Plan Review Details - Permit 99081034
Plan Review Stops For Permit 99081034
Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-10-27 Cont ID  
Sent By ndenmark Date 1999-10-27 Time 12:02 Rev Time 0.33
Received By ndenmark Date 1999-10-27 Time 12:02 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 NEED FAN SHUT DOWN BY DUCT SMOKE DETEC-
 TOR WITH NOTIFICATION BY HORN AND STROBE
 PER NFPA 90A 4-4.4.3
 NEEDS NOTICE OF COMMENCEMENT ON FILE
 PRIOR TO 1ST INSPECTION

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 1999-08-27 Cont ID  
Sent By ndenmark Date 1999-08-27 Time 13:54 Rev Time 0.25
Received By ndenmark Date 1999-08-27 Time 13:54 Sent To  
Notes
2001-01-08 00:00:00DENIED
 NEED DUCT SIZES AND CFM VALUES AT DROPS