Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-04 Cont ID  
Sent By dpalmer Date 1999-10-04 Time 16:05 Rev Time 0.00
Received By dpalmer Date 1999-10-04 Time 16:05 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO******************
  
 1)NOTE;AS PER ARTS:110-9/215-5 NEED TO
 SUBMIT AIC RATING FIGURED FROM FAULT
 CURRENT CALCULATIONS.
 2)NOTE;AS PER 1996 NFPA-72 SMOKE
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS IN NEW CONSTRUCTION
 OF DWELLING UNITS.
 3)NOTE:AS PER ART;210-9-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERTOPS ARE TO BE
 GFI/GFI PROTECTED.
 4)NOTE:AS PER ART;210-52 2`6`12` RULE
 APPLIES TO ALL WALL SPACE.
 5)NOTE:AS PER ART;250-81 GROUNDING
 ELECTRODE CONDUCTOR IS TO GOT TO BLDG,
 STEEL ALSO.
  
 ALL THE ABOVE NEEDS TO BE SUBMITTED
 AND APPROVED BEFORE ROUGH ELECTRICAL
 INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-07 Cont ID  
Sent By jleech Date 1999-09-07 Time 09:59 Rev Time 0.50
Received By jleech Date 1999-09-07 Time 09:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-11-18 Cont ID  
Sent By tlarge Date 1999-11-18 Time 20:35 Rev Time 0.50
Received By tlarge Date 1999-11-18 Time 20:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-12-08 Cont ID  
Sent By tlarge Date 1999-10-29 Time 08:34 Rev Time 0.50
Received By sgraham Date 1999-10-29 Time 08:34 Sent To  
Notes
2001-01-08 00:00:00SUBMIT DETAIL OF REINFORCEMENT OF WALLS
 FOR FUTURE INSTALLATION OF GRAB BARS AS
 REQUIRED BY FEDERAL FAIR HOUSING ACT
 24 CFR 100.205 SECTION 3 REQUIREMENT #6.
 NOTE:ALL BATHROOMS WITHIN THE COVERED
 DWELLING SHALL COMPLY.
  
 ALL BATHROOMS IN THE DWELLING UNIT SHALL
 COMPLY WITH THE PROVISIONS OF THE
 FEDERAL FAIR HOUSING ACT 24 CFR 100.205
 (C)(3)(IV) REQ.#7 (2)PARAGRAPH (A)OR(B).
 CLEAR FLOOR SPACE SHALL BE PROVIDED AT
 FIXTURES TO ALLOW A PERSON IN A
 WHEELCHAIR OR OTHER MOBILITY AID USE OF
 THE FIXTURES.CLEAR FLOOR SPACE SHALL BE
 SHOWN ON THE PLANS AND DESIGNATE WHICH
 OPTION OF REQUIREMENT #7(A OR B )IS
 USED.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-12-08 Cont ID  
Sent By tlarge Date 1999-09-11 Time 06:35 Rev Time 0.00
Received By sgraham Date 1999-12-08 Time 11:29 Sent To  
Notes
2001-01-08 00:00:00CLEARLY SHOW ON PLANS THAT UNITS COMPLY
 W/FEDERAL FAIR HOUSING ACT AND FLA.
 STATUTE 760
  
 SANITARY RISER SHALL CORRELATE W/FLOOR
 PLAN.(SEE W/M STACK AREA.)

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-12-07 Cont ID  
Sent By jcaloger Date 1999-10-12 Time 08:40 Rev Time 2.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-12-08 Cont ID  
Sent By sgraham Date 1999-12-08 Time 11:31 Rev Time 1.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***