Plan Review Details - Permit 99090901
Plan Review Stops For Permit 99090901
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-03-29 Cont ID  
Sent By lmartine Date 2000-03-29 Time 14:13 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-11-03 Cont ID  
Sent By hpiskura Date 1999-11-03 Time 10:19 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-15 Cont ID  
Sent By dpalmer Date 2000-03-15 Time 12:35 Rev Time 0.00
Received By dpalmer Date 2000-03-15 Time 12:35 Sent To  
Notes
2001-01-08 00:00:00SERVICE RISER CHANGE DELETING TWO
 FUTUER SERVICES.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-18 Cont ID  
Sent By lsmith Date 1999-12-27 Time 08:44 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER DVP 10/18/1999

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-09-29 Cont ID  
Sent By lsmith Date 1999-12-27 Time 08:43 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER RETT 9/29/99

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-01-26 Cont ID  
Sent By ndenmark Date 2000-01-26 Time 08:21 Rev Time 0.25
Received By ndenmark Date 2000-01-26 Time 08:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-11-17 Cont ID  
Sent By ndenmark Date 1999-11-17 Time 12:51 Rev Time 0.50
Received By ndenmark Date 1999-11-17 Time 12:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-17 Cont ID  
Sent By ndenmark Date 1999-10-12 Time 11:31 Rev Time 0.50
Received By ndenmark Date 1999-10-12 Time 11:31 Sent To  
Notes
2001-01-08 00:00:00CORRECTED ON REVISION************
 1) PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2) PROVIDE AIR BALANCE SCHEDULE PER 1997
 SMC 501.2
 3)NOTE: CONDENSATE DRAIN LINE TO BE SIZE
 D IN ACCORDANCE WITH ACCEPTED ENGINEERIN
 G PRACTICE (INCREASE SIZE TO ACCOMIDATE
 ADDITIONAL UNITS)

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-01-31 Cont ID  
Sent By pschmitz Date 2000-01-31 Time 14:13 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 1999-12-23 Cont ID  
Sent By tlarge Date 1999-12-23 Time 11:25 Rev Time 3.75
Received By tlarge Date 1999-12-23 Time 11:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 1999-12-23 Cont ID  
Sent By tlarge Date 1999-12-04 Time 12:04 Rev Time 1.00
Received By tlarge Date 1999-12-04 Time 12:04 Sent To  
Notes
2001-01-08 00:00:00SHT.27OU-1-SHOWS 8" HORIZONTAL STORM
 DRAIN SERVING 25,900 SQ.FT.OF ROOF AREA.
 8" IS INADEQUATE.COMPLY W/SPC SEC.1108.2
  
 SUBMIT COMPLETE DETAILS INCLUDING STORM
 RISER DIAGRAM SHOWING SIZE OF ROOF DRAIN
 AND SQ.FOOTAGE DRAINED BY EACH DRAIN.
 AND INDICATE SLOPE OF PIPE ON PLAN.
 COMPLY W/SPC 1108.1,1108.2
  
 PLANS SHOW DRAIN AT SCISSOR LIFT.SUBMIT
 DETAILS FOR DRAIN.SHOW TERMINATION POINT
 AND SIZE.(AN INTERCEPTOR MAY BE REQD.
 IF LIFT IS HYDRAULIC.)
  
 VENTS FOR INTERCEPTOR SHALL COMPLY W/SPC
 SEC.906.2.1.(MUST RISE 6" ABOVE FLOOD
 LEVEL RIM PRIOR TO OFFSETTING HORIZ.)
  
 STORM DRAINAGE CANNOT BE COMBINED W/
 SANITARY.(SEE DRAIN AT DUMPSTER.
 PROVISIONS SHALL BE MADE TO AVOID STORM
 WATER DRAINING ONTO PAD.)SPC 1106.3.
  
 VOID OLD REVISIONS IN PLANS.

Review Stop P PLUMBING
Rev No 2 Status N Date 1999-12-23 Cont ID  
Sent By tlarge Date 1999-11-18 Time 13:20 Rev Time 1.25
Received By tlarge Date 1999-11-18 Time 13:20 Sent To  
Notes
2001-01-08 00:00:00SHT.270U-I REFERS TO SHTS.9363A-1 ETC.
 FOR EXISTING ROOF SCUPPERS.THESE DWGS.
 HAVE NOT BEEN SUBMITTED.CLARIFY.
  
 8" HORIZONTAL STORM DRAIN IS INADEQUATE
 TO CARRY PROJECTED ROOF AREA.SUBMIT
 COMPLETE DETAILS FOR THE STORM DRAINAGE
 SYSTEM.COMPLY W/TABLES 1108.1 1108.2.
 (PARAPET WALLS SHALL BE INCLUDED IN
 CALCULATIONS PER SPC SEC.1108.3)
  
 STORM DRAINAGE CANNOT BE COMBINED W/SAN.
 (SEE DRAIN AT DUMPSTER PAD.)SPC 1106.3
  
 PLANS SHOW DRAIN AT SCISSOR LIFT-SHOW
 TERMINATION PT.OF DRAIN.(INTERCEPTOR
 MAY BE REQD. IF LIFT IS OPERATED BY
 HYDRAULICS).SPC SEC.1004.1
  
 INDICATE SQUARE FOOTAGE OF ROOF DRAINED
 BY EACH ROOF DRAIN AND INDICATE SLOPE OF
 PIPE ON PLAN.
  
 VENTS FOR INTERCEPTOR SHALL COMPLY W/SPC
 SEC.906.2.1.(MUST RISE 6" ABOVE FLOOD
 LEVEL RIM PRIOR TO OFFSETTING HORIZ.)

Review Stop P PLUMBING
Rev No 1 Status N Date 1999-12-23 Cont ID  
Sent By tlarge Date 1999-10-11 Time 07:20 Rev Time 0.65
Received By tlarge Date 1999-10-11 Time 07:20 Sent To  
Notes
2001-01-08 00:00:00PLANS SHOW DRAIN AT SCISSOR LIFT-SHOW
 TERMINATION PT.OF DRAIN.(MAY BE REQUIRED
 TO DRAIN TO INTERCEPTOR IF LIFT IS
 OPERATED BY HYDRAULICS.)SPC SEC.1004.1.
  
 SUBMIT DETAILS FOR SECONDARY ROOF DRAIN-
 AGE.COMPLY W/SPC SEC.1109.
  
 RAIN SENSOR REQD.ON IRRIGATION SYSTEM
 PER FLA.STATUTE 373.62.
  
 INDICATE SQUARE FOOTAGE OF ROOF DRAINED
 BY ROOF DRAIN AND INDICATE SLOPE OF PIPE
 COMPLY W/SPC TABLE 1108.1,1108.2.
  
 CONTACT RODNEY COMPO AT CITY OF W.P.B.
 REGIONAL WASTEWATER TREATMENT PLANT FOR
 REQS.OF GREASE INTERCEPTOR.(561)835-7423