Plan Review Details - Permit 99090596
Plan Review Stops For Permit 99090596
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 1999-11-10 Cont ID  
Sent By hpiskura Date 1999-11-10 Time 11:39 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 1999-10-04 Cont ID  
Sent By hpiskura Date 1999-10-04 Time 09:30 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 1999-10-22 Cont ID  
Sent By dpalmer Date 1999-10-22 Time 06:52 Rev Time 0.00
Received By dpalmer Date 1999-10-22 Time 06:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-09-27 Cont ID  
Sent By jleahy Date 1999-09-27 Time 14:31 Rev Time 0.45
Received By dpalmer Date 1999-09-27 Time 14:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-10-04 Cont ID  
Sent By hpiskura Date 1999-10-04 Time 09:31 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 1999-09-27 Cont ID  
Sent By ndenmark Date 1999-09-27 Time 09:22 Rev Time 0.25
Received By ndenmark Date 1999-09-27 Time 09:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-04-17 Cont ID  
Sent By tlarge Date 2000-04-17 Time 06:56 Rev Time 0.30
Received By tlarge Date 2000-04-17 Time 06:56 Sent To  
Notes
2001-01-08 00:00:00REV.LOCATION OF FIXTURES IN R.R.

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-11-10 Cont ID  
Sent By tlarge Date 1999-11-10 Time 06:52 Rev Time 0.65
Received By tlarge Date 1999-11-10 Time 06:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-10-23 Cont ID  
Sent By tlarge Date 1999-10-23 Time 12:52 Rev Time 0.75
Received By tlarge Date 1999-10-23 Time 12:52 Sent To  
Notes
2001-01-08 00:00:00SUBMIT A WATER RISER FOR REVIEW THAT
 CLEARLY REFLECTS THE ENTIRE SCOPE OF
 PLUMBING WORK BEING DONE.SPC 104.2.1.
  
 SUBMIT TOTAL OCCUPANT LOAD OF STRUCTURE
 AND NOTE ON THE PLAN THE NUMBER OF EXIST
 PLUMBING FIXTURES TO ENSURE COMPLIANCE
 W/SPC TABLE 407.
  
 DRINKING FOUNTAIN REQD.PER SPC TABLE 407
  
 SUBMIT DETAILS FOR THE HANDICAP FIXTURES
 ACCESSIBLE TOILET STALLS SHALL COMPLY
 W/FACBC SEC.4.17.3(SEE EXCEPTION:NEW
 CONSTRUCTION).

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-09-30 Cont ID  
Sent By tlarge Date 1999-09-30 Time 16:30 Rev Time 1.25
Received By tlarge Date 1999-09-30 Time 16:29 Sent To  
Notes
2001-01-08 00:00:00SUBMIT A WATER RISER FOR REVIEW PER SPC
 104.2.1.
  
 SUBMIT DETAILS ON THE HANDICAP FIXTURES.
 ACCESSIBLE STALLS SHALL COMPLY W/FACBC
 SEC.4.17.3(NEW CONSTRUCTION.)
  
 SUBMIT TOTAL OCCUPANT LOAD OF STRUCTURE
 AND NUMBER AND TYPE OF EXISTING PLUMBING
 FIXTURES TO ENSURE COMPLIANCE W/SPC
 TABLE 407.NUMBER OF PLBG.FIXTURES SHALL
 COMPLY W/FLA.STATUTE #553.141.(POTTY
 PARITY.)
  
 WALLS OF RESTROOMS SHALL COMPLY W/SBC
 SEC.1204.2.(NON-ABSORBENT MATERIAL TO 4'

Review Stop Z ZONING
Rev No 1 Status P Date 1999-09-21 Cont ID  
Sent By gjoyce Date 1999-09-21 Time 16:18 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***