Plan Review Details - Permit 99080839
Plan Review Stops For Permit 99080839
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 1999-09-20 Cont ID  
Sent By hpiskura Date 1999-09-20 Time 16:29 Rev Time 1.50
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 1999-09-27 Cont ID  
Sent By dpalmer Date 1999-09-27 Time 10:55 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00AS PER JAKE LEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 1999-09-27 Cont ID  
Sent By dpalmer Date 1999-09-27 Time 10:56 Rev Time 0.00
Received By dpalmer Date 1999-09-27 Time 10:56 Sent To  
Notes
2001-01-08 00:00:00AS PER RETT T.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 1999-09-03 Cont ID  
Sent By ndenmark Date 1999-09-03 Time 10:29 Rev Time 0.33
Received By ndenmark Date 1999-09-03 Time 10:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 1999-09-25 Cont ID  
Sent By tlarge Date 1999-09-25 Time 07:48 Rev Time 0.65
Received By tlarge Date 1999-09-25 Time 07:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 1999-09-23 Cont ID  
Sent By tlarge Date 1999-09-23 Time 09:22 Rev Time 0.50
Received By tlarge Date 1999-09-23 Time 09:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 1999-09-23 Cont ID  
Sent By tlarge Date 1999-08-31 Time 14:07 Rev Time 1.00
Received By tlarge Date 1999-08-31 Time 14:06 Sent To  
Notes
2001-01-08 00:00:00HORIZONTAL WET VENTS TO RECEIVE
 DISCHARGE FROM FIXTURE DRAINS ONLY PER
 COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE
 SEC.911.1.1
  
 "M"COPPER NOT PERMITTED U/GPER
 COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE
 SEC.611.3.
  
 INDICATE TYPE OF PIPE MATERIAL TO BE
 USED FOR GAS SYSTEM. STD.GAS CODE SEC.
 302.
  
 SHOW LOCATION OF GAS METER AND INDICATE
 SUPPLY PRESSURE OF SYSTEM ON PLANS.
 SGC 305.2
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.(PERMANENT LADDER REQD
 OR HEATER SHALL BE INSTALLED ON FLOOR.
  
 SUBMIT OCCUPANT LOAD AND SQUARE FOOTAGE
 OF BLDG.PER SBC 104.2.1.COMPLY W/TABLE
 407 OF SPC
  
 RESTROOMS SHALL COMPLY W/FLA.STATUTE
 SEC.553.141.(EQUAL NUMBER OF FIXTURES
 REQD.IN WOMANS AS IN MEN'S RESTROOM)
  
 PLANS SHALL BE ROUTED TO DEPT. OF BUS.
 REGULATION PRIOR TO BEING REVIEWED BY
 THIS DEPT.101.4.7.