Plan Review Details - Permit 99081169
Plan Review Stops For Permit 99081169
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-01-04 Cont ID  
Sent By dpalmer Date 2000-01-04 Time 10:40 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00***********SAME PROVISO***************
  
 SEE ORIG. NOTE ATTACHED.
  
 NEED TO BE SUBMITTED FOR REVIEW AND
 APPROVAL BEFORE FIRST ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096
 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 1999-10-19 Cont ID  
Sent By dpalmer Date 1999-10-19 Time 09:06 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00RESUBMITTED AND THE PROVISO NOTES
 WERE NOT DONE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-08 Cont ID  
Sent By dpalmer Date 1999-10-08 Time 06:20 Rev Time 0.00
Received By dpalmer Date 1999-10-08 Time 06:20 Sent To  
Notes
2001-01-08 00:00:00*******************PROVISO**************
  
 1)NOTE:AS PER ARTS:110-9/215-5 NEED TO
 SUBMIT AIC RATING OF EQUIPMENT,MAINS AND
 BRKRS. AIC RATING IS FIGURED FRON FAULT
 CURRENT CALCULATIONS.
 2)NOTE;OUTLETS IN LAUNDRY ROOM AND
 GARAGE ARE REQ`D TO BE GFI/GFI PROTECTED
 3)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 4)NOTE:GROUNDING ELECTRODE CONDUCTOR IS
 REQ`D TO GO TO BLDG.STEEL ALSO.AS PER
 ART:250-81
 5)NOTE:OUTLET SPACING IS TO CONFORM TO
 ART:210-52 2`6`12` RULE.
  
 NEED TO SUBMIT FOR REVIEW AND APPROVAL
 BEFORE FIRST ROUGH ELECTRICAL INSPECTION

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2000-01-12 Cont ID  
Sent By jleech Date 1999-10-07 Time 13:55 Rev Time 0.00
Received By cthirben Date 2000-01-12 Time 11:20 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 PLANS ARE STILL NOT LIKE FLOOR PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-01-12 Cont ID  
Sent By jleech Date 1999-09-02 Time 13:43 Rev Time 0.50
Received By cthirben Date 1999-09-02 Time 13:42 Sent To  
Notes
2001-01-08 00:00:00A/C PLAN NOT TO BUILDING PLAN.

