Plan Review Details - Permit 99081017
Plan Review Stops For Permit 99081017
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-09-03 Cont ID  
Sent By dpalmer Date 1999-09-03 Time 08:23 Rev Time 0.00
Received By dpalmer Date 1999-09-03 Time 08:22 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
  
 NOTE:NEED TO SUBMIT AIC RATING OF
 EQUIPMENT, AND BRKRS. ART 110-9 215-5
 NOTE:SMOKE DETECTRORREQ`D OUTSIDE
 MASTER BEDROOM AS PER NFPA-72
 NOTE:WP GFI REC. REQ`D FOR A/C 210-63
 NOTE: GROUNDING ELECTRODE CONDUCTOR
 TO GO TO BLDG.STEEL AND COLD WATER PIPE.
  
 ALL THE ABOVE NEEDS TO BE DONE SUBMITTED
 AND APPROVED BEFORE ROUGH ELECTRICAL
 INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-01-26 Cont ID  
Sent By ndenmark Date 2000-01-26 Time 13:33 Rev Time 0.25
Received By ndenmark Date 2000-01-26 Time 13:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-03 Cont ID  
Sent By ndenmark Date 1999-09-03 Time 08:50 Rev Time 0.25
Received By ndenmark Date 1999-09-03 Time 08:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-09-03 Cont ID  
Sent By tlarge Date 1999-09-03 Time 07:33 Rev Time 0.50
Received By tlarge Date 1999-09-03 Time 07:33 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-11-09 Cont ID  
Sent By jcaloger Date 1999-10-26 Time 09:45 Rev Time 9.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-09-01 Cont ID  
Sent By gjoyce Date 1999-09-01 Time 10:13 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***