Plan Review Details - Permit 99091007
Plan Review Stops For Permit 99091007
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-07 Cont ID  
Sent By dpalmer Date 1999-10-07 Time 19:53 Rev Time 0.00
Received By dpalmer Date 1999-10-07 Time 19:53 Sent To  
Notes
2001-01-08 00:00:00************PROVISO********************
  
 1)NOTE:NEED TO SUBMIT AIC RATING OF
 EQUIPMENT,MAINS AND BRKRS,AS PER ARTS;
 110-9/215-5 AIC FIGURED FROM FAULT
 CURRENT CALCULATIONS.
 2)NOTE:GROUNDING ELECTRODE CONDUCTOR
 IS ONLY TO GO FROM FIRST MEANS OF DISC.
 TO PANEL.
 3)NOTE: AS PER ART:210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 4)NOTE: AS PER ART: 210-63 RECEPT.REQ`D
 FOR A/C
  
 NEED TO SUBMIT FOR REVIEW AND APPROVAL
 BEFORE FIRST ROUGH ELECTRICAL
 INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-07 Cont ID  
Sent By jleech Date 1999-10-07 Time 14:33 Rev Time 0.50
Received By jleech Date 1999-10-07 Time 14:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-02-03 Cont ID  
Sent By tlarge Date 2000-02-03 Time 07:27 Rev Time 0.00
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISED PLBG.RISER.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-07 Cont ID  
Sent By tlarge Date 1999-10-07 Time 07:42 Rev Time 0.33
Received By tlarge Date 1999-10-07 Time 07:42 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 1999-12-17 Cont ID  
Sent By jgomez Date 1999-12-17 Time 16:42 Rev Time 1.00
Received By jgomez Date 1999-12-17 Time 16:42 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS (WITH LEGIBLE DRAWINGS), ROUND
 AND ARCHED WINDOWS.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 1999-12-03 Cont ID  
Sent By jgomez Date 1999-12-03 Time 12:01 Rev Time 1.00
Received By jgomez Date 1999-12-03 Time 12:01 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-COMMENTS ON CHECKLIST DATED 11/19/99
 WERE NOT ADDRESSED.
 2-ROYAL WALL DRAWINGS WERE NOT REVISED
 SHOWING THE REQUIRED THICKNESS AS PER
 CONVERSATION WITH ROYAL WALL ENGINEER.
 -ROYAL WALL DRAWING #1 IS NOT LEGIBLE.
 DRAWINGS ARE TOO SMALL.
 DOES THIS DRAWING INCLUDE ALL THE
 CONCRETE PANELS USED IN THIS PROJECT.
 3-MISSING ROYAL WALL FLOOR PLAN WHICH
 IDENTIFIES ALL ROYAL WALL PANELS.
 4-ENGINEER SHOULD NOT SEAL THE ORIGINAL
 VELLUM. SEC 61G15-23.002.
 5-PROVIDE COPIES OF APPROVED DRAWINGS
 ON THE PRODUCT APPROVAL.
 6-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS, ARCHED WINDOWS, FIXED WINDOW AT
 DINING AREA.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 1999-11-19 Cont ID  
Sent By jgomez Date 1999-11-19 Time 10:56 Rev Time 2.00
Received By jgomez Date 1999-11-19 Time 10:56 Sent To  
Notes
2001-01-08 00:00:00REVISION:
 ROYAL WALL SYSTEM IN LIEU OF CBS.
  