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-10-07 Cont ID  
Sent By tlarge Date 1999-10-07 Time 06:53 Rev Time 0.33
Received By tlarge Date 1999-10-07 Time 06:53 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-01-12 Cont ID  
Sent By jgomez Date 2000-01-12 Time 18:16 Rev Time 2.50
Received By jgomez Date 2000-01-12 Time 18:16 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 1999-10-20 Cont ID  
Sent By jgomez Date 1999-10-20 Time 13:38 Rev Time 2.00
Received By jgomez Date 1999-10-20 Time 13:38 Sent To D
Notes
2001-01-08 00:00:00SECOND CHECKLIST:
 1-PAY IMPACT FEES TO THE COUNTY.
 2-ARCHITECT'S NAME WAS CROSSED OUT AND
 THERE IS NOT LETTER OF ARCHITECT
 REGARDING SUCH ACTION.
 ALSO, NEED TO REPRINT DRAWINGS WITHOUT
 THE COPYRIGHT STATEMENT.
 3-DELETE THE OPTIONAL PORCH FROM
 ORIGINAL DRAWINGS.
 4-PROVIDE THE DESIGN PRESSURES FOR ALL
 EXTERIOR OPENINGS. SEC. 1606 SBC 1997.
 5-PROVIDE PRODUCT APPROVALS FOR:
 BUTT GLAZING ASSEMBLY, FIREPLACE,
 WINDOW AND DOOR MULLIONS, ENTRY DOOR
 WITH TRANSOM ABOVE ASSEMBLY, FIXED
 WINDOW AT FAMILY AND LIVING ROOM, ROOF
 TILE, CURRENT SLIDING GLASS DOORS
 PRODUCT APPROVAL.
 6-PROVIDE SPECIFICATIONS OF HOW TO
 COMPLY WITH SEC. 402.7 SGC 1997 FOR
 INSTALLATION OF GAS APPLIANCES IN THE
 GARAGE.
 7-PROVIDE COMPLETE INSTALLATION DETAILS
 FOR AHU'S IN ATTIC. SEC 104.2.2 CITY
 AMENDMENTS TO SBC 1997.
 8-PROVIDE COMPLETE INSTALLATION DETAILS
 AND SPECIFICATIONS FOR CONSTRUCTION
 BETWEEN WINDOWS AT FRON ELEVATION OF
 THE HOUSE. SEC. 104.2.2 CITY AMENDMENTS
 9-PROVIDE ATTIC ACCESS.SEC 2309.6 SBC/97
 10-PROVIDE COMPLETE DETAILS AND SPECS
 FOR CONSTRUCTION OF CHIMNEY.
 SEC. 104.2.2 CITY AMENDMENTS.
 11-PROVIDE COMPLETE COLUMN SCHEDULE.
 SEC. 104.2.2 CITY AMENDMENTS.
 12-PROVIDE COMPLETE DETAILS AND SPECS
 FOR FRONT AND REAR PORCHES' CEILING
 CONSTRUCTION. SEC 2504.2 SBC 1997.
 13-SHEET S-2. REVISE DESIGN LOADS AS
 REQUIRED. SEE APPENDIX A OF SBC 1997.
 ALSO, REVISE DESIGN CERTIFICATION FOR
 WIND LOAD COMPLIANCE FORM. MEAN ROOF
 HEIGHT AND DESIGN PRESSURE DON'T MATCH.
 SEE TABLE 1606.2A SBC 1997.
 14-SPECIFY SIZE OF CEILING FANS AS PER
 TABLE 6-6 OF FLORIDA ENERGY CODE, 1997.
 CREDIT IS TAKEN IN ENERGY CALCULATIONS
 FOR CEILING FANS.
 15-FOOTING F2 IS ENCROACHING INTO THE
 NEIGHBOR'S PROPERTY AT ZERO LOT LINE.
 16-STORM PANELS:
 *REVISE INSTALLATION SCHEDULE.
 EG: OPENINGS #1,2,6,7, ETC.
 *REVISE ANCHOR SCHEDULE AS REQUIRED.
 NOT ALL THE STRUTURE IS 3000 PSI CONC.
 SOME AREAS THERE IS CONCRETE BLOCK.
 *PROVIDE DETAIL SHOWING INSTALLATION OF
 STORM PANEL AT FRONT WINDOWS WHERE
 THERE MAY A CONFLICT WITH ELABORATED
 TRIM AROUND THE WINDOWS.
 17-PROVIDE COMPLETE SPECIFICATIONS AND
 DETAILS FOR INSTALLATION OF BUTT
 GLAZING. SEC 104.2.2 CITY AMENDMENTS.
 18-PROVIDE TWO COPIES OF ENGINEERED
 TRUSS DRAWINGS SIGNED AND SEALED AND
 REVIEWED BY THE DESIGNER OF RECORD.
 19-SEE PLANS FOR ADDITIONAL COMMENTS AND
 REVISE ALL ORIGINAL DRAWINGS SHOWING
 THE CLARIFICATIONS/CORRECTIONS AS
 REQUESTED.
 20-OWES $405.32 FOR LOW VALUATION AND
 RADON FEES.
  
