Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-10-07 Cont ID  
Sent By dpalmer Date 1999-10-07 Time 06:16 Rev Time 0.00
Received By dpalmer Date 1999-10-07 Time 06:16 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
  
 1)NOTE:AS PER ARTS;110-9/215-5 NEED TO
 HAVE AIC RATING DRAWN ON PANEL SCEDULE
 FIGURED FROM FAULT CURRENT CALCULATIONS
 2)NOTE:AS PER ART;250-81 NEED TO SHOW
 GROUNDING ELECTRODE CONDUCTOR GOING TO
 COLD WATER PIPE AND BLDG.STEEL ALSO.
 3)NOTE:RISER DIAGRAM SHOWS MAIN LUG ONLY
 (MLO) PANEL ,YET PANEL SCHED.SHOWS
 MAIN CIRCUT BRKR.(MCB) PLEASE MATCH
 BOTH. A MAIN BRKR. OR MAIN DISC. IS
 REQ`D.
  
 NEED TO HAVE SUBMITTED FOR REVIEW AND
 APPROVAL BEFORE FIRST ROUGH ELECTRICAL
 INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-03-02 Cont ID  
Sent By jleech Date 2000-03-02 Time 14:36 Rev Time 0.25
Received By jleech Date 2000-03-02 Time 14:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 1999-11-13 Cont ID  
Sent By jleech Date 1999-11-13 Time 09:46 Rev Time 0.50
Received By jleech Date 1999-11-13 Time 09:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-11-13 Cont ID  
Sent By jleech Date 1999-10-05 Time 13:28 Rev Time 0.50
Received By jleech Date 1999-10-05 Time 13:28 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 A/C PLAN IS NOT THE SAME AS FLOOR PLAN.

Review Stop P PLUMBING
Rev No 4 Status P Date 1999-11-17 Cont ID  
Sent By tlarge Date 1999-11-17 Time 12:42 Rev Time 0.50
Received By tlarge Date 1999-11-17 Time 12:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 1999-11-15 Cont ID  
Sent By tlarge Date 1999-11-15 Time 14:19 Rev Time 0.30
Received By tlarge Date 1999-11-15 Time 14:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-11-03 Cont ID  
Sent By tlarge Date 1999-11-03 Time 06:40 Rev Time 0.33
Received By tlarge Date 1999-11-03 Time 06:40 Sent To  
Notes
2001-01-08 00:00:00SANITARY RISER DIAGRAM SHALL CORRELATE
 W/THE ARCHITECTURAL FLOOR PLAN.SPC SEC.
 104.2.1.

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-10-02 Cont ID  
Sent By tlarge Date 1999-10-02 Time 06:17 Rev Time 0.33
Received By tlarge Date 1999-10-02 Time 06:17 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-12-01 Cont ID  
Sent By jcaloger Date 1999-10-18 Time 14:05 Rev Time 6.50
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status A Date 1999-10-18 Cont ID  
Sent By jcaloger Date 1999-10-18 Time 14:06 Rev Time 0.50
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:0010/18APPROVED BY GRACE JOYCE


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved