Plan Review Details - Permit 99090078
Plan Review Stops For Permit 99090078
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-04 Cont ID  
Sent By dpalmer Date 1999-10-04 Time 16:58 Rev Time 0.00
Received By dpalmer Date 1999-10-04 Time 16:58 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO******************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT FIGURED FROM FAULT CURRENT
 CALCULATIONS AS PER ARTS 110-9/215-5.
 2)NOTE:AS PER ART: 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED.
 3)NOTE:AS PER ART: 250-81 GROUNDING
 ELECTRODE CONDUCTOR REQ`D TO GO TO BLDG.
 STEEL ALSO.
 4)NOTE; NOTE ON RISER DIAGRAM,EQUIPMENT
 GROUND ONLY AFTER FIRST MEANS OF DISC.
 5)NOTE:GFI FOR OPT.WHIRLPOOL TUB AND IS
 TO BE ACCESSIBLE.
  
 NEED TO HAVE THE ABOVE INFORMATION
 SUBMITTED AND APPROVED BEFORE ROUGH
 ELECTRICAL INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-07 Cont ID  
Sent By jleech Date 1999-09-07 Time 10:53 Rev Time 0.50
Received By jleech Date 1999-09-07 Time 10:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-12 Cont ID  
Sent By tlarge Date 1999-10-12 Time 10:51 Rev Time 0.50
Received By tlarge Date 1999-10-12 Time 10:51 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 1999-11-20 Cont ID  
Sent By jgomez Date 1999-11-20 Time 14:44 Rev Time 1.50
Received By jgomez Date 1999-11-20 Time 14:44 Sent To  
Notes
2001-01-08 00:00:00REVISION:
 ROYAL WALL INSTEAD OF MASONRY:
  
 CHECKLIST:
 1-FIRE RATED WALL DOESN'T MEET THE
 REQUIREMENTS FOR SECTIONS 709.2.1.4.4
 AND 709.2.1.4.5 SBC 1997.
 (CALCULATIONS ARE INCORRECT).
 2-WHEN WALL FINISHES CONTRIBUTE TO GET
 THE TOTAL FIRE RESISTANCE OF THE WALL,
 THEN, THEY SHALL BE INSTALLED AS PER
 SECTION 709.3.1.6 SBC 1997.
 3-PROVIDE COMPLETE DETAILS AND SPECS
 FOR CONCRETE PANELS WITH ROUND AND
 ARCHED OPENINGS. SECTION 104.2.2 CITY
 AMENDMENTS TO SBC 1997.
 4-PROVIDE INFORMATION SHOWING THE R
 VALUE (12.9) CALCULATED IN THE ENERGY
 CALCULATIONS.SEC 104.2.2 CITY AMENDMEN
 5-PROVIDE COPIES OF APPROVED DRAWINGS
 REFERENCED ON THE PRODUCT APPROVAL.
 6-PROVIDE COMPLETE DETAILS AND SPECS FOR
 COLUMN AT REAR PORCH.
 SECTION 104.2.2 CITY AMENDMENTS.
  
 FROM PREVIOUS PROVISO:
 1-UPDATE ALL ENGINEERED TRUSSES.
 CUT AND PASTE IS NOT ACCEPTABLE.
 2-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION
 SCHEDULE AS PER CITY SAMPLE.
 -PROVIDE DETAIL FOR INSTALLATION OF
 STORM PANELS AT FRONT WINDOWS. SEE
 EXTERIOR SILL DETAIL AND INSTALLATION
 SCHEDULE.
 3-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS, WINDOW AT DINING AREA.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-10-09 Cont ID  
Sent By jgomez Date 1999-10-09 Time 13:51 Rev Time 2.00
Received By jgomez Date 1999-10-09 Time 13:50 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PLEASE REVISE ALL ORIGINALS SHOWING
 ALL CLARIFICATIONS/CORRECTIONS MARKED
 ON SUBMITTED DRAWINGS.
 2-PROVIDE SAFETY GLASS IN LIBRARY WINDOW
 SEC. 2405.2 SBC 1997
 3-PROVIDE SPECIFICATIONS OF HOW TO
 COMPLY WITH SEC. 402.7.2 SGC 1997 FOR
 INSTALLATION OF GAS APPLIANCES IN THE
 GARAGE.
 4-ENTRY DOOR TO HAVE 32" MINIMUM CLEAR
 OPENING. TABLE 1004 SBC 1997.
 5-PROVIDE TWO COPIES OF ENGINEERED ROOF
 TRUSSES SIGNED AND SEALED AND REVIEWED
 BY DESIGNER OF RECORD.
 6-REVISE DESIGN CERITIFICATION FOR WIND
 LOAD COMPLIANCE FORM. MEAN ROOF HEIGHT
 IS 21"-0" MORE OR LESS.
 7-SPECIFY SIZE OF CEILING FANS. TABLE
 6-6 FLORIDA ENERGY CODE 1997 EDITION.
 CREDIT FOR CEILING FANS WAS TAKEN ON
 ENERGY CALCULATIONS.
 8-PROVIDE PRODUCT APPROVAL FOR WINDOW AT
 DINING AREA. CLARIFY IF WINDOW AT
 LIVING AREA HAS TRUE VERTICAL MULLIONS
 OR FALSE MULLIONS IN ORDER TO VERIFY
 SIZE OF FIXED WINDOW.
 9-STORM PANELS: PROVIDE A COMPLETE
 INSTALLATION SCHEDULE (AS PER CITY
 SAMPLE) AND KEY PLAN.
 10-PROVIDE ATTIC ACCESS TO MAIN ROOF.
 SEC 2309.6 SBC 1997.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-09-03 Cont ID  
Sent By gjoyce Date 1999-09-03 Time 15:33 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***