Plan Review Details - Permit 99090379
Plan Review Stops For Permit 99090379
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-02-29 Cont ID  
Sent By lmartine Date 2000-02-29 Time 13:52 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-01-20 Cont ID  
Sent By lmartine Date 2000-01-20 Time 13:51 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-10-12 Cont ID  
Sent By hpiskura Date 1999-10-12 Time 10:32 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-09-18 Cont ID  
Sent By dpalmer Date 2000-09-18 Time 14:11 Rev Time 0.00
Received By dpalmer Date 2000-09-18 Time 14:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-31 Cont ID  
Sent By dpalmer Date 2000-07-31 Time 12:16 Rev Time 0.00
Received By dpalmer Date 2000-07-31 Time 12:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-04 Cont ID  
Sent By jleahy Date 1999-10-04 Time 13:32 Rev Time 0.55
Received By jleahy Date   Time   Sent To  
Notes
2001-01-08 00:00:001) SUBFEED TO PANEL "A" TO SMALL OR FUSE
 TO BIG 240-3 ALLOWS NEXT STANDARD SIZ
 WHICH IS 350A !!!
 2) DINING ROOMS DO NOT HAVE ENOUGH OUT-
 LETS LOCAL CODE CALLS FOR OUTLETS
 EVERY 20' ON CENTER!! CHECK OTHER
 AREAS!!
 3) SUBMIT INFORMATION BEFORE 1ST ELECTRI
 INSPECTION !!!!!
 4) ALSO CUT SHEETS FOR FIXTURES.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-05-12 Cont ID  
Sent By rturnque Date 2000-05-12 Time 08:47 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 1999-12-07 Cont ID  
Sent By rturnque Date 1999-12-07 Time 07:30 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-10-08 Cont ID  
Sent By lsmith Date 1999-10-08 Time 11:07 Rev Time 0.25
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PER RETT 9/27/99

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-27 Cont ID  
Sent By ndenmark Date 1999-09-27 Time 14:07 Rev Time 0.25
Received By ndenmark Date 1999-09-27 Time 14:07 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR W/
 NOTIFICATIN BY HORN AND STROBE REQUIRED
 BATHROOM EXHAUST REQUIRED PER 1997 SMC 5
 503.3.1
 SEPARATE PERMITS REQUIRED FOR HOOD, SUPP
 RESSION, COOLER/FREEZER, ETC. SUBMIT
 PLANS W/ PERMIT APPLICATION

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-08-27 Cont ID  
Sent By pschmitz Date 2000-08-27 Time 08:48 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 1999-11-18 Cont ID  
Sent By tlarge Date 1999-11-18 Time 07:28 Rev Time 1.00
Received By tlarge Date 1999-11-18 Time 07:28 Sent To  
Notes
2001-01-08 00:00:00DRY VENTS NOT PERMITTED.SPC 906.2.1.
  
 MAX.20 FIXTURE UNITS PERMITTED TO
 DISCHARGE INTO 3" HORIZ.BRANCH PER SPC
 TABLE 714.1.,714.2.
  
 SIZE ALL SECTIONS OF THE SANITARY SYSTEM
 AT SERVING STATION #1.COUNTYWIDE AMEND-
 MENTS TO STD.PLBG.CODE SEC.104.2.1.
  
 INSTALLATION OF CIRCUIT AND LOOP SYSTEM
 SHALL COMPLY W/SPC 914.1.
  
 CLEANOUTS SHALL BE INSTALLED PER SPC SEC
 710.2.1.
  
 MAX.2 FIXTURES SHALL BE SUPPLIED BY 1/2"
 C.W.AND 4 FIXTURES BY 1/2" H.W.PER
 COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE
 SEC.607.7.
  
 SIZING OF GAS SYSTEM SHALL COMPLY W/SGC
 TABLE 305.4(A).
  
 GAS SHUT-OFF VALVES SHALL BE LOCATED
 BELOW CEILING PER NFPA SEC.3.3.4.VALVE
 AND UNION ARRANGEMENT SHALL BE INSTALLED
 PER NFPA SEC.5.5.4.

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-11-03 Cont ID  
Sent By tlarge Date 1999-11-03 Time 09:57 Rev Time 3.00
Received By tlarge Date 1999-11-03 Time 09:57 Sent To  
Notes
2001-01-08 00:00:00COPY OF DEPT.OF BUSINESS REG.STAMP ON
 OFFICE PLANS.

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-10-20 Cont ID  
Sent By tlarge Date 1999-10-20 Time 10:13 Rev Time 1.50
Received By tlarge Date 1999-10-20 Time 10:13 Sent To  
Notes
2001-01-08 00:00:00MOP SINK REQUIRES INDIVIDUAL VENT PER
 COUNTYWIDE AMENDMENTS TO STANDARDPLBG.
 CODE SEC.911.1
  
 PLANS SHALL BE REVIEWED AND APPROVED BY
 DEPT.OF BUSINESS REGULATION PRIOR TO
 APPROVAL BY THE CITY OF W.P.B.BLDG.DEPT.
 PER SPC SEC.101.4.7.
  
 FLOOR SINKS BY BUFFET AREA NOT SHOWN ON
 SANITARY RISER AND ARE NOT PROPERLY
 VENTED.SPC SEC.908.1 & TABLE 908.1.
  
 WATER CLOSETS AND FIXTURE BRANCHES NOT
 PERMITTED ON WET VENTS PER COUNTYWIDE
 AMENDMENTS TO PLBG.CODE SEC.911.1.
  
 NO MORE THAN 2 WATER CLOSETS ARE
 PERMITTED ON 3" DRAIN PER TABLES 714.1 &
 714.2 FOOTNOTES #3 AND #2.
  
 SIZE ALL SECS.OF THE DRAIN, WASTE AND
 VENT SYSTEM.SPC 104.2.1.
  
 SIZE ALL SECTIONS OF THE WATER RISER.SPC
 SEC.104.2.1.
  
 SIZE ALL SECTIONS OF THE GAS RISER PER
 STD.GAS CODE SEC.302 AND NFPA 54.
  
 ALL GAS EQIUPMENT SHALL BE APPROVED PER
 STD.GAS CODE 402 AND NFPA 54.SUBMIT
 MANUF.SHEETS.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1, 610.4.2.
  
 OVER 2 FIXTURES SUPPLIED BY 1/2" C.W.
 LINE.PER COUNTYWIDE AMENDMENTS SEC.607.7
  
 NO "M" COPPER PERMITTED U/G.PER COUNTY-
 WIDE AMENDMENTS TO PLBG.CODE SEC.611.3.
  
 COMPLY W/PREVIOUS COMMENTS DATED 10/7/99
  
 REVISIONS SHALL BE ATTACHED TO MASTER
 SET OF PLANS.

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-10-07 Cont ID  
Sent By pschmitz Date 1999-10-07 Time 10:34 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW UNSAT
 (1)CONTACT HOTEL BUSINESS REGULATION
 FOR THEIR APPROVAL 954-958-5520
 (2)GAS ISOMETRIC,EMERGENCY VALVE TO BE
 BELOW CEILING,UNION DOWN STREAM OF
 MANUAL SHUT OFF,SHOW PIPE SIZES.
 (3) SHOW LOCATION OF EXISTING GREASE
 TRAP, SIZE,PUMP OUT & CERTIFY.
 END OF COMMENTS

Review Stop Z ZONING
Rev No 1 Status P Date 2000-02-08 Cont ID  
Sent By lmartine Date 2000-02-08 Time 06:48 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED BY ANGELA JONES