Plan Review Details - Permit 99090409
Plan Review Stops For Permit 99090409
Review Stop E ELECTRICAL
Rev No 1 Status N Date 2000-01-07 Cont ID  
Sent By jleahy Date 1999-11-19 Time 13:59 Rev Time 1.00
Received By fknapp Date 1999-11-19 Time 13:43 Sent To  
Notes
2001-01-08 00:00:001- NEED RISER DIAGRAM SHOW ALL SERVICE
 EQUIPMENT.
  
 2- YOU NEED TO SHOW ALL EXISTING OUTLETS
 SO WE KNOW THAT THE BLD. MEETS MIN.
 ELECTRICAL REQUIREMENTS
  
 3- NEED PANEL SCHEDULE(S)
  
 4- PLEASE DESIGNATE WHAT THE USE OF EACH
 IS EX. BEDROOM, LIVINGROOM, ECT.
  
 5- BEDROOMS REQUIRE A SMOKE DETECTOR ON
 THE INSIDE AND OUTSIDE OF EACH BED-
 ROOM!

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-01-07 Cont ID  
Sent By cthirben Date 1999-12-03 Time 10:17 Rev Time 0.50
Received By fknapp Date 1999-12-03 Time 10:16 Sent To  
Notes
2001-01-08 00:00:00SHOW DUCT SIZES AND CFM OUTPUT

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-01-06 Cont ID  
Sent By tlarge Date 2000-01-06 Time 11:04 Rev Time 0.75
Received By tlarge Date 2000-01-06 Time 11:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-01-06 Cont ID  
Sent By tlarge Date 1999-11-23 Time 07:19 Rev Time 0.65
Received By tlarge Date 1999-11-23 Time 07:19 Sent To  
Notes
2001-01-08 00:00:00SUBMIT A GAS RISER DIAGRAM FOR REVIEW.
 SHOW TYPE OF PIPING MATERIAL,ALL LINE
 SIZES,BTU LOAD OF EACH APPLIANCE AND
 TOTAL BTU LOAD ON SYSTEM.INDICATE ON
 PLAN HOW PIPING WILL BE INSTALLED UNDER
 BLDG.COMPLY W/S.G.C. SEC.308.3.1,308.3.2
  
 SUBMIT A SANITARY RISER DIAGRAM THAT
 CLEARLY SHOWS ALL NEW WORK.COUNTYWIDE
 AMENDMENTS TO STD.GAS CODE SEC.104.2.1.
  
 PLBG.FIXTURES LOCATED DOWNSTREAM OF
 WATER CLOSETS SHALL BE VENTED PER SPC
 913.2.
  
 GAS INSTALLATION SHALL BE PERFORMED BY
 QUALIFIED PERSONNEL PER NFPA 54 SEC.1.4.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-01-07 Cont ID  
Sent By fknapp Date 2000-01-07 Time 14:16 Rev Time 6.00
Received By fknapp Date 2000-01-07 Time 14:16 Sent To  
Notes
2001-01-08 00:00:00 
 *****************PROVISO****************
  
 SBC 104.2.2
  
 PROVIDE 2 CURRENT COPIES OF PRODUCT
 APPROVALS FOR:
 1)ALL NEW EXTERIOR WINDOWS AND DOORS
  
 2)STORM PANELS FOR ALL NON-IMPACT
 GLAZING.UNDER SEPERATE PERMIT
  
 PLEASE SUBMIT PRIOR TO INSTALLATION