| 2001-01-08 00:00:00 | REVISION: ROYAL WALL SYSTEM IN LIEU OF |
| | MASONRY CONSTRUCTION. |
| | |
| | CHECKLIST: |
| | 1-FIRE RATED WALL AT ZERO LOT LINE DOES |
| | NOT MEET THE REQUIREMENTS FOR SECTION |
| | 709.2.1.4.4 AND SECTION 709.2.1.4.5 |
| | SBC 1997.(CALCS ARE INCORRECT). |
| | 2-WHEN FINISHES ON CONCRETE WALLS ARE |
| | ASSUMED TO CONTRIBUTE TO THE TOTAL |
| | FIRE RESISTANCE OF THE WALL, THEN THE |
| | INSTALLATION REQUIREMENTS SHALL BE AS |
| | PER SECTION 709.3.1.6 SBC 1997. |
| | SECTION 709.2.1.4.6 SBC 1997. |
| | 3-PROVIDE COMPLETE DETAILS AND SPECS FOR |
| | CONCRETE PANELS WITH ROUND AND ARCHED |
| | OPENINGS. SEC. 104.2.2 CITY AMENDMENTS |
| | 4-PROVIDE INFORMATION SHOWING THE R |
| | VALUE (12.9) FOR THE INSULATION SHOWN. |
| | SEC. 104.2.2 CITY AMENDMENTS TO SBC/97 |
| | 5-DETERMINE WHICH ROYAL WALL SYSTEM |
| | PRODUCT APPROVAL IS GOING TO BE USED. |
| | DADE COUNTY OR SBCCI. AND PROVIDE |
| | COPIES OF THE APPROVED DRAWINGS. |
| | 6-PROVIDE COMPLETE DETAILS AND SPECS FOR |
| | COLUMN AT COVERED PORCH. |
| | SECTION 104.2.2 CITY AMENDMENTS. |
| | |
| | FROM PREVIOUS PROVISO, DATED 10/13/99: |
| | 1-PROVIDE PRODUCT APPROVAL FOR: |
| | FIXED WINDOW AT LIVING AREA, ENTRY |
| | DOORS, ROUND AND ARCHED WINDOWS. |
| | 2-STORM PANELS: |
| | -PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE AS PER CITY SAMPLE (ATTACHED) |
| | -PROVIDE DETAIL FOR INSTALLATION OF |
| | STORM PANELS AT FRONT WINDOWS. SEE |
| | EXTERIOR SILL DETAIL AND INSTALLATION |
| | SCHEDULE. |
| | 3-TRUSS DRAWINGS: |
| | -UPDATE ALL DETAILS AND ENGINEERED ROOF |
| | TRUSSES. ENGINEERED TRUSSES SHOW CUT |
| | AND PASTE INFORMATION SHOWING THE |
| | DESIGN CRITERIA TO BE SBC 1997. |
| | THIS IS NOT ACCEPTABLE. |
| | -CLARIFY/REVISE IF TRUSS FGT4 IS ONE |
| | PLY OR TWO PLYS. |