Plan Review Details - Permit 99090501
Plan Review Stops For Permit 99090501
Review Stop E ELECTRICAL
Rev No 2 Status P Date 1999-11-05 Cont ID  
Sent By jleahy Date 1999-11-05 Time 15:36 Rev Time 0.45
Received By jleahy Date 1999-11-05 Time 15:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 1999-11-10 Cont ID  
Sent By dpalmer Date 1999-10-07 Time 09:26 Rev Time 0.00
Received By fknapp Date 1999-10-07 Time 09:26 Sent To  
Notes
2001-01-08 00:00:00***************DENIED******************
  
 1)NOTE:AS PER ART:220-3-D-1 ADDITIONS
 OVER 500 SQ.FT. NEED TO HAVE LOAD CALCS.
 2)NOTE;AS PER 250-24-C-1,2,3 SEPARTE
 DISC.MEANS IS REQ`D IF YOU MEET THAT
 CODE ART.IF BATH IS INSTALLED THEN BATH
 REQ`D CIRCUT AND RECEPT.AS PER ART;
 210-52D
  
  
 PLEASE PROVIDE EXISTING RISER DIAGRAM,
 SHOWING SIZE OF SERVICE,WIRE,AND LOADS.
 IF DETACHED GARAGE MEETS THE REQ`MENTS
 OF 250-24C THEN SHOW THE MEANS OF DISC.
 (PANEL) FEED,PIPE SIZE, WIRE,GROUNDING
 ELECTRODE SYSTEM, ETC.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 1999-10-07 Cont ID  
Sent By fknapp Date 1999-11-10 Time 15:06 Rev Time 0.25
Received By jleech Date 1999-10-07 Time 09:11 Sent To  
Notes
2001-01-08 00:00:00SUBMIT A/C PLAN WITH A/C APPLICATION.

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-11-08 Cont ID  
Sent By tlarge Date 1999-11-08 Time 07:12 Rev Time 0.33
Received By tlarge Date 1999-11-08 Time 07:12 Sent To  
Notes
2001-01-08 00:00:00PROVISO:GAS DRAWINGS AND PERMIT REQD.
 PRIOR TO BEGINNING WORK.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-05 Cont ID  
Sent By pschmitz Date 1999-10-05 Time 14:12 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 1999-11-10 Cont ID  
Sent By fknapp Date 1999-11-10 Time 14:45 Rev Time 2.00
Received By fknapp Date 1999-11-10 Time 14:45 Sent To  
Notes
2001-01-08 00:00:00*************PROVISO********************
  
 SBC 104.2.2
  
 1)PROVIDE SITE SPECIFIC PRODUCT APPROVAL
 FOR CUSTOM GARAGE DOORS.
 2)PROVIDE PRODUCT APPROVAL FOR SIDE DOOR
 OF GARAGE
 SUBMIT PRIOR TO INSTALLATION
 3)PROVIDE STORM PANEL INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC
 MOUNTING AND ANCHORS TO BE USED
 UNDER SEPERATE PERMIT

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 1999-11-10 Cont ID  
Sent By fknapp Date 1999-10-07 Time 06:45 Rev Time 3.00
Received By fknapp Date 1999-10-07 Time 07:29 Sent To M
Notes
2001-01-08 00:00:00DENIED:
 SBC 104.2.2
 1)PROVIDE ARCHITECT RAISED SEAL ON ALL
 PLANS.
  
 2)CORRECT PLANS TO MEET ZONING APPROVAL
  
 3)PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVAL FOR THE FOLLOWING:
 WINDOWS
 GARAGE DOOR
 ROOF COVERING
 STORM PANELS WITH INSTALLATION SCHEDU-
 LE & KEY PLAN WITH SPECIFIC MOUNTING
 & ANCHORS TO BE USED
  
 4)PROVIDE OWNER SIGNATURE ON ENERGY
 CALCULATION
  
 5)PROVIDE ROOF SHEATHING NAILING ZONES
 COMPLYING WITH SBC 2306.1
  
 6)PROVIDE SPECIFIC WINDOW AND DOOR BUCK
 CONNECTIONS FOR WIND LOAD RESISTANCE
 SBC 1606

Review Stop Z ZONING
Rev No 1 Status P Date 1999-09-20 Cont ID  
Sent By gjoyce Date 1999-09-20 Time 09:21 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***