Plan Review Details - Permit 99081019
Plan Review Stops For Permit 99081019
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-09-02 Cont ID  
Sent By dpalmer Date 1999-09-02 Time 16:32 Rev Time 0.00
Received By dpalmer Date 1999-09-02 Time 16:32 Sent To P
Notes
2001-01-08 00:00:00***********PROVISO********************
  
 NOTE: NEED TO SUBMIT AIC RATING OF ALL
 EQUIPMENT PANELS,DISC, BREAKERS. NEED TO
 HAVE DRAWN ON PANEL SCHED. AS PER ARTS:
 110-9 AND 215-5
 NOTE: MASTER BEDROOM REQ`S SMOKE
 DETECTOR OUTSIDE AS PER NFPA-72
 2-2.1.1.1
 NOTE:ART 210-63 REQ`S GFI RECEPT. FOR
 A/C EQUIPMENT.
 NOTE:GRNDING ELECTRODE TO BLDG.STEEL,
 AND COLD WATER PIPE AS PER ART:250-81
  
 PLEASE HAVE SUBMITTED AND APPROVED
 BEFORE ROUGH ELECTRICAL INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-02 Cont ID  
Sent By jleech Date 2000-03-02 Time 14:49 Rev Time 0.25
Received By jleech Date 2000-03-02 Time 14:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-02 Cont ID  
Sent By jleech Date 1999-09-02 Time 12:03 Rev Time 0.50
Received By jleech Date 1999-09-02 Time 12:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-09-03 Cont ID  
Sent By dpalmer Date 1999-09-02 Time 16:37 Rev Time 0.50
Received By tlarge Date 1999-09-03 Time 07:32 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-12-01 Cont ID  
Sent By jcaloger Date 1999-10-08 Time 10:54 Rev Time 3.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-09-01 Cont ID  
Sent By gjoyce Date 1999-09-01 Time 10:11 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***