Plan Review Details - Permit 99090628
Plan Review Stops For Permit 99090628
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-10-13 Cont ID  
Sent By hpiskura Date 1999-10-13 Time 08:30 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 1999-11-01 Cont ID  
Sent By jleahy Date 1999-11-01 Time 08:51 Rev Time 0.00
Received By jleahy Date 2000-01-12 Time 10:48 Sent To  
Notes
2001-01-08 00:00:001)NEED DRAWING SHOWING ALL BRANCH CKT.
 NUMBERS ON THE PLAN PRIOR TO FINAL!

Review Stop E ELECTRICAL
Rev No 1 Status F Date 1999-10-07 Cont ID  
Sent By jleahy Date 1999-10-07 Time 10:12 Rev Time 0.45
Received By jleahy Date 1999-10-07 Time 10:03 Sent To  
Notes
2001-01-08 00:00:001) SUBMIT PANEL SCHEDULES FOR A,B,C
  
 2) SUBMIT RISER DIAGRAM
  
 3) NO BRANCH CIRCUIT NUMBERS SHOWN ON
 PLAN!
  
 4) PLANS SHOW NO REFERENCE TO 517 FOR
 RECEPTACLE PLACMENT!!!!!
  
 5) 517-18, 517-19, 517-33 FOR PATIENT
 CARE AREAS!!!! IF THESE DO NOT APPLY
 WHY?????????????????????????????????

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 1999-11-02 Cont ID  
Sent By jcaloger Date 1999-11-02 Time 09:19 Rev Time 0.50
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-11-02 Cont ID  
Sent By jcaloger Date 1999-11-02 Time 09:19 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED BY FIRE 9/24/99

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-01-04 Cont ID  
Sent By ndenmark Date 2000-01-04 Time 15:59 Rev Time 0.25
Received By ndenmark Date 2000-01-04 Time 15:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-11-09 Cont ID  
Sent By ndenmark Date 1999-11-09 Time 10:23 Rev Time 0.25
Received By ndenmark Date 1999-11-09 Time .0:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-09 Cont ID  
Sent By ndenmark Date 1999-10-08 Time 10:37 Rev Time 0.33
Received By ndenmark Date 1999-10-08 Time 10:37 Sent To  
Notes
2001-01-08 00:00:00CORRECTED BY REVISIONA
 CALC-30 CFM PER PERSON REQUIRED FOR AH4
 FAN SHUT DOWN TO BE TIED TO BLDG FIRE
 ALARM OR HORN AND STROBE FOR NOTIFICATIO
 N PER NFPA 90A 4-4.4.2 OR.3.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-01-12 Cont ID  
Sent By tlarge Date 2000-01-12 Time 11:47 Rev Time 0.50
Received By tlarge Date 2000-01-12 Time 11:46 Sent To  
Notes
2001-01-08 00:00:00PLBG.NOT AFFECTED THIS REVISION.
 (AS-BUILTS).

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-11-16 Cont ID  
Sent By tlarge Date 1999-11-16 Time 11:59 Rev Time 0.75
Received By tlarge Date 1999-11-16 Time 11:52 Sent To  
Notes
2001-01-08 00:00:00REVIEWED REVISED PLBG.SHEETS.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-09 Cont ID  
Sent By tlarge Date 1999-10-09 Time 10:58 Rev Time 1.00
Received By tlarge Date 1999-10-09 Time 10:58 Sent To  
Notes
***NONE***