 NOTE:
 PLEASE RETURN REVIEWED SET AFTER ALL
 CLARIFICATIONS/CORRECTIONS ARE DONE, IN
 ORDER TO EXPEDITE THE REVIEW PROCESS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 1999-10-02 Cont ID  
Sent By jgomez Date 1999-10-02 Time 16:32 Rev Time 2.00
Received By jgomez Date   Time   Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO THE COUNTY.
 2-ALL DRAWINGS TO BE SIGNED, SEALED AND
 DATED BY ARCHITECT. SEC 104.2.1 CITY
 AMENDMENTS TO SBC 1997.
 3-SPECIFY IF THE OPTIONAL REAR PORCH IS
 GOING TO BE BUILT IN ORDER TO PROPERLY
 ASSESS THE RADON FEES.
 IF SO, PROVIDE COMPLETE CONSTRUCTION
 DETAILS.
 4-PROVIDE THE DESIGN PRESSURES AT ALL
 EXTERIOR OPENINGS. SEC 1606 SBC 1997.
 5-PROVIDE PRODUCT APPROVALS FOR:
 BUTT GLAZING, FIREPLACE, WINDOW AND
 DOOR MULLIONS, ENTRY DOOR ASSEMBLY WITH
 TRANSOM ABOVE, FIXED WINDOW AT FAMILY
 AND LIVING ROOM, ROOF TILE (UNDER A
 SEPARATE PERMIT), SLIDING GLASS DOORS.
 6-PROVIDE SPECIFICATIONS OF HOW TO
 COMPLY WITH SECTION 402.7 SGC 1997 FOR
 INSTALLATION OF GAS APPLIANCES IN GARAG
 7-PROVIDE COMPLETE INSTALLATION DETAILS
 FOR AHU'S IN ATTIC.
 8-PROVIDE COMPLETE INSTALLATION DETAILS
 FOR CONSTRUCTION OF MULLIONS BETWEEN
 WINDOWS AT FRONT OF THE HOUSE(SEE ELEV)
 9-PROVIDE ATTIC ACCESS. SEC 2309.6 SBC
 10-PROVIDE COMPLETE DETAIL/SECTION FOR
 CHIMNEY CONSTRUCTION.
 11-PROVIDE COMPLETE COLUMN SCHEDULE.
 12-SPECIFY CEILING CONSTRUCTION AT FRONT
 AND REAR PORCHES. SEC 2504.2 SBC 1997
 AS PER ASTM C926 AND ASTM C1063.
 13-DESIGN LOADS ON SHEET S2 AND DESIGN
 CERTIFICATION FOR WIND LOAD COMPLIANCE
 FORM ARE DIFFERENT. REVISE AS REQUIRED.
 14-SPECIFY TEH CEILING FANS AS PER
 CREDIT TAKEN IN ENERGY CALCULATIONS.
 15-FOOTING F2 IS ENCROACHING INTO THE
 NEIGHBOR'S PROPERTY AT ZERO LOT LINE.
 REVISE AS REQUIRED.
 16-STORM PANELS:
 *REVISE INSTALLATION SCHEDULE. EG:
 OPENINGS #1,2,6,7.
 *REVISE ANCHOR SCHEDULE. ANCHOR AND
 SPACING SPECIFIED IS GOOD ONLY FOR
 3000 PSI CONCRETE. CONSTRUCTION OF THIS
 HOUSE IS HOLLOW CONCRETE BLOCK.
 *PROVIDE DETAIL SHOWING INSTALLATION
 OF STORM PANEL AT FRONT WINDOWS WHERE
 THERE IS AN ELABORATED TRIM AROUND THEM
 17-PROVIDE COMPLETE SPECIFICATIONS AND
 DETAILS FOR INSTALLATION OF BUTT
 GLAZING. SEC 104.2.1 CITY AMENDMENTS.
 18-SEE PLANS FOR ADDITIONAL COMMENTS.
 19-PROVIDE ENGINEERED TRUSS DRAWINGS.
 REVIEWED BY DESIGNER OF RECORD PRIOR TO
 SUBMITTAL TO THIS OFFICE.

Review Stop Z ZONING
Rev No 1 Status P Date 1999-08-30 Cont ID  
Sent By gjoyce Date 1999-08-30 Time 08:38 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***