Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-09-23 Cont ID  
Sent By dpalmer Date 1999-09-23 Time 16:43 Rev Time 0.00
Received By dpalmer Date 1999-09-23 Time 16:40 Sent To  
Notes
2001-01-08 00:00:00************PROVISO*********************
  
 1)NOTE:AS PER ART;110-9/215-5 NEED TO
 SUBMIT AIC RATING OF EQUIPMENT AND BRKS.
 ABOVE FIGURED FROM FAULT CURRENT CALCS.
 2)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS.
 3)NOTE:AS PER ART; 250-81 GROUNDING
 ELECTRODE CONDUCTOR IS REQ`D TO GO TO
 BLDG.STEEL ALSO.
 4)NOTE;AS PER ART;210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED.
 5)NOTE;OUTLET SPACING IS TO CONFORM TO
 ART;210-52 2`6`12` RULE.
  
 NEED TO HAVE THE ABOVE SUBMITTED AND
 APPROVED BEFORE FIRST ELECTRICAL
 ROUGH INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-08-27 Cont ID  
Sent By jleech Date 1999-08-27 Time 15:53 Rev Time 0.50
Received By jleech Date 1999-08-27 Time 15:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-11-18 Cont ID  
Sent By tlarge Date 1999-11-18 Time 20:39 Rev Time 0.50
Received By tlarge Date 1999-11-18 Time 20:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 1999-10-29 Cont ID  
Sent By tlarge Date 1999-10-29 Time 05:37 Rev Time 0.50
Received By tlarge Date 1999-10-29 Time 05:37 Sent To  
Notes
2001-01-08 00:00:00SUBMIT DETAIL OF REINFORCEMENT OF WALLS
 FOR FUTURE INSTALLATION OF GRAB BARS AS
 REQUIRED BY FEDERAL FAIR HOUSING ACT
 24 CFR 100.205 SECTION 3 REQUIREMENT #6.
 NOTE:ALL BATHROOMS WITHIN THE COVERED
 DWELLING SHALL COMPLY.
  
 ALL BATHROOMS IN THE DWELLING UNIT SHALL
 SHALL COMPLY WITH THE PROVISIONS OF
 FEDERAL FAIR HOUSING ACT 24 CFR 100.205
 (C)(3)(IV) REQ.#7 (2)PARAGRAPH (A)OR(B).
 CLEAR FLOOR SPACE SHALL BE PROVIDED AT
 FIXTURES TO ALLOW A PERSON IN A
 WHEELCHAIR OR OTHER MOBILITY AID USE OF
 THE FIXTURES.CLEAR FLOOR SPACE SHALL BE
 SHOWN ON THE PLANS AND DESIGNATE WHICH
 OPTION OF REQUIREMENT #7(A OR B) IS
 BEING USED.

Review Stop P PLUMBING
Rev No 1 Status F Date 1999-08-28 Cont ID  
Sent By tlarge Date 1999-08-28 Time 07:32 Rev Time 0.75
Received By tlarge Date 1999-08-28 Time 07:32 Sent To  
Notes
2001-01-08 00:00:00LAYOUT OF W/M AND LAV.ON RISER DIAGRAM
 DOESN'T MATCH FLOOR PLAN.A SEPARATE
 STACK IS REQD.FOR THE LAV.SPC 104.2.1,
 TABLE 908.
  
 UNITS SHALL COMPLY W/FEDERAL FAIR
 HOUSING ACT/24 CFR 100.205 & FLA.STATUTE
 760.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 1999-12-06 Cont ID  
Sent By jcaloger Date 1999-10-06 Time 10:09 Rev Time 1.00
Received By jcaloger Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 1999-10-06 Cont ID  
Sent By gjoyce Date 1999-10-06 Time 10:12 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved