Plan Review Details - Permit 99090699
Plan Review Stops For Permit 99090699
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 1999-11-03 Cont ID  
Sent By hpiskura Date 1999-11-03 Time 14:31 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-10-18 Cont ID  
Sent By hpiskura Date 1999-10-18 Time 10:42 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-18 Cont ID  
Sent By jleahy Date 1999-09-22 Time 14:24 Rev Time 0.45
Received By dpalmer Date 1999-09-22 Time 14:22 Sent To  
Notes
2001-01-08 00:00:00LOAD CALCULATION NOT TO CODE.65% ON
 ALL LOADS, ALSO NEED LOAD CA;C. ON 600A
 MAIN!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
 10/18/99 ELEC.SHEETS ADDED AS PER NOTES.
 LOAD CALCULATIONS OK.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-10-18 Cont ID  
Sent By hpiskura Date 1999-10-18 Time 10:46 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00APP'D ON PLANS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-10-04 Cont ID  
Sent By ndenmark Date 1999-10-04 Time 11:32 Rev Time 0.33
Received By jleech Date 1999-10-04 Time 11:32 Sent To  
Notes
2001-01-08 00:00:00SEPARATE MECHANICAL PERMITS REQUIRED FOR
 HOOD, SUPPRESSION SYSTEM, COOLER AND
 FREEZER. SUBMIT PLANS WITH MECH PERMIT
 APPLICATION

Review Stop P PLUMBING
Rev No 5 Status P Date 1999-12-23 Cont ID  
Sent By tlarge Date 1999-12-23 Time 18:02 Rev Time 0.50
Received By tlarge Date 1999-12-23 Time 18:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 1999-12-07 Cont ID  
Sent By tlarge Date 1999-12-07 Time 15:33 Rev Time 0.50
Received By tlarge Date 1999-12-07 Time 15:33 Sent To  
Notes
2001-01-08 00:00:00 
 PLBG.REVISION-RELOCATE P & T LINE FROM
 EWH & REVISE SANITARY.

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-11-10 Cont ID  
Sent By tlarge Date 1999-11-10 Time 15:24 Rev Time 0.75
Received By tlarge Date 1999-11-10 Time 15:24 Sent To  
Notes
2001-01-08 00:00:00RPOVISO:PERMANENT LADDER REQD.FOR EWH
 PER SPC 501.7

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-11-01 Cont ID  
Sent By tlarge Date 1999-11-01 Time 09:41 Rev Time 2.50
Received By tlarge Date 1999-11-01 Time 09:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-10-08 Cont ID  
Sent By tlarge Date 1999-10-08 Time 14:57 Rev Time 4.50
Received By tlarge Date 1999-10-08 Time 14:57 Sent To  
Notes
2001-01-08 00:00:00SUBMIT OCCUPANT LOAD TO ENSURE
 COMPLIANCE W/SEC.407 AND TABLE 407 OF
 SPC.
  
 HANDICAP STALL SHALL COMPLY W/FACBC SEC.
 4.17.3(SEE EXCEPTION:NEW CONSTRUCTION)
  
 URINAL SHALL BE SCREENED FOR PRIVACY.
 PER SPC SEC.404.3 (LOCATED IN LINE OF
 SIGHT FROM VESTIBULE.)
  
 AMOUNT AND TYPE OF REQD.PLBG. FIXTURES
 SHALL COMPLY W/FLA.STATUTE 553.141(3).
  
 DISPENSERS IN H.C.TOILET STALL SHALL
 COMPLY W/FACBC SEC.4.22.7,4.27,AND FIG.
 30 OF FACBC.
  
 GRAB BAR BEHIND TOILET SHALL COMPLY W/
 FACBC FIG.30.
  
 RECEPTORS RECEIVING DISCHARGE FROM I.W.
 PIPES SHALL COMPLY W/SPC SEC.807.1.3.
 (FLOOR DRAINS NOT PERMITTED.)
  
 SUBMIT MANUF.SHEETS FOR ALL GAS EQUIP.
 EQUIP. SHALL BE LISTED/APPROVED PER STD.
 GAS CODE 402.1.
  
 MAX.TEMP. OF WATER TO RESTROOMS SHALL BE
 110 DEGREES PER FLA.ENERGY CODE SEC.
 412.1.ABCD.2.3.2.
  
 LOCATION OF BACKFLOW DEVICE SHALL BE
 APPROVED BY CITY OF WEST PALM BEACH
 UTILITY DEPT.
  
 CONTACT RODNEY COMPO AT CITY OF WEST
 PALM BEACH REGIONAL WASTEWATER TREATMENT
 PLANT FOR PROPER SIZE OF GREASE TRAP.
 (561)835-7423.
  
 HUB DRAINS ARE NOT PERMITTED PER SPC.
 FLOOR DRAINS SHALL BE INSTALLED.TABLE
 713.1
  
 CIRCUIT AND LOOP SYSTEM SHALL COMPLY W/
 SPC SEC.914.1 AND 920.3.
  
 DRY VENTS ARE NOT PERMITTED PER SPC SEC.
 901.2.
  
 MOP SINK REQUIRES INDIVIDUAL VENT PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.911.1.1
  
 INDICATE TYPE OF PIPE MATERIAL TO BE
 INSTALLED FOR THE GAS SYSTEM AND
 INDICATE IF GAS IS NATURAL OR LP. PER
 S.G.C.SEC.302.
  
 SIZE GAS SUPPLY LINE TO THE APPLIANCE
 ON THE GAS RISER.S.G.C.302.
  
 INDICATE ON PLANS IF ALCOHOL WILL BE
 SERVED ON THE PREMISES.(WILL AFFECT
 FIXTURE REQS.)COMPLY W/TABLE 407 OF SPC.