 CHECKLIST:
 1-FIRE RATED WALL AT ZERO LOT LINE DOES
 NOT MEET THE REQUIREMENTS FOR SECTIONS
 709.2.1.4.4 AND SECTION 709.2.1.4.5
 SBC 1997. (CALCS ARE INCORRECT).
 2-WHEN FINISHES ON CONCRETE WALLS ARE
 ASSUMED TO CONTRIBUTE TO THE TOTAL
 FIRE RESISTANCE OF THE WALL, THEN THE
 INSTALLATION REQUIREMENTS SHALL BE AS
 PER SECTION 709.3.1.6 SBC 1997.
 CODE SECTION 709.2.1.4.6 SBC 1997.
 3-PROVIDE COMPLETE DETAILS AND SPECS FOR
 CONCRETE PANELS WITH ROUND AND ARCHED
 OPENINGS. SEC. 104.2.2 CITY AMENDMENTS
 4-PROVIDE INFORMATION SHOWING THE R
 VALUE (12.9) FOR INSULATION SHOWN.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 5-PROVIDE COPIES OF THE APPROVED DRAWING
 IN NOTED ON THE PRODUCT APPROVAL.
 6-PROVIDE COMPLETE DETAILS AND SPECS FOR
 COLUMN AT REAR PORCH.
 SECTION 104.2.2 CITY AMENDMENTS.
  
 FROM PREVIOUS PROVISO DATED 10/29//99:
 1-PROVIDE FULL SET OF PRODUCT APPROVALS.
 2-UPDATE ALL ENGINEERED TRUSS DRAWINGS.
 CUT AND PASTE IS NOT ACCEPTABLE.
 3-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION
 SCHEDULE AS PER CITY SAMPLE.
 -PROVIDE DETAIL FOR INSTALLATION OF
 STORM PANELS AT FRONT WINDOWS. SEE
 EXTERIOR SILL DETAIL AND INSTALLATION
 SCHEDULE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-10-29 Cont ID  
Sent By jgomez Date 1999-10-29 Time 16:46 Rev Time 1.50
Received By jgomez Date 1999-10-29 Time 16:46 Sent To  
Notes
2001-01-08 00:00:00 
 APPROVED WITH PROVISO:
 1-PLEASE REVISE ALL ORIGINALS SHOWING
 ALL CORRECTIONS/CLARIFICATIONS.
 2-PROVIDE SAFETY GLASS IN LIBRARY WINDOW
 SEC. 2405.2 SBC 1997.
 3-ENTRY DOOR TO HAVE 32" MINIMUM CLEAR
 OPENING. TABLE 1004 SBC 1997.
 4-ENGINEERED TRUSS DRAWINGS:
 -UPDATE ALL DETAILS.
 -UPDATE DESIGN CRITERIA
 -ENGINEER OF RECORD TO REVIEW ALL
 TRUSS DRAWINGS PRIOR TO SUBMITTAL.
 5-REVISE DESIGN CERTIFICATION FOR WIND
 LOAD COMPLIANCE FORM. MEAN ROOF HEIGHT
 IS INCORRECT (21'-0" PLUS O MINUS).
 6-SPECIFY SIZE OF CEILING FANS. TABLE
 6-6 FLORIDA ENERGY CODE 1997 EDITION.
 CREDIT FOR CEILING FANS WAS TAKEN ON
 THE ENERGY CALCULATIONS.
 7-PROVIDE FULL SET OF PRODUCT APPROVALS
 (MASTER PERMIT IS ON HOLD TILL ALL
 PLANS AND PRODUCT APPROVALS ARE
 COMPLETELY PREPARED).
 8-STORM PANELS:
 PROVIDE A COMPLETE INSTALLATION
 SCHEDULE,AS PER CITY SAMPLE, ATTACHED,
 AND KEY PLAN. HIGHLIGHT SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR SCHED.
 9-PROVIDE ATTIC ACCESS AT MAIN ROOF.
 SEC. 2309.6 SBC 1997.
 10-PROVIDE COMPLETE SPECIFICATIONS FOR
 CEILINGS AT FRONT AND BACK PORCH.
 SEC. 104.2.2 CITY AMENDMENTS.
 11-PROVIDE COMPLETE DETAILS AND SPECS
 FOR MOUNTING OF AHU'S.
 SEC. 104.2.2 CITY AMENDMENTS.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-10-04 Cont ID  
Sent By gjoyce Date 1999-10-04 Time 08:38 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***