| Plan Review Stops For Permit 99090901 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-03-29 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-03-29 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
1999-11-03 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-11-03 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-03-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-03-15 |
Time |
12:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-03-15 |
Time |
12:35 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SERVICE RISER CHANGE DELETING TWO | | | FUTUER SERVICES. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-10-18 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
1999-12-27 |
Time |
08:44 |
Rev Time |
1.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PER DVP 10/18/1999 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
1999-09-29 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
1999-12-27 |
Time |
08:43 |
Rev Time |
1.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PER RETT 9/29/99 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-01-26 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-01-26 |
Time |
08:21 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-01-26 |
Time |
08:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
1999-11-17 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-11-17 |
Time |
12:51 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
1999-11-17 |
Time |
12:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-11-17 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-10-12 |
Time |
11:31 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
1999-10-12 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | CORRECTED ON REVISION************ | | | 1) PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 2) PROVIDE AIR BALANCE SCHEDULE PER 1997 | | | SMC 501.2 | | | 3)NOTE: CONDENSATE DRAIN LINE TO BE SIZE | | | D IN ACCORDANCE WITH ACCEPTED ENGINEERIN | | | G PRACTICE (INCREASE SIZE TO ACCOMIDATE | | | ADDITIONAL UNITS) |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2000-01-31 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-01-31 |
Time |
14:13 |
Rev Time |
0.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
1999-12-23 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-12-23 |
Time |
11:25 |
Rev Time |
3.75 |
| Received By |
tlarge |
Date |
1999-12-23 |
Time |
11:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
1999-12-23 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-12-04 |
Time |
12:04 |
Rev Time |
1.00 |
| Received By |
tlarge |
Date |
1999-12-04 |
Time |
12:04 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SHT.27OU-1-SHOWS 8" HORIZONTAL STORM | | | DRAIN SERVING 25,900 SQ.FT.OF ROOF AREA. | | | 8" IS INADEQUATE.COMPLY W/SPC SEC.1108.2 | | | | | | SUBMIT COMPLETE DETAILS INCLUDING STORM | | | RISER DIAGRAM SHOWING SIZE OF ROOF DRAIN | | | AND SQ.FOOTAGE DRAINED BY EACH DRAIN. | | | AND INDICATE SLOPE OF PIPE ON PLAN. | | | COMPLY W/SPC 1108.1,1108.2 | | | | | | PLANS SHOW DRAIN AT SCISSOR LIFT.SUBMIT | | | DETAILS FOR DRAIN.SHOW TERMINATION POINT | | | AND SIZE.(AN INTERCEPTOR MAY BE REQD. | | | IF LIFT IS HYDRAULIC.) | | | | | | VENTS FOR INTERCEPTOR SHALL COMPLY W/SPC | | | SEC.906.2.1.(MUST RISE 6" ABOVE FLOOD | | | LEVEL RIM PRIOR TO OFFSETTING HORIZ.) | | | | | | STORM DRAINAGE CANNOT BE COMBINED W/ | | | SANITARY.(SEE DRAIN AT DUMPSTER. | | | PROVISIONS SHALL BE MADE TO AVOID STORM | | | WATER DRAINING ONTO PAD.)SPC 1106.3. | | | | | | VOID OLD REVISIONS IN PLANS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
1999-12-23 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-11-18 |
Time |
13:20 |
Rev Time |
1.25 |
| Received By |
tlarge |
Date |
1999-11-18 |
Time |
13:20 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SHT.270U-I REFERS TO SHTS.9363A-1 ETC. | | | FOR EXISTING ROOF SCUPPERS.THESE DWGS. | | | HAVE NOT BEEN SUBMITTED.CLARIFY. | | | | | | 8" HORIZONTAL STORM DRAIN IS INADEQUATE | | | TO CARRY PROJECTED ROOF AREA.SUBMIT | | | COMPLETE DETAILS FOR THE STORM DRAINAGE | | | SYSTEM.COMPLY W/TABLES 1108.1 1108.2. | | | (PARAPET WALLS SHALL BE INCLUDED IN | | | CALCULATIONS PER SPC SEC.1108.3) | | | | | | STORM DRAINAGE CANNOT BE COMBINED W/SAN. | | | (SEE DRAIN AT DUMPSTER PAD.)SPC 1106.3 | | | | | | PLANS SHOW DRAIN AT SCISSOR LIFT-SHOW | | | TERMINATION PT.OF DRAIN.(INTERCEPTOR | | | MAY BE REQD. IF LIFT IS OPERATED BY | | | HYDRAULICS).SPC SEC.1004.1 | | | | | | INDICATE SQUARE FOOTAGE OF ROOF DRAINED | | | BY EACH ROOF DRAIN AND INDICATE SLOPE OF | | | PIPE ON PLAN. | | | | | | VENTS FOR INTERCEPTOR SHALL COMPLY W/SPC | | | SEC.906.2.1.(MUST RISE 6" ABOVE FLOOD | | | LEVEL RIM PRIOR TO OFFSETTING HORIZ.) |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
1999-12-23 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-10-11 |
Time |
07:20 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
1999-10-11 |
Time |
07:20 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLANS SHOW DRAIN AT SCISSOR LIFT-SHOW | | | TERMINATION PT.OF DRAIN.(MAY BE REQUIRED | | | TO DRAIN TO INTERCEPTOR IF LIFT IS | | | OPERATED BY HYDRAULICS.)SPC SEC.1004.1. | | | | | | SUBMIT DETAILS FOR SECONDARY ROOF DRAIN- | | | AGE.COMPLY W/SPC SEC.1109. | | | | | | RAIN SENSOR REQD.ON IRRIGATION SYSTEM | | | PER FLA.STATUTE 373.62. | | | | | | INDICATE SQUARE FOOTAGE OF ROOF DRAINED | | | BY ROOF DRAIN AND INDICATE SLOPE OF PIPE | | | COMPLY W/SPC TABLE 1108.1,1108.2. | | | | | | CONTACT RODNEY COMPO AT CITY OF W.P.B. | | | REGIONAL WASTEWATER TREATMENT PLANT FOR | | | REQS.OF GREASE INTERCEPTOR.(561)835-7423 |
|
|