Plan Review Details - Permit 99080943
Plan Review Stops For Permit 99080943
Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-09-29 Cont ID  
Sent By dpalmer Date 1999-09-29 Time 12:51 Rev Time 0.00
Received By dpalmer Date 1999-09-29 Time 12:51 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT AND BRKRS.AS PER ARTS;215-5/
 110-9
 2)NOTE:AS PER ART:210-8-A-6 ALL RECEPTS.
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 3)NOTE:AS PER ART;250-81 GROUNDING
 ELECTRODE CONDUCTOR TO GOT TO BLDG.
 STEEL ALSO.
 4)NOTE:AS PER 1996-NFPA-72 SMOKE
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS IN NEW CONSTRUCTION.
  
 NEED TO SUBMIT THE ABOVE INFORMATIONN
 FOR APPROVAL BEFORE THE FIRST ROUGH
 ELECTRICAL INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-29 Cont ID  
Sent By jleech Date 1999-09-29 Time 15:00 Rev Time 0.50
Received By jleech Date 1999-09-29 Time 14:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 1999-11-18 Cont ID  
Sent By tlarge Date 1999-11-18 Time 20:36 Rev Time 0.50
Received By tlarge Date 1999-11-18 Time 20:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 1999-10-29 Cont ID  
Sent By tlarge Date 1999-10-29 Time 09:16 Rev Time 0.50
Received By tlarge Date 1999-10-29 Time 09:16 Sent To  
Notes
2001-01-08 00:00:00SUBMIT DETAIL OF REINFORCEMENT OF WALLS
 FOR FUTURE INSTALLATION OF GRAB BARS AS
 REQUIRED BY FEDERAL FAIR HOUSING ACT
 24 CFR 100.205 SEC.3 REQUIREMENT#6.
 NOTE:ALL BATHROOMS WITHIN THE COVERED
 DWELLING UNIT SHALL COMPLY.
  
 ALL BATHROMS IN THE DWELLING UNIT SHALL
 COMPLY W/THE PROVISIONS OF FEDERAL FAIR
 HOUSING ACT 24 CFR 100.205 (C)(3)(IV)
 REQ.#7 (2) PARAGRAPH (A) OR (B).CLEAR
 FLOOR SPACE SHALL BE PROVIDED AT
 FIXTURES TO ALLOW A PERSON IN A WHEEL-
 CHAIR OR OTHER MOBILITY AID USE OF THE
 FIXTURES.CLEAR FLOOR SPACE SHALL BE
 SHOWN ON THE PLANS AND DESIGNATE WHICH
 OPTION OF REQUIREMENT #7 (A OR B) IS
 BEING USED.

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-10-29 Cont ID  
Sent By tlarge Date 1999-10-27 Time 15:13 Rev Time 0.50
Received By tlarge Date 1999-10-27 Time 15:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-08-28 Cont ID  
Sent By tlarge Date 1999-08-28 Time 06:42 Rev Time 1.00
Received By tlarge Date 1999-08-28 Time 06:42 Sent To  
Notes
2001-01-08 00:00:00LAYOUT OF W/M AND LAV.ON RISER DIAGRAM
 DOESN'T MATCH FLOOR PLAN.A SEPARATE
 STACK IS REQD.FOR THE LAV.SPC 104.2.1,
 TABLE 908.
  
 UNITS SHALL COMPLY W/FEDERAL FAIR
 HOUSING ACT/24 CFR 100.205,& FLA.STATUTE
 760.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-12-06 Cont ID  
Sent By jcaloger Date 1999-10-06 Time 11:42 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-08-23 Cont ID  
Sent By gjoyce Date 1999-08-23 Time 16:16 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***