| Plan Review Stops For Permit 99090379 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2000-02-29 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-02-29 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-01-20 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-01-20 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
1999-10-12 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
1999-10-12 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-09-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-18 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-18 |
Time |
14:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-07-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-31 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-31 |
Time |
12:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
1999-10-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
1999-10-04 |
Time |
13:32 |
Rev Time |
0.55 |
| Received By |
jleahy |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) SUBFEED TO PANEL "A" TO SMALL OR FUSE | | | TO BIG 240-3 ALLOWS NEXT STANDARD SIZ | | | WHICH IS 350A !!! | | | 2) DINING ROOMS DO NOT HAVE ENOUGH OUT- | | | LETS LOCAL CODE CALLS FOR OUTLETS | | | EVERY 20' ON CENTER!! CHECK OTHER | | | AREAS!! | | | 3) SUBMIT INFORMATION BEFORE 1ST ELECTRI | | | INSPECTION !!!!! | | | 4) ALSO CUT SHEETS FOR FIXTURES. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-05-12 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-05-12 |
Time |
08:47 |
Rev Time |
0.20 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
1999-12-07 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
1999-12-07 |
Time |
07:30 |
Rev Time |
0.20 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
1999-10-08 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
1999-10-08 |
Time |
11:07 |
Rev Time |
0.25 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PER RETT 9/27/99 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
1999-09-27 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
1999-09-27 |
Time |
14:07 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
1999-09-27 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | FAN SHUT DOWN BY DUCT SMOKE DETECTOR W/ | | | NOTIFICATIN BY HORN AND STROBE REQUIRED | | | BATHROOM EXHAUST REQUIRED PER 1997 SMC 5 | | | 503.3.1 | | | SEPARATE PERMITS REQUIRED FOR HOOD, SUPP | | | RESSION, COOLER/FREEZER, ETC. SUBMIT | | | PLANS W/ PERMIT APPLICATION |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2000-08-27 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-08-27 |
Time |
08:48 |
Rev Time |
0.75 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
1999-11-18 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-11-18 |
Time |
07:28 |
Rev Time |
1.00 |
| Received By |
tlarge |
Date |
1999-11-18 |
Time |
07:28 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DRY VENTS NOT PERMITTED.SPC 906.2.1. | | | | | | MAX.20 FIXTURE UNITS PERMITTED TO | | | DISCHARGE INTO 3" HORIZ.BRANCH PER SPC | | | TABLE 714.1.,714.2. | | | | | | SIZE ALL SECTIONS OF THE SANITARY SYSTEM | | | AT SERVING STATION #1.COUNTYWIDE AMEND- | | | MENTS TO STD.PLBG.CODE SEC.104.2.1. | | | | | | INSTALLATION OF CIRCUIT AND LOOP SYSTEM | | | SHALL COMPLY W/SPC 914.1. | | | | | | CLEANOUTS SHALL BE INSTALLED PER SPC SEC | | | 710.2.1. | | | | | | MAX.2 FIXTURES SHALL BE SUPPLIED BY 1/2" | | | C.W.AND 4 FIXTURES BY 1/2" H.W.PER | | | COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE | | | SEC.607.7. | | | | | | SIZING OF GAS SYSTEM SHALL COMPLY W/SGC | | | TABLE 305.4(A). | | | | | | GAS SHUT-OFF VALVES SHALL BE LOCATED | | | BELOW CEILING PER NFPA SEC.3.3.4.VALVE | | | AND UNION ARRANGEMENT SHALL BE INSTALLED | | | PER NFPA SEC.5.5.4. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
1999-11-03 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-11-03 |
Time |
09:57 |
Rev Time |
3.00 |
| Received By |
tlarge |
Date |
1999-11-03 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | COPY OF DEPT.OF BUSINESS REG.STAMP ON | | | OFFICE PLANS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
1999-10-20 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
1999-10-20 |
Time |
10:13 |
Rev Time |
1.50 |
| Received By |
tlarge |
Date |
1999-10-20 |
Time |
10:13 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | MOP SINK REQUIRES INDIVIDUAL VENT PER | | | COUNTYWIDE AMENDMENTS TO STANDARDPLBG. | | | CODE SEC.911.1 | | | | | | PLANS SHALL BE REVIEWED AND APPROVED BY | | | DEPT.OF BUSINESS REGULATION PRIOR TO | | | APPROVAL BY THE CITY OF W.P.B.BLDG.DEPT. | | | PER SPC SEC.101.4.7. | | | | | | FLOOR SINKS BY BUFFET AREA NOT SHOWN ON | | | SANITARY RISER AND ARE NOT PROPERLY | | | VENTED.SPC SEC.908.1 & TABLE 908.1. | | | | | | WATER CLOSETS AND FIXTURE BRANCHES NOT | | | PERMITTED ON WET VENTS PER COUNTYWIDE | | | AMENDMENTS TO PLBG.CODE SEC.911.1. | | | | | | NO MORE THAN 2 WATER CLOSETS ARE | | | PERMITTED ON 3" DRAIN PER TABLES 714.1 & | | | 714.2 FOOTNOTES #3 AND #2. | | | | | | SIZE ALL SECS.OF THE DRAIN, WASTE AND | | | VENT SYSTEM.SPC 104.2.1. | | | | | | SIZE ALL SECTIONS OF THE WATER RISER.SPC | | | SEC.104.2.1. | | | | | | SIZE ALL SECTIONS OF THE GAS RISER PER | | | STD.GAS CODE SEC.302 AND NFPA 54. | | | | | | ALL GAS EQIUPMENT SHALL BE APPROVED PER | | | STD.GAS CODE 402 AND NFPA 54.SUBMIT | | | MANUF.SHEETS. | | | | | | WATER SUPPLY CONTROL SHALL COMPLY W/SPC | | | SEC.610.4.1, 610.4.2. | | | | | | OVER 2 FIXTURES SUPPLIED BY 1/2" C.W. | | | LINE.PER COUNTYWIDE AMENDMENTS SEC.607.7 | | | | | | NO "M" COPPER PERMITTED U/G.PER COUNTY- | | | WIDE AMENDMENTS TO PLBG.CODE SEC.611.3. | | | | | | COMPLY W/PREVIOUS COMMENTS DATED 10/7/99 | | | | | | REVISIONS SHALL BE ATTACHED TO MASTER | | | SET OF PLANS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
1999-10-07 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
1999-10-07 |
Time |
10:34 |
Rev Time |
1.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW UNSAT | | | (1)CONTACT HOTEL BUSINESS REGULATION | | | FOR THEIR APPROVAL 954-958-5520 | | | (2)GAS ISOMETRIC,EMERGENCY VALVE TO BE | | | BELOW CEILING,UNION DOWN STREAM OF | | | MANUAL SHUT OFF,SHOW PIPE SIZES. | | | (3) SHOW LOCATION OF EXISTING GREASE | | | TRAP, SIZE,PUMP OUT & CERTIFY. | | | END OF COMMENTS |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-02-08 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-02-08 |
Time |
06:48 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED BY ANGELA JONES |
|
|