999-11-22 Time 09:58 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-ROYAL WALL SYSTEM DOESN'T MEET THE
 REQUIREMENTS FOR SECTIONS 709.2.1.4.4
 AND 709.2.1.4.5 SBC 1997. CALCULATIONS
 ARE INCORRECT.
 2-WHEN WALL FINISHES CONTRIBUTE TO GET
 THE TOTAL FIRE RESISTANCE OF THE WALL,
 THEN, THEY SHALL BE INSTALLED AS PER
 SECTION 709.3.1.6 SBC 1997.
 PROVIDE SPECIFICATIONS.
 3-PROVIDE COMPLETE DETAILS AND SPECS FOR
 FOR CONCRETE PANELS WITH ROUND AND
 ARCHED OPENINGS. SECTION 104.2.2 CITY
 AMENDMENTS TO SBC 1997.
 4-PROVIDE INFORMATION SHOWING THE R
 VALUE (12.9) CALCULATED IN THE ENERGY
 CALCULATIONS.SEC 104.2.2 OF AMENDMENTS
 5-PROVIDE COPIES OF APPROVED DRAWINGS
 REFERENCED IN THE PRODUCT APPROVAL.
 6-PROVIDE COMPLETE DETAILS AND SPECS FOR
 COLUMN AT REAR PORCH. SECTION 104.2.2
 CITY AMENDMENTS.
 7-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION
 SCHEDULE AS PER CITY SAMPLE.
 -PROVIDE DETAILS FOR INSTALLATION OF
 STORM PANELS AT FRONT WINDOWS. SEE
 EXTERIOR SILL DETAIL AND INSTALLATION
 SCHEDULE.
 8-PROVIDE COMPLETE SET OF PRODUCT
 APPROVALS, INCLUDING ENTRY DOORS,
 ROUND AND ARCHED WINDOWS, WINDOW AT
 LIVING AREA, ETC.
 9-UPDATE ALL ENGINEERED TRUSS DRAWINGS.
 CUT AND PASTE IS NOT ACCEPTABLE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 1999-10-20 Cont ID  
Sent By jcaloger Date 1999-10-20 Time 12:25 Rev Time 2.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-10-04 Cont ID  
Sent By gjoyce Date 1999-10-04 Time 08:35 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***