| 2001-01-08 00:00:00 | SUBMIT OCCUPANT LOAD TO ENSURE |
| | COMPLIANCE W/SEC.407 AND TABLE 407 OF |
| | SPC. |
| | |
| | HANDICAP STALL SHALL COMPLY W/FACBC SEC. |
| | 4.17.3(SEE EXCEPTION:NEW CONSTRUCTION) |
| | |
| | URINAL SHALL BE SCREENED FOR PRIVACY. |
| | PER SPC SEC.404.3 (LOCATED IN LINE OF |
| | SIGHT FROM VESTIBULE.) |
| | |
| | AMOUNT AND TYPE OF REQD.PLBG. FIXTURES |
| | SHALL COMPLY W/FLA.STATUTE 553.141(3). |
| | |
| | DISPENSERS IN H.C.TOILET STALL SHALL |
| | COMPLY W/FACBC SEC.4.22.7,4.27,AND FIG. |
| | 30 OF FACBC. |
| | |
| | GRAB BAR BEHIND TOILET SHALL COMPLY W/ |
| | FACBC FIG.30. |
| | |
| | RECEPTORS RECEIVING DISCHARGE FROM I.W. |
| | PIPES SHALL COMPLY W/SPC SEC.807.1.3. |
| | (FLOOR DRAINS NOT PERMITTED.) |
| | |
| | SUBMIT MANUF.SHEETS FOR ALL GAS EQUIP. |
| | EQUIP. SHALL BE LISTED/APPROVED PER STD. |
| | GAS CODE 402.1. |
| | |
| | MAX.TEMP. OF WATER TO RESTROOMS SHALL BE |
| | 110 DEGREES PER FLA.ENERGY CODE SEC. |
| | 412.1.ABCD.2.3.2. |
| | |
| | LOCATION OF BACKFLOW DEVICE SHALL BE |
| | APPROVED BY CITY OF WEST PALM BEACH |
| | UTILITY DEPT. |
| | |
| | CONTACT RODNEY COMPO AT CITY OF WEST |
| | PALM BEACH REGIONAL WASTEWATER TREATMENT |
| | PLANT FOR PROPER SIZE OF GREASE TRAP. |
| | (561)835-7423. |
| | |
| | HUB DRAINS ARE NOT PERMITTED PER SPC. |
| | FLOOR DRAINS SHALL BE INSTALLED.TABLE |
| | 713.1 |
| | |
| | CIRCUIT AND LOOP SYSTEM SHALL COMPLY W/ |
| | SPC SEC.914.1 AND 920.3. |
| | |
| | DRY VENTS ARE NOT PERMITTED PER SPC SEC. |
| | 901.2. |
| | |
| | MOP SINK REQUIRES INDIVIDUAL VENT PER |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.911.1.1 |
| | |
| | INDICATE TYPE OF PIPE MATERIAL TO BE |
| | INSTALLED FOR THE GAS SYSTEM AND |
| | INDICATE IF GAS IS NATURAL OR LP. PER |
| | S.G.C.SEC.302. |
| | |
| | SIZE GAS SUPPLY LINE TO THE APPLIANCE |
| | ON THE GAS RISER.S.G.C.302. |
| | |
| | INDICATE ON PLANS IF ALCOHOL WILL BE |
| | SERVED ON THE PREMISES.(WILL AFFECT |
| | FIXTURE REQS.)COMPLY W/TABLE 407 OF SPC